| 2016-08-03 10:20:51 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: 2836 FLAGLER |
| | JOB ADDRESS: 2836 FLAGLER |
| | DESCRIPTION: SFR ADDITION |
| | MASTER PERMIT:16070876 |
| | |
| | |
| | 1. PLEASE LABEL ALL SPACES ON THE ELECTRICAL FLOOR PLAN |
| | TO DETERMINE PROPER ELECTRICAL REQUIREMENTS. |
| | 2. NEC 210.52(H): HALLWAYS GREATER THAN 10? SHALL HAVE |
| | AT LEAST 1 RECEPTACLE. |
| | 3. NEC 210.52(A)(2): OUTLETS ARE MISSING IN THE GREAT |
| | ROOM. IF THERE IS NOT ENOUGH WALL SPACE TO MOUNT AN |
| | ELECTRICAL OUTLET, YOU SHALL INSTALL FLOOR BOXES TO |
| | MEET THE MINIMUM SPACING REQUIREMENTS. |
| | 4. NEC 210.70(A)(2)(B): A LIGHT CONTROLLED BY A WALL |
| | SWITCH IS REQUIRED ON THE EXTERIOR DOORS AT THE CABANA |
| | AND REAR STORAGE. |
| | 5. NEC 230.208: INDICATE THE SIZING OF THE PROTECTION |
| | DEVICE FOR THE SERVICE AT THE MDP ON THE RISER DIAGRAM. |
| | 6. NEC 408.36: INDICATE IF PANEL ?A? IS MCB OR MLO ON |
| | THE RISER DIAGRAM. IF MCB INDICATE THE SIZE. |
| | 7. NEC 250.94: YOU SHALL INCLUDE THE REQUIRED |
| | INTER-SYSTEM BONDING TERMINAL AT THE NEW SERVICE |
| | LOCATION AND SO REFLECTED ON THE RISER DIAGRAM. |
| | 8. NEC 210.63: THOUGHT THERE IS NO ELECTRICAL SHEET |
| | INDICATING THE LOCATION OF THE CONDENSING UNITS MOUNTED |
| | ON THE ROOF, I DETERMINED FROM SHEET ?A4? THAT THERE |
| | MAY BE MORE THAN THE REQUIRED 25? FROM THE SERVICE |
| | OUTLET FOR ONE OR TWO OF THE UNITS. MAKE MENTION OF |
| | THIS REQUIREMENT ON THE RESPECTIVE PAGE TO AVOID |
| | MISSING THE REQUIREMENT. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |