| Date |
Text |
| 2016-08-22 04:50:51 | 1) THE CIVIL DRAWINGS ARE NOT SIGNED AND SEALED BY THE |
| | DESIGN PROFESSIONAL. FL. ADMIN. CODE RULE 61G15-23.001. |
| | 2) SEPARATE PLANS/SPECIFICATIONS AND PERMIT WILL BE |
| | REQUIRED FOR THE BACKFLOW PREVENTERS. |
| | 3) THE HUB DRAIN RECEIVING THE DISCHARGE FROM THE |
| | ELEVATOR SUMP SHALL BE EQUIPPED WITH A FLOOR DRAIN. |
| | 2014 FPC SEC. 1002.4. |
| | 4) SUBMIT A CONDENSATE RISER DIAGRAM FOR REVIEW. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 5) SUBMIT A DETAIL FOR THE " CONCRETE SHOWER PAN" AT |
| | THE TERRACE REFERENCED ON THE ARCHITECTURAL SHEETS. WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 6) SUBMIT A DETAIL FOR THE "PLENUM DRAINAGE" REFERENCED |
| | ON THE PLANS. |
| | 7) SHT.A2.05 - IDENTIFY THE PARAMETERS OF THE |
| | INDIVIDUAL ROOF AREAS A-D.WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 8) SHT. A2.05 - CALLS OUT 8 INCH BY 4 INCH SCUPPERS AND |
| | SHT. P1.05 SHOWS 6 INCH BY 4 INCH. CLARIFY. |
| | 9) ROOF DRAINS #2 & #3 APPEAR TO BE MISSING EMERGENCY |
| | OVERFLOW DRAINS/SCUPPERS. SHOW THE LOCATION OF THE |
| | OVERFLOW DRAINS ON THE PLAINS.2014 FPC SEC. 1108. |
| | 10) SUBMIT ROOF DRAINAGE CALCULATIONS THAT SHOW THAT |
| | ONE-HALF THE AREA OF ALL VERTICAL WALLS THAT DIVERT |
| | RAINWATER TO THE ROOF HAS BEEN ADDED TO THE PROJECTED |
| | ROOF AREA FOR THE REQUIRED SIZING OF THE VERTICAL |
| | CONDUCTORS, LEADERS AND HORIZONTAL STORM DRAINAGE |
| | PIPING. FPC SEC.1106.4. |
| | 11) PROVIDE OVERFLOW STORM DRAIN DETAILS FOR STAIR |
| | TOWERS #1 & #2. FPC SEC. 1108. |
| | 12) SUBMIT DETAILS FOR THE SCUPPERS AND OVERFLOW |
| | SCUPPERS. COMPLY WITH 2014 FBC SEC.1503.4.2. |
| | 13) SHT. A7.01 & A8.11 - AS AN FYI, FLORIDA DOES NOT |
| | ENFORCE THE ADA. FLORIDA HAS ITS OWN ACCESSIBILITY CODE |
| | AND CAN BE FOUND IN THE 2014 (5TH EDITION) OF THE |
| | FLORIDA BUILDING CODE, NOT THE 2010 EDITION. ALL |
| | HANDICAPPED ITEMS SHALL COMPLY WITH THE FBC. |
| | 14) COAT HOOKS AND TOWEL BARS SHALL COMPLY AND BE |
| | LOCATED WITHIN THE REACH RANGES MANDATED IN SECS. |
| | 213.3.7, 308.2.1, 308.3.2, 604.8.3, 603.4. |
| | 15) GRAB BARS SHALL BE MEASURED FROM THE FINISH FLOOR |
| | TO THE TOP OF THE GRIPPING SURFACE PER THE FAC SEC. |
| | 609.4. |
| | 16) THE TOILET PAPER DISPENSER SHALL BE LOCATED IN |
| | ACCORDANCE WITH THE FAC SEC. 604.7. |
| | 17) WHERE ARE THE REQUIRED DRINKING FOUNTAINS ON THE |
| | GROUND FLOOR? COMPLY WITH THE 2014 FPC TABLE 403.1. A |
| | MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED IN |
| | ACCORDANCE WITH 2014 FPC TABLE 403.1, FOOTNOTE # (E) |
| | AND THE FAC SEC. 211.2, 602.4, 602.7. |
| | 18) SHT. A7.02 - DETAIL #1 -THE CLEAR FLOOR SPACE FOR |
| | THE WATER CLOSET SHALL COMPLY WITH THE FAC SEC.604.3. |
| | SHOW THIS ON THE PLAN. |
| | 19) THE SEAT IN THE ACCESSIBLE SHOWER SHALL COMPLY WITH |
| | THE FAC SEC. 610.3. SUBMIT DETAILS. THE SEAT SHALL BE |
| | OF A FOLDING TYPE. |
| | 20) THE WET BAR/SINK IN THE HANDICAPPED ACCESSIBLE UNIT |
| | SHALL COMPLY WITH THE FAC SECS.212.2, 606. |
| | 21) SUBMIT SPECIFICATIONS FOR THE "STEAM SHOWER." IS |
| | THIS A SAUNA ALSO? THE STEAM SHOWER IN THE ACCESSIBLE |
| | UNIT SHALL COMPLY WITH FAC SECS. 241, 302, 404.2 & 612. |
| | SUBMIT AN ENLARGED FLOOR PLAN FOR THIS SHOWER. |
| | 22) THE POOL IN THE ACCESSIBLE SUITE SHALL COMPLY WITH |
| | 2014 FAC SEC. 242. |
| | 23) SHT. A7.02 - THE ACCESSIBLE LAVATORY SHALL BE |
| | DESIGNED FOR A FORWARD APPROACH. FAC SECS. 213.3.4 & |
| | 606. |
| | 24) THE SHOWER CONTROLS IN THE ACCESSIBLE SHOWER SHALL |
| | COMPLY WITH THE FAC SECS.608.5.3.SHOW THE DISTANCE OF |
| | THE CONTROLS IN RELATION TO THE SEAT, FROM ADJACENT |
| | WALLS, ABOVE THE FLOOR, ETC. |
| | 25) SHT. A7.02 REFERS TO FAIR HOUSING REQS. THIS |
| | PROJECT DOES FALL UNDER THE PURVIEW OF THE FAIR HOUSING |
| | ACT. REVISE NOTE TO READ 2014 FBC-ACCESSIBILITY VOLUME. |
| | 26) SHT. A8.11 REFERENCES THE 2010 FBC /FHA. THESE |
| | DETAILS DO NOT APPLY. THE CODE IN EFFECT IS THE 2014 |
| | FBC-ACCESSIBILITY. |
| | 27) SUBMIT FACTORY SIZING CALCULATIONS FROM SCHIER FOR |
| | THE LAUNDRY INTERCEPTOR. 2014 FBC SEC. 1003.2. |
| | 28) THE CONNECTION OF THE LAUNDRY SUMP DRAIN TO THE |
| | SANITARY SYSTEM SHALL COMPLY WITH FPC SEC. 712.3.5. |
| | 29) SUBMIT SPECIFICATIONS FOR THE PUMPS FOR THE |
| | LAUNDRY. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 30) SUBMIT MANUF. SPECIFICATIONS /DETAILS FOR THE GAS |
| | WATER HEATERS. SUBMIT VENT DETAILS (SIZE, TYPE OF PIPE, |
| | ETC.).COMPLY WITH FGC SEC.502, 503, 504. |
| | 31) SUBMIT CALCULATIONS FOR COMBUSTION AIR IN |
| | ACCORDANCE WITH THE 2014 FBC-GAS SEC.304. |
| | 32) SHOW THE DISTANCE OF THE GAS WATER HEATER VENTS |
| | FROM BUILDING OPENINGS. COMPLY WITH FGC SEC. 503.6.4. |
| | 33) SUBMIT MANUF. SPECIFICATIONS /DETAILS FOR THE |
| | DRYERS. SUBMIT VENT DETAILS (SIZE, TYPE OF MATERIAL, |
| | TERMINATION POINTS, ETC.). |
| | 34) CARBON MONOXIDE SENSORS ARE REQUIRED PER THE 2014 |
| | FBC SEC. 908.7. |
| | 35) SEPARATE PERMITS ARE REQUIRED FOR THE SWIMMING |
| | POOLS. |
| | 36) SHT. P3.02 - SIZE THE IRRIGATION BRANCHES ON THE |
| | RISER. |
| | 37) SHT. P3.02 - COLD WATER RISERS SHALL HAVE SHUTOFF |
| | VALVES PER FPC SEC.606.1. SEE RISER CW /1 WHICH |
| | SUPPLIES FIXTURE P-6. |
| | 38) SHUT OFF VALVES ARE REQD. ON THE WATER SUPPLIES TO |
| | FIXTURE P-7 IN THE BASEMENT. FPC SEC. 606.1 (5). |
| | 39) SHT. P3.03 - SHOWS RISER S/2 FOR FIXTURE P-4 & SHT. |
| | P1.02 SHOWS RISER S/2 FOR P-3. CLARIFY. |
| | 40) SHT. P1.02 SHOWS RISER S/3 FOR FIXTURE P-4 AND SHT. |
| | P3.03 SHOWS FIXTURE P-3. CLARIFY. |
| | 41) SHT. P3.04 - SIZE THE VENT FOR THE HUB DRAIN AND |
| | SHOW THE CONTINUATION/TERMINATION POINT OF THE VENT. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | 42) SHT. P3.04 - SIZE THE FORCE MAIN FROM THE SANITARY |
| | EJECTOR ON THE RISER. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 43) SHT. P1.01 APPEARS TO SHOW A 2 INCH FORCE MAIN |
| | INSIDE STAIR FS-1. PENETRATIONS OTHER THAN THOSE |
| | NECESSARY FOR THE PURPOSE OF THE EXIT ACCESS STAIRWAY |
| | ENCLOSURE ARE PROHIBITED PER THE 2014 FBC |
| | SEC.1009.3.1.5.1. |
| | 44) SHT. P4.01 - INDICATE THE SIZE OF THE EXPANSION FOR |
| | THE WATER HEATERS. |
| | 45) SHT.P4.01 - WATER HEATER DETAIL - PAN DRAINS ARE |
| | REQUIRED FOR THE WATER HEATERS. DRAINS SHALL COMPLY |
| | WITH FPC SEC.504.7.1 & 504.7.2. |
| | 46)SHT. P4.01 - A FULL OPEN VALVE SHALL BE INSTALLED ON |
| | THE WATER HEATERS. 2014 FPC SEC.606.1 (8). |
| | 47)SHT. P3.05 SHOWS A ONE HALF-INCH DISCHARGE LINE FROM |
| | THE STORM SUMP. THIS IS OBVIOUSLY A TYPOGRAPHICAL |
| | ERROR. PLEASE CORRECT. |
| | 48)INDICATE THE SLOPE OF THE HORIZONTAL STORM DRAINAGE |
| | PIPING ON THE PLANS. COMPLY WITH TABLE 1106.3 OF THE |
| | FPC. |
| | 49)SHT. P3.05 - THERE ARE ROOF DRAINS THAT DO NOT SHOW |
| | THE SQUARE FOOTAGE BEING DRAINED. CLARIFY. |
| | 50)SHT. P3.05 - THE SQUARE FOOTAGE BEING DRAINED BY |
| | EACH DRAIN IS LABELED AS ?FU?. PLEASE CORRECT. |
| | 51)SHOW THE LOCATION OF THE POOL HEATERS ON THE PLANS. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | 52)SHT.A.201B SHOWS A MECHANICAL ROOM. SUPPLY |
| | INFORMATION AS TO WHAT TYPE OF EQUIPMENT WILL BE |
| | LOCATED IN THIS ROOM AND PROVIDE AN EQUIPMENT SCHEDULE. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | 53) INDICATE ON THE PLANS WHAT TYPE OF MATERIALS/ITEMS |
| | WILL BE PLACED IN THE STORAGE ROOM.WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |