| 2016-11-02 13:23:44 | 1)2ND REQUEST THE CIVIL DRAWINGS ARE NOT SIGNED AND |
| | SEALED BY THE DESIGN PROFESSIONAL. FL. ADMIN. CODE RULE |
| | 61G15-23.001. IT APPEARS THE CIVIL PAGES WHERE STAMPED |
| | BUT THEY MUST BE PERSONALLY SIGNED AND DATED |
| | |
| | |
| | 19) 2ND REQUEST THE SEAT IN THE ACCESSIBLE SHOWER SHALL |
| | COMPLY WITH THE FAC SEC. 610.3. SUBMIT DETAILS. THE |
| | SEAT SHALL BE OF A FOLDING TYPE. |
| | SEAT SHOWN AT 15" SHOW COMPLIANCE WITH FBC ACC |
| | 610.3 SHOWER COMPARTMENT SEATS. |
| | WHERE A SEAT IS PROVIDED IN A STANDARD ROLL-IN SHOWER |
| | COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE |
| | INSTALLED ON THE SIDE WALL ADJACENT TO THE CONTROLS, |
| | AND SHALL EXTEND FROM THE BACK WALL TO A POINT WITHIN 3 |
| | INCHES (75 MM) OF THE COMPARTMENT ENTRY. WHERE A SEAT |
| | IS PROVIDED IN AN ALTERNATE ROLL-IN TYPE SHOWER |
| | COMPARTMENT, IT SHALL BE A FOLDING TYPE, SHALL BE |
| | INSTALLED ON THE FRONT WALL OPPOSITE THE BACK WALL, AND |
| | SHALL EXTEND FROM THE ADJACENT SIDE WALL TO A POINT |
| | WITHIN 3 INCHES (75 MM) OF THE COMPARTMENT ENTRY. IN |
| | TRANSFER-TYPE SHOWERS, THE SEAT SHALL EXTEND FROM THE |
| | BACK WALL TO A POINT WITHIN 3 INCHES (75 MM) OF THE |
| | COMPARTMENT ENTRY. THE TOP OF THE SEAT SHALL BE 17 |
| | INCHES (430 MM) MINIMUM AND 19 INCHES (485 MM) MAXIMUM |
| | ABOVE THE BATHROOM FINISH FLOOR. SEATS SHALL COMPLY |
| | WITH 610.3.1 OR 610.3.2. |
| | |
| | 20) 2ND REQUEST THE WET BAR/SINK IN THE HANDICAPPED |
| | ACCESSIBLE UNIT SHALL COMPLY WITH THE FAC SECS.212.2, |
| | 606. NO ACCESSIBILITY SHOWN FOR SINK |
| | |
| | 24) 2ND REQUEST THE SHOWER CONTROLS IN THE ACCESSIBLE |
| | SHOWER SHALL COMPLY WITH THE FAC SECS.608.5.3.SHOW THE |
| | DISTANCE OF THE CONTROLS IN RELATION TO THE SEAT, FROM |
| | ADJACENT WALLS, ABOVE THE FLOOR, ETC. |
| | 608.5.2 STANDARD ROLL-IN TYPE SHOWER COMPARTMENTS. |
| | WHERE A SEAT IS PROVIDED, THE CONTROLS, FAUCETS, AND |
| | SHOWER SPRAY UNIT SHALL BE INSTALLED ON THE BACK WALL |
| | ADJACENT TO THE SEAT WALL AND SHALL BE LOCATED 27 |
| | INCHES (685 MM) MAXIMUM FROM THE SEAT WALL ABOVE THE |
| | GRAB BAR, BUT NO HIGHER THAN 48 INCHES. |
| | |
| | 26) 2ND REQUEST SHT. A8.11 DETAIL #5 REFERENCES THE |
| | 2010 FBC /FHA. THESE DETAILS DO NOT APPLY. THE CODE IN |
| | EFFECT IS THE 2014 FBC-ACCESSIBILITY. |
