| 2016-07-27 11:13:12 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) SHEET LS 1.01 - CONTRUCTION TYPE/OCCUPANCY. PLEASE |
| | PROVIDE INDICATIONS/ VERIFICATIONS/CLARIFICATONS AS TO |
| | THE OCCUPANCY CLASSIFICATION OF THE HOTEL AND THE THE |
| | PARKING GARAGE. THE PARKING GARAGE IS A PARKING |
| | STRUCTURE IN ACCORDANCE OF NFPA 88A AND APPLICABLE |
| | REQUIRMENTS. |
| | |
| | |
| | 28.1.3 MULTIPLE OCCUPANCIES. |
| | 28.1.3.1 MULTIPLE OCCUPANCIES SHALL BE IN ACCORDANCE |
| | WITH 6.1.14. |
| | |
| | 6.1.14 MULTIPLE OCCUPANCIES. |
| | 6.1.14.1 GENERAL. |
| | 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF 6.1.14.1 AND ONE OF THE FOLLOWING: |
| | (1) MIXED OCCUPANCIES ? 6.1.14.3 |
| | (2) SEPARATED OCCUPANCIES ? 6.1.14.4 |
| | |
| | 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY |
| | WHERE THE OCCUPANCIES ARE SEPARATED BY FIRE RESISTANCER |
| | RATED ASSEMBLIES. |
| | 6.1.14.3 MIXED OCCUPANCIES. |
| | 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE |
| | CLASSIFIED AS TO ITS USE IN ACCORDANCE WITH SECTION 6.1 |
| | 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST |
| | RESTRICTIVE REQUIREMENTS OF THE OCCUPANCIES INVOLVED, |
| | UNLESS SEPARATE SAFEGUARDS ARE APPROVED. |
| | |
| | PLEASE PROVIDE VERIFICATION AND THE APPLICABLE |
| | REQUIRMENTS. |
| | |
| | |
| | 2) SHEET LS 1.01 - A PARKING GARAGE IS INDICATED ON THE |
| | GROUND FLOOR. IS IT AN OPEN PAKING STRUCUTRE OR CLOSED |
| | PARKING STRUCTURE? |
| | |
| | PER NFPA 88A STANDARD FORPARKING STRUCTURES 2011 |
| | EDITION- 3.3 GENERAL DEFINITIONS. 3.3.2* PARKING |
| | STRUCTURE. A BUILDING, STRUCTURE, OR PORTION THEREOF |
| | USED FOR THE PARKING, STORAGE, OR BOTH, OF MOTOR |
| | VEHICLES. |
| | 3.3.2.3 PARKING STRUCTURE, ENCLOSED. ANY PARKING |
| | STRUCTURE THAT IS NOT AN OPEN PARKING STRUCTURE. |
| | 3.3.2.4 PARKING STRUCTURE, OPEN. A PARKING STRUCTURE |
| | THAT MEETS THE REQUIREMENTS OF SECTION 5.5. |
| | |
| | PLEASE PROVIDE INDICATIONS/JUSTIFICATION OF TYPE OF |
| | PARKING STRUCTURE AND COMPLIANCE WITH THE REQUIRMENTS. |
| | |
| | |
| | |
| | 3) SHEET LS 1.01 & 2-5 FLOOR PLAN SHEETS. THE MEANS OF |
| | EGRESS SHALL COMPLY WITH NFPA 101 CHAPTER 28, NEW |
| | HOTELS AND DORMITORIE AND ALL APPLICABLE CODES. |
| | EXIT FROM THE HOTEL ROOM CORRIDOR APPEARS TO BE OEPNING |
| | INTO AN OPEN CORRIDOR. |
| | |
| | 28.2.2 MEANS OF EGRESS COMPONENTS. |
| | 28.2.2.1 GENERAL. |
| | 28.2.2.1.1 COMPONENTS OF MEANS OF EGRESS SHALL BE |
| | LIMITED TO THE TYPES DESCRIBED IN 28.2.2.2 THROUGH |
| | 28.2.2.12. |
| | 28.2.2.1.2 IN BUILDINGS, OTHER THAN HIGH-RISE |
