| Plan Review Notes For Permit 16070837 |
| Permit Number |
16070837 |
|
| Review Stop |
R |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-08-09 15:45:18 | ROOFING PLAN REVIEW | | | W. P. B. PERMIT: 16070837 | | | ADD: 309/317 N. ROSEMARY AVE. | | | CONT: TBD/ TO BE DETERMINED | | | TEL: 305-456-7252 | | | E-MAIL: [email protected] | | | | | | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH | | | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, | | | ADMINISTRATION | | | | | | 1ST REVIEW | | | DATE: SUN. AUGUST 07/2016 | | | ACTION: DENIED | | | .(2) ROOFING APPROVALS WERE SUBMITTED FOR THIS REVIEW. | | | CARLISLE MIRASEAL FLUID APPLIED WATERPROOFING MEMBRANE | | | NOA 13-0129.22 | | | CARLISLE CCW-500-R HOT APPLIED LIQUID MEMBRANE NOA | | | 12-0801.01 | | | IN BOTH APPROVALS THERE ARE MULTIPLE SUB-SYSTEMS AND | | | ASSOCIATED PRESSURES. IN NEITHER REPORT WAS A | | | SUB-SYSTEM AND ASSOCIATED PRESSURES INDICATED. ALSO IN | | | BOTH REPORTS LIMITATION # 9 IS INDICATED NO ENHANCED | | | FASTENING CAN OCCUR. THE PLANS DO NOT INDICATE ROOF TOP | | | PRESSURES FOR ZONES 1,2 & 3. PLEASE PROVIDE PRESSURES | | | IN VASD SINCE THE PRODUCT APPROVALS ARE IN VASD. 2014 | | | FBC- B 1603.1.4 WIND DESIGN DATA. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | CONSTRUCTION SERVICES DIVISION | | | DEVELOPMENT SERVICES DEPARTMENT | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|