| | |
| | 29) 2ND REQUEST SPEC SUBMITTED ARE NOT FROM MANUFACTURE |
| | SUBMIT SPECIFICATIONS FOR THE PUMPS FOR THE LAUNDRY. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | |
| | 30) 2ND REQUEST SPEC SUBMITTED ARE NOT FROM MANUFACTURE |
| | SUBMIT MANUF. SPECIFICATIONS /DETAILS FOR THE GAS WATER |
| | HEATERS. SUBMIT VENT DETAILS (SIZE, TYPE OF PIPE, |
| | ETC.).COMPLY WITH FGC SEC.502, 503, 504. |
| | |
| | 31) 2ND REQUEST COULD NOT LOCATE ON MECHANICAL PAGES |
| | SUBMIT CALCULATIONS FOR COMBUSTION AIR IN ACCORDANCE |
| | WITH THE 2014 FBC-GAS SEC.304. |
| | |
| | 32) 2ND REQUEST NOT COMPLIED SHOW THE DISTANCE OF THE |
| | GAS WATER HEATER VENTS FROM BUILDING OPENINGS. COMPLY |
| | WITH FGC SEC. 503.6.4. |
| | |
| | 33) 2ND REQUEST SPEC SUBMITTED ARE NOT FROM MANUFACTURE |
| | SUBMIT MANUF. SPECIFICATIONS /DETAILS FOR THE DRYERS. |
| | SUBMIT VENT DETAILS (SIZE, TYPE OF MATERIAL, |
| | TERMINATION POINTS, ETC.). |
| | |
| | 34) 2ND REQUEST COULD NOT LOCATE ON MECHANICAL PAGES |
| | CARBON MONOXIDE SENSORS ARE REQUIRED PER THE 2014 FBC |
| | SEC. 908.7. |
| | |
| | NEW COMMENTS: |
| | |
| | 1. SHT. A7.02 THE ROLL IN SHOWER SHALL BE MIN 30" X 60" |
| | PER FBC ACC SEC 608.2.2 |
| | |
| | 2. SHT 7.02 SHOW CLEAR FLOOR SPACE FOR ROLL IN SHOWER. |
| | PER FBC ACC 608.2.2.1 |
| | |
| | 3. THE ACCESSIBLE SUITE #2 ON THE 2ND FLOOR IS SHOWN AS |
| | A STANDARD ROOM ON THE PLUMBING SHEETS PLEASE CLARIFY. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 4. ON THE PLUMBING SHEETS IT SHOWS A SINK INSIDE THE |
| | SAUNA ON SHT, A7.02 IT SHOWS A SAUNA HEATER PLEASE |
| | CLARIFY . PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. MODEL PS-15-B LINT TRAP IS EQUIPPED WITH A 2" INLET |
| | AND OUTLET YOU WILL BE REQUIRED TO USE A MODEL THAT IS |
| | EQUIPPED WITH A 3" INLET AND OUTLET THE DRAIN FROM THE |
| | LAUNDRY IS REQUIRED TO-BE 3' AND YOU CAN NOT REDUCE THE |
| | PIPE SIZE IN THE DIRECTION OF FLOW. PER FBC PL 406.2 / |
| | 704.2 |
| | |
| | 6. THE PLUMBING SCHEDULE SHOWS P-3 AS A TUB AND IT |
| | SHOWS P-4 AS A SHOWER ON THE FLOOR PLAN AND THE RISER |
| | THE SHOWER IS SHOWN AS A P-3 PLEASE CLARIFY. PER WPB |
| | AMEND TO FBC 107.2.1 |
| | |
| | 7. THE VENT FOR THE HUB DRAIN IN THE TRASH ROOM THAT IS |
| | TERMINATING OUT OF THE SIDE WALL SHALL COMPLY WITH FBC |
| | PL903.5 / 903.6 |
| | |