| | BUILDINGS, THAT ARE PROTECTED THROUGHOUT BY AN |
| | APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH 28.3.5, EXIT ENCLOSURES SHALL HAVE A |
| | MINIMUM 1-HOUR FIRE RESISTANCE RATING, AND DOORS SHALL |
| | HAVE A MINIMUM 1-HOUR FIRE PROTECTION RATING. |
| | |
| | 28.2.5 ARRANGEMENT OF MEANS OF EGRESS. |
| | 28.2.5.1 ACCESS TO ALL REQUIRED EXITS SHALL BE IN |
| | ACCORDANCE WITH SECTION 7.5, AS MODIFIED BY 28.2.5.2. |
| | |
| | 7.5 ARRANGEMENT OF MEANS OF EGRESS. |
| | 7.5.1 GENERAL. |
| | 7.5.1.1 EXITS SHALL BE LOCATED, AND EXIT ACCESS SHALL |
| | BE ARRANGED, SO THAT EXITS ARE READILY ACCESSIBLE AT |
| | ALL TIMES. |
| | 7.5.1.1.1* WHERE EXITS ARE NOT IMMEDIATELY ACCESSIBLE |
| | FROM AN OPEN FLOOR AREA, CONTINUOUS PASSAGEWAYS, |
| | AISLES, OR CORRIDORS LEADING DIRECTLY TO EVERY EXIT |
| | SHALL BE MAINTAINED AND SHALL BE ARRANGED TO PROVIDE |
| | ACCESS FOR EACH OCCUPANT TO NOT LESS THAN TWO EXITS BY |
| | SEPARATE WAYS OF TRAVEL, UNLESS OTHERWISE PROVIDED IN |
| | 7.5.1.1.3 AND 7.5.1.1.4. |
| | |
| | 28.3.6 CORRIDORS. |
| | 28.3.6.1 WALLS. |
| | 28.3.6.1.1 EXIT ACCESS CORRIDOR WALLS SHALL COMPLY WITH |
| | 28.3.6.1.2 OR 28.3.6.1.3. |
| | 28.3.6.1.2 IN BUILDINGS NOT COMPLYING WITH 28.3.6.1.3, |
| | EXIT ACCESS CORRIDOR WALLS SHALL CONSIST OF FIRE |
| | BARRIERS IN ACCORDANCE WITH SECTION 8.3 THAT HAVE NOT |
| | LESS THAN A 1-HOUR FIRE RESISTANCE RATING. |
| | 28.3.6.1.3 IN BUILDINGS PROTECTED THROUGHOUT BY AN |
| | APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH 28.3.5, CORRIDOR WALLS SHALL HAVE A |
| | MINIMUM?-HOUR FIRE RESISTANCE RATING. |
| | |
| | THE ARRANGEMENTS OF THE EXITS ARE NOT IMMEDIATELY |
| | ACCESSIBLE AND DO NOT MEET THE PROVISIONS INDICATED. |
| | |
| | A PROTECTED CORRIDOR IS REQUIRED OR EACH FLOOR LEVEL. |
| | |
| | |
| | |
| | 4) SHEET LS 1.01 & A 2.01B - A BASEMENT IS INDICATED |
| | WITH ONLY ONE (1) EXIT. |
| | |
| | PER NFPA 101, CHAPTER 28, |
| | |
| | 28.2.4 NUMBER OF MEANS OF EGRESS. |
| | 28.2.4.1 MEANS OF EGRESS SHALL COMPLY WITH ALL OF THE |
| | FOLLOWING, EXCEPT AS OTHERWISE PERMITTED BY 28.2.4.2 |
| | AND 28.2.4.3: |
| | (1) THE NUMBER OF MEANS OF EGRESS SHALL BE IN |
| | ACCORDANCE WITH SECTION 7.4. |
| | (2) NOT LESS THAN TWO SEPARATE EXITS SHALL BE PROVIDED |
| | ON EVERY STORY. |
| | (3) NOT LESS THAN TWO SEPARATE EXITS SHALL BE |
| | ACCESSIBLE FROM EVERY PART OF EVERY STORY. |
| | |
| | 7.4* NUMBER OF MEANS OF EGRESS. |
| | 7.4.1 GENERAL. |
| | 7.4.1.1 THE NUMBER OF MEANS OF EGRESS FROM ANY BALCONY, |
| | MEZZANINE, STORY, OR PORTION THEREOF SHALL BE NOT LESS |
| | THAN TWO, EXCEPT UNDER ONE OF THE FOLLOWING CONDITIONS: |
| | (1) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED WHERE |
| | PERMITTED IN CHAPTERS 11 THROUGH 43. |
| | (2) A SINGLE MEANS OF EGRESS SHALL BE PERMITTED FOR A |
| | MEZZANINE OR BALCONY WHERE THE COMMON PATH OF TRAVEL |
| | LIMITATIONS OF CHAPTERS 11 THROUGH 43 ARE MET. |
| | 7.4.1.2 THE NUMBER OF MEANS OF EGRESS FROM ANY STORY OR |
| | PORTION THEREOF, OTHER THAN FOR EXISTING BUILDINGS AS |
| | PERMITTED IN CHAPTERS 11 THROUGH 43, SHALL BE AS |
| | FOLLOWS: |
| | (1) OCCUPANT LOAD MORE THAN 500 BUT NOT MORE THAN 1000 |
| | ? NOT LESS THAN 3 |
| | (2) OCCUPANT LOAD MORE THAN 1000 ? NOT LESS THAN 4 |
| | |
| | PLEASE PROVIDE A SECOND (2ND) EXIT FORM THE BASEMENT. |
| | |
| | |
| | 5) SHEET LS 1.01 & M 1.00 - THERE IS NO INDICATIONS OF |
| | SMOKE VENTING IN/FROM THE BASEMENT AREA. |
| | |
| | NFPA 101 CHAPTER 11 SPECIAL STRUCTURES AND HIGH-RISE |
| | BUILDINGS |
| | 11.7 UNDERGROUND AND LIMITED ACCESS STRUCTURES. |
| | 11.7.4 ADDITIONAL PROVISIONS FOR UNDERGROUND |
| | STRUCTURES. |
| | 11.7.4.1 A STRUCTURE OR PORTION OF A STRUCTURE SHALL |
| | NOT BE CONSIDERED AN UNDERGROUND STRUCTURE IF THE STORY |
| | IS PROVIDED, ON NOT LESS THAN TWO SIDES, WITH NOT LESS |
| | THAN 20 FT2 (1.9 M2) OF EMERGENCY ACCESS OPENING |
| | LOCATED ENTIRELY ABOVE THE ADJOINING FINISHED GROUND |
| | LEVEL IN EACH 50 LINEAL FT (15 LINEAL M) OF EXTERIOR |
| | ENCLOSING WALL AREA. |
| | 11.7.4.2 THE REQUIREMENTS OF 11.7.3 SHALL APPLY. |
| | 11.7.4.4 THE UNDERGROUND PORTIONS OF AN UNDERGROUND |
| | STRUCTURE,OTHER THAN AN EXISTING UNDERGROUND STRUCTURE, |
| | SHALL BE PROVIDED WITH APPROVED AUTOMATIC SMOKE VENTING |
| | IN ACCORDANCE WITH SECTION 9.3 WHERE THE UNDERGROUND |
| | STRUCTURE HAS THE FOLLOWING FEATURES: |
| | (1) OCCUPANT LOAD OF MORE THAN 100 PERSONS IN THE |
| | UNDERGROUND PORTIONS OF THE STRUCTURE |
| | (2) FLOOR LEVEL USED FOR HUMAN OCCUPANCY LOCATED MORE |
| | THAN 30 FT (9.1 M) BELOW THE LOWEST LEVEL OF EXIT |
| | DISCHARGE, OR MORE THAN ONE LEVEL LOCATED BELOW THE |
| | LOWEST LEVEL OF EXIT DISCHARGE |
| | (3) COMBUSTIBLE CONTENTS, COMBUSTIBLE INTERIOR FINISH, |
| | OR COMBUSTIBLE CONSTRUCTION |
| | |
| | PLEASE PROVIDE SMOKE VENTING FOR THE BASEMANT AREA AS |
| | REQUIRED PER (3). |
| | |
| | |
| | |
| | 6) SHEET LS 1.01 & 2-5 FLOOR PLAN SHEETS - THERE |
| | APPEARS TO BE TWO(2) UNPROTECTED VERICAL OPENINGS: |
| | |
| | A.THE AREA ON THE WEST SIDE OPENING FROM THE PARKING |
| | GARAGE UP THROUGH THE ROOF. |
| | B. THE AREA LOCATED MORE NORTH INTERIOR FROM THE SECOND |
