| 2016-08-04 14:46:57 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) THE PROVIDED SHEETS DO NOT PROVIDE SUFFICIENT DETAIL |
| | FOR A COMPLETE PROJECT REVIEW, SEE ALSO BUILDING |
| | COMMENTS. |
| | |
| | NFPA 1, 5TH EDITION |
| | |
| | 1.7.11 PLANS AND SPECIFICATIONS. |
| | |
| | 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE |
| | PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH |
| | APPLICABLE CODES AND STANDARDS. |
| | |
| | 1.7.11.2 PLANS SHALL BE SUBMITTED TO THE AHJ PRIOR TO |
| | CONSTRUCTION UNLESS OTHERWISE PERMITTED BY 1.7.11.4. |
| | |
| | 1.7.11.3 THE CONSTRUCTION DOCUMENTS FOR EACH PHASE |
| | SHALL BE COMPLETE IN THEMSELVES, SO THAT REVIEW AND |
| | INSPECTION CAN PROPERLY BE MADE. PRELIMINARY PLANS OF |
| | THE TOTAL BUILDING SHALL BE SUBMITTED WITH THE |
| | CONSTRUCTION DOCUMENTS, AND WITH SUFFICIENT DETAIL, SO |
| | THAT PROPER EVALUATION CAN BE MADE. AREAS AND ITEMS NOT |
| | INCLUDED IN THE PHASE TO BE PERMITTED SHALL BE SHOWN AS |
| | NOT INCLUDED. |
| | |
| | |
| | PLEASE PROVIDE SUFFICIENT PLAN DRAWING DETAIL AND |
| | SCALE. |
| | |
| | |
| | 2) THE TECHICAL DATA SHEET FOR PRODUCT GL -5992 FR, |
| | FIRE RETARDANT COATING, PAGE 2 OF 3, SECTION 4.1 |
| | PERFORMANCE DATA UNDER RECOMMENDED USAGE INDICATES |
| | "INTERIOR USE". THE APPLICATION SUBMITTED APPEARS TO BE |
| | EXTERIOR. |
| | |
| | PLEASE CORRECT OR CLARIFY. |
| | |
| | |
| | |
| | |
| | 3) PROVIDE THE APPLICABLE LISTING OR PRODUCT SHEET FOR |
| | THE APPLICABLE ENVIROMENT IN COMPLIANCE WITH NFPA |
| | STANDARDS. |
| | |
| | 12.5.7* FIRE-RETARDANT COATINGS. |
| | 12.5.7.1* THE REQUIRED FLAME SPREAD OR SMOKE |
| | DEVELOPMENT CLASSIFICATION OF EXISTING SURFACES OF |
| | WALLS, PARTITIONS, COLUMNS, AND CEILINGS SHALL BE |
| | PERMITTED TO BE SECURED BY APPLYING APPROVED |
| | FIRE-RETARDANT COATINGS TO SURFACES HAVING HIGHER FLAME |
| | SPREAD RATINGS THAN PERMITTED. SUCH TREATMENTS SHALL BE |
| | TESTED, OR SHALL BE LISTED AND LABELED FOR APPLICATION |
| | TO THE MATERIAL TO WHICH THEY ARE APPLIED, AND SHALL |
| | COMPLY WITH THE REQUIREMENTS OF NFPA 703, STANDARD FOR |
| | FIRE RETARDANT?TREATED WOOD AND FIRE-RETARDANT COATINGS |
| | FOR BUILDING MATERIALS. [101:10.2.6.1] |
| | 12.5.7.2 IN NEW CONSTRUCTION, SURFACES OF WALLS, |
| | PARTITIONS, COLUMNS, AND CEILINGS SHALL BE PERMITTED TO |
| | BE FINISHED WITH FACTORY-APPLIED FIRE-RETARDANT COATED |
| | ASSEMBLIES THAT HAVE BEEN LISTED AND LABELED TO |
| | DEMONSTRATE COMPLIANCE WITH THE FOLLOWING: |
| | (A) A FLAME SPREAD INDEX OF 25 OR LESS, WHEN TESTED IN |
| | ACCORDANCE WITH ASTM E 84, STANDARD TEST METHOD OF |
| | SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS, |
| | OR ANSI/UL 723, STANDARD FOR TEST FOR SURFACE BURNING |
| | CHARACTERISTICS OF BUILDING MATERIALS, |
| | (B) SHOW NO EVIDENCE OF SIGNIFICANT PROGRESSIVE |
| | COMBUSTION WHEN THE TEST IS CONTINUED FOR AN ADDITIONAL |
| | 20-MINUTE PERIOD, AND |
| | (C) RESULT IN A FLAME FRONT THAT DOES NOT PROGRESS MORE |
| | THAN 10 FT 6 IN. (3.2 M) BEYOND THE CENTERLINE OF THE |
| | BURNERS AT ANY TIME DURING THE TEST. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |