| Notes |
| Date |
Text |
| 2016-07-21 15:52:47 | 1ST REVIEW BUILDING | | | PERMIT #16070838 | | | 7/21/16 | | | | | | 1) IDENTIFY ON THE SUBMITTED NOA WHICH SYSTEM IS TO BE | | | INSTALLED, AND SEE GENERAL LIMITATION NOTE #7 ON PAGE | | | 16- PERIMETER AND CORNER AREAS SHALL COMPLY WITH THE | | | ENHANCED UPLIFT PRESSURE REQUIREMENTS OF THESE AREAS. | | | FASTENER DENSITIES SHALL BE INCREASED FOR BOTH | | | INSULATION AND BASE SHEET AS CALCULATED BY A FL. | | | REGISTERED PROFESSIONAL ENGINEER. | | | | | | CHRISTOPHER L. COLE | | | BUILDINGL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|