| | (2ND) FLOOR THROUGH THE ROOF. |
| | |
| | NFPA 101, CHAPTER 28 |
| | 28.3 PROTECTION. |
| | 28.3.1 PROTECTION OF VERTICAL OPENINGS. |
| | 28.3.1.1 VERTICAL OPENINGS SHALL COMPLY WITH 28.3.1.1.1 |
| | THROUGH 28.3.1.2. |
| | 28.3.1.1.1 VERTICAL OPENINGS SHALL BE ENCLOSED OR |
| | PROTECTED IN ACCORDANCE WITH SECTION 8.6. |
| | 28.3.1.1.2 VERTICAL OPENINGS IN ACCORDANCE WITH 8.6.9.1 |
| | SHALL BE PERMITTED. |
| | 28.3.1.1.3 IN BUILDINGS, OTHER THAN HIGH-RISE |
| | BUILDINGS, THAT ARE PROTECTED THROUGHOUT BY AN |
| | APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH 28.3.5, THE WALLS ENCLOSING VERTICAL |
| | OPENINGS SHALL HAVE A MINIMUM 1-HOUR FIRE RESISTANCE |
| | RATING, AND DOORS SHALL HAVE A MINIMUM 1-HOUR FIRE |
| | PROTECTION RATING. |
| | |
| | 8.6 VERTICAL OPENINGS. |
| | 8.6.1 FLOOR SMOKE BARRIERS. EVERY FLOOR THAT SEPARATES |
| | STORIES IN A BUILDING SHALL MEET THE FOLLOWING |
| | CRITERIA: |
| | (1) IT SHALL BE CONSTRUCTED AS A SMOKE BARRIER IN |
| | ACCORDANCE WITH SECTION 8.5. |
| | (2) IT SHALL BE PERMITTED TO HAVE OPENINGS AS DESCRIBED |
| | BY 8.6.6, 8.6.7, 8.6.8, 8.6.9, OR CHAPTERS 11 THROUGH |
| | 43. 8.6.2* CONTINUITY. OPENINGS THROUGH FLOORS SHALL BE |
| | ENCLOSED WITH FIRE BARRIER WALLS, SHALL BE CONTINUOUS |
| | FROM FLOOR TO FLOOR, OR FLOOR TO ROOF, AND SHALL BE |
| | PROTECTED AS APPROPRIATE FOR THE FIRE RESISTANCE RATING |
| | OF THE BARRIER. |
| | |
| | PLEASE PROVIDE THE REQUIRED PROTECTION AS INDICATED. |
| | |
| | |
| | |
| | 7) SHEETS A 2.02 - 2.04 - A H.K. ROOM IS INDICATED THAT |
| | INCLUDES A LAUNDRY CHUTE. NO DIMENSIONS ARE INDICATED |
| | OF THE SIZE OF ROOM. |
| | |
| | PER NFPA 101 CHAPTER 28 |
| | 28.5.4 RUBBISH CHUTES, INCINERATORS, AND LAUNDRY |
| | CHUTES. RUBBISH CHUTES, INCINERATORS, AND LAUNDRY |
| | CHUTES SHALL COMPLY WITH THE PROVISIONS OF SECTION 9.5. |
| | |
| | 9.5 RUBBISH CHUTES, INCINERATORS, AND LAUNDRY CHUTES. |
| | 9.5.1 ENCLOSURE. |
| | 9.5.1.1 RUBBISH CHUTES AND LAUNDRY CHUTES SHALL BE |
| | SEPARATELY ENCLOSED BY WALLS OR PARTITIONS IN |
| | ACCORDANCE WITH THE PROVISIONS OF SECTION 8.3. |
| | |
| | 9.5.1.4 THE ROOM USED FOR ACCESSING THE CHUTE OPENING |
| | SHALL BE SEPARATED FROM OTHER SPACES IN ACCORDANCE WITH |
| | SECTION 8.7. |
| | 9.5.1.5 THE REQUIREMENTS OF 9.5.1.1 THROUGH 9.5.1.4 |
| | SHALL NOT APPLY WHERE OTHERWISE PERMITTED BY THE |
| | FOLLOWING: |
| | (1) EXISTING INSTALLATIONS HAVING PROPERLY ENCLOSED |
| | SERVICE CHUTES AND PROPERLY INSTALLED AND MAINTAINED |
| | SERVICE OPENINGS SHALL BE PERMITTED TO HAVE INLETS OPEN |
| | TO A CORRIDOR OR NORMALLY OCCUPIED SPACE. |
| | (2) RUBBISH CHUTES AND LAUNDRY CHUTES SHALL BE |
| | PERMITTED TO OPEN INTO ROOMS NOT EXCEEDING 400 FT2 (37 |
| | M2) THAT ARE USED FOR STORAGE, PROVIDED THAT THE ROOM |
| | IS PROTECTED BY AUTOMATIC SPRINKLERS. |
| | |
| | THOUGH IT APPEARS TO COMPLY, PLEASE PROVIDE DIMENSIONS |
| | TO ENSURE COMPLAINCE WITH THE ABOVE (2). |
| | |
| | |
| | |
| | 8) SHEETS A 2.02 - 2.04 - A H.K. ROOM IS INDICATED THAT |
| | INCLUDES A LAUNDRY CHUTE. THE ROOM IS NOT INDICATED AS |
| | BEING PROTECTED UNDER THE REQUIREMENTS OF THE |
| | FOLLOWING. |
| | |
| | 9.5.1.4 THE ROOM USED FOR ACCESSING THE CHUTE OPENING |
| | SHALL BE SEPARATED FROM OTHER SPACES IN ACCORDANCE WITH |
| | SECTION 8.7. |
| | |
| | 8.7.1.2 IN NEW CONSTRUCTION, WHERE PROTECTION IS |
| | PROVIDED WITH AUTOMATIC EXTINGUISHING SYSTEMS WITHOUT |
| | FIRE-RESISTIVE SEPARATION, THE SPACE PROTECTED SHALL BE |
| | ENCLOSED WITH SMOKE PARTITIONS IN ACCORDANCE WITH |
| | SECTION 8.4, UNLESS OTHERWISE PERMITTED BY ONE OF THE |
| | FOLLOWING CONDITIONS: |
| | (1) WHERE MERCANTILE OCCUPANCY GENERAL STORAGE AREAS |
| | AND STOCKROOMS ARE PROTECTED BY AUTOMATIC SPRINKLERS IN |
| | ACCORDANCE WITH SECTION 9.7 |
| | (2) WHERE HAZARDOUS AREAS IN INDUSTRIAL OCCUPANCIES ARE |
| | PROTECTED BY AUTOMATIC EXTINGUISHING SYSTEMS IN |
| | ACCORDANCE WITH 40.3.2 |
| | (3) WHERE HAZARDOUS AREAS IN DETENTION AND CORRECTIONAL |
| | OCCUPANCIES ARE PROTECTED BY AUTOMATIC SPRINKLERS IN |
| | ACCORDANCE WITH 22.3.2 |
| | |
| | NFPA 82 INCINERATORS AND WASTE AND LINEN HANDLING |
| | SYSTEMS AND EQUIPMENT |
| | |
| | 5.2.5 SERVICE OPENING ROOMS. |
| | 5.2.5.1 GENERAL. |
| | 5.2.5.1.1 EVERY SERVICE OPENING SHALL BE IN A ROOM OR |
| | COMPARTMENT THAT IS SEPARATED FROM THE OTHER PARTS OF |
| | THE BUILDING BY WALLS, PARTITIONS, FLOORS, AND |
| | FLOOR-CEILING ASSEMBLIES HAVING A FIRE RESISTANCE |
| | RATING OF NOT LESS THAN THE REQUIRED RATING OF |
| | THE CHUTE ENCLOSURE. |
| | 5.2.5.1.2 WHERE SERVICE OPENING ROOMS ARE PROTECTED BY |
| | AUTOMATIC SPRINKLERS, THE ROOM SHALL BE ENCLOSED IN A |
| | MINIMUM OF 1-HOUR CONSTRUCTION, AND OPENINGS SHALL BE |
| | PROTECTED WITH 3?4-HOUR FIRE-RATED DOORS. |
| | 5.2.5.1.3 OPENINGS INTO SUCH A ROOM OR COMPARTMENT |
| | SHALL BE PROTECTED BY APPROVED SELF-CLOSING DOORS THAT |
| | ARE APPROPRIATE FOR PROTECTING THE OPENINGS OR ARE OF |
| | NOT LESS THAN A 1?HOUR PARTITION RATING WITH A 3?4-HOUR |
| | FIRE-RATED DOOR. |
| | 5.2.5.1.4 THE SIZE OF THE SERVICE OPENING ROOM OR |
| | COMPARTMENT SHALL NOT BE LESS THAN THAT REQUIRED TO |
| | MAINTAIN A MINIMUM 152.4 MM (6 IN.) CLEARANCE BETWEEN |
| | THE INTAKE OPENING AND THE CLOSED SERVICE OPENING ROOM |
| | DOOR. |
| | |
| | PLEASE PROVIDE PROTECTION AS REQUIRED FOR ALL WALLS |
| | SURROUNDING THE LAUNDRY CHUTE ROOM, INCLUDING THE |
| | CORRIDOR WALL AND JANITOR/MECHANICAL ROOMS. |
| | |
| | |
| | |
| | 9) SHEETS A 2.02 - 2.04 - A H.K. ROOM IS INDICATED THAT |
| | INCLUDES A LAUNDRY CHUTE. THE DOOR TO THE LAUNDRY CHUTE |
| | ROOM; 8, AND MECHANICAL ROOM; 10, ARE NOT INDICATED AS |
| | HAVING ANY RATING OR CLSING DEVICES PER DOOR SCHEDULE |
| | SHHET A 9.02. |
| | |
| | 9.5.1.4 THE ROOM USED FOR ACCESSING THE CHUTE OPENING |
| | SHALL BE SEPARATED FROM OTHER SPACES IN ACCORDANCE WITH |
| | SECTION 8.7. |
| | |
| | 8.7.1.3 DOORS IN BARRIERS REQUIRED TO HAVE A FIRE |
| | RESISTANCE RATING SHALL HAVE A MINIMUM ?-HOUR FIRE |
| | PROTECTION RATING AND SHALL BE SELF-CLOSING OR |
| | AUTOMATIC-CLOSING IN ACCORDANCE WITH 7.2.1.8. |
| | |
| | PLEASE PROVIDE FOR THE DOOR REQUIREMENTS. |
| | |
| | |
| | |
| | 10) SHEET A 6.05 & A 2.02 - A 2.04 - THE LINEN CHUTE |
| | CHASE DOES NOT INDICATE AND FIRE RATING. |
| | |
| | NFPA 82 INCINERATORS AND WASTE AND LINEN HANDLING |
| | SYSTEMS AND EQUIPMENT |
| | |
| | 5.2.3 CHUTE ENCLOSURE (CHASE). |
| | 5.2.3.1 GENERAL. |
| | 5.2.3.1.1 VERTICAL WASTE OR LINEN CHUTES IN ALL STORIES |
| | ABOVE THE STORAGE OR COMPACTING ROOM SHALL BE ENCLOSED |
| | WITHIN A CONTINUOUS FIRE-RATED ENCLOSURE CONSISTENT |
| | WITH THE CONSTRUCTION TYPE. |
| | 5.2.3.1.2 THE WALLS OF THE ENCLOSURE SHALL HAVE A FIRE |
| | RESISTANCE RATING OF NOT LESS THAN 2 HOURS IF THE |
| | BUILDING IS FOUR OR MORE STORIES IN HEIGHT AND NOT LESS |
| | THAN 1 HOUR IF THE BUILDING IS LESS THAN FOUR STORIES |
| | IN HEIGHT. |
| | 5.2.3.1.3 OPENINGS IN THE FIRE-RATED ENCLOSURE SHALL BE |
| | AS FOLLOWS: |
| | (1) 11?2-HOUR FIRE RESISTANCE RATING FOR 2 HOUR?RATED |
| | ENCLOSURES |
| | (2) 1-HOUR FIRE RESISTANCE RATING FOR 1 HOUR?RATED |
| | ENCLOSURES |
| | |
| | PLEASE PROVIDE THE INDICATED FIRE RATED PROTECTION. |
| | |
| | |
| | |
| | 11) SHEET B - THE LAUNDRY CHUTE DISCHARPE ROOM DOES NOT |
| | INDICATED AN FIRE RATING. |
| | |
| | NFPA 82 INCINERATORS AND WASTE AND LINEN HANDLING |
| | SYSTEMS AND EQUIPMENT |
| | |
| | 5.2.4 CHUTE DISCHARGE ROOMS. |
| | 5.2.4.1 GENERAL. |
| | 5.2.4.1.1 WASTE AND LINEN CHUTES SHALL TERMINATE OR |
| | DISCHARGE DIRECTLY INTO A ROOM HAVING A MINIMUM FIRE |
| | RESISTANCE RATING NOT LESS THAN THAT SPECIFIED FOR THE |
| | CHUTE. |
| | 5.2.4.1.2 OPENINGS INTO SUCH A ROOM OR COMPARTMENT |
| | SHALL BE PROTECTED BY APPROVED SELF-CLOSING FIRE DOORS |
| | HAVING A MINIMUM FIRE PROTECTION RATING NOT LESS THAN |
| | SPECIFIED FOR THE CHUTE. |
| | |
| | PLEASE PROVIDE FIRE RATING AS REQUIRED. |
| | |
| | |
| | |
| | 12) SHEETS A 2.02 - 2.03 - THE H.K. ROOM APPEARS TO |
| | HAVE A TRASH RECEPTICLE LOCATED WITHIN IT. THE ROOM CAN |
| | BE USED FOR STORAGE BUT IT CAN NOT BE USED AS A TRASH |
| | ROOM. |
| | |
| | 9.5.1.4 THE ROOM USED FOR ACCESSING THE CHUTE OPENING |
| | SHALL BE SEPARATED FROM OTHER SPACES IN ACCORDANCE WITH |
| | SECTION 8.7. |
| | 9.5.1.5 THE REQUIREMENTS OF 9.5.1.1 THROUGH 9.5.1.4 |
| | SHALL NOT APPLY WHERE OTHERWISE PERMITTED BY THE |
| | FOLLOWING: |
| | (1) EXISTING INSTALLATIONS HAVING PROPERLY ENCLOSED |
| | SERVICE CHUTES AND PROPERLY INSTALLED AND MAINTAINED |
| | SERVICE OPENINGS SHALL BE PERMITTED TO HAVE INLETS OPEN |
| | TO A CORRIDOR OR NORMALLY OCCUPIED SPACE. |
| | (2) RUBBISH CHUTES AND LAUNDRY CHUTES SHALL BE |
| | PERMITTED TO OPEN INTO ROOMS NOT EXCEEDING 400 FT2 (37 |
| | M2) THAT ARE USED FOR STORAGE, PROVIDED THAT THE ROOM |
| | IS PROTECTED BY AUTOMATIC SPRINKLERS. |
| | |
| | FOR PURPOSES OF IDENTIFYING STORAGE: |
| | 3.3.188.15* STORAGE OCCUPANCY. AN OCCUPANCY USED |
| | PRIMARILY FOR THE STORAGE OR SHELTERING OF GOODS, |
| | MERCHANDISE, PRODUCTS, OR VEHICLES. |
| | |
| | PER (2), THE ROOM CAN BE USED FOR STORAGE PURPOSES. |
| | TRASH IS NOT CONSIDERED AS ALLOWABLE WITHIN THIS ROOM. |
| | |
| | |
| | |
| | 13) SHEET A 2.04 - THE H.K. ROOM IS INDICATED AS HAVING |
| | A MECHANICAL ROOM; SHEET E 1.03 INDICATES IT AS A |
| | BOILER ROOM, WITH WHAT APPEARS TO BE WATER HEATERS. THE |
| | H.K. ROOM IS DIFFERENT THAN ALL OTHER FLOORS LEVELS. |
| | PLEASE CONFIRM AND PROVIDE CLARIFYING NARRATIVE. |
| | |
| | 9.5.1.4 THE ROOM USED FOR ACCESSING THE CHUTE OPENING |
| | SHALL BE SEPARATED FROM OTHER SPACES IN ACCORDANCE WITH |
| | SECTION 8.7. |
| | 9.5.1.5 THE REQUIREMENTS OF 9.5.1.1 THROUGH 9.5.1.4 |
| | SHALL NOT APPLY WHERE OTHERWISE PERMITTED BY THE |
| | FOLLOWING: |
| | (1) EXISTING INSTALLATIONS HAVING PROPERLY ENCLOSED |
| | SERVICE CHUTES AND PROPERLY INSTALLED AND MAINTAINED |
| | SERVICE OPENINGS SHALL BE PERMITTED TO HAVE INLETS OPEN |
| | TO A CORRIDOR OR NORMALLY OCCUPIED SPACE. |
| | (2) RUBBISH CHUTES AND LAUNDRY CHUTES SHALL BE |
| | PERMITTED TO OPEN INTO ROOMS NOT EXCEEDING 400 FT2 (37 |
| | M2) THAT ARE USED FOR STORAGE, PROVIDED THAT THE ROOM |
| | IS PROTECTED BY AUTOMATIC SPRINKLERS. |
| | |
| | A. PER (2), THE ROOM CAN BE USED FOR STORAGE PURPOSES. |
| | WATER HEATERS ARE NOT CONSIDERED AS ALLOWABLE WITHIN |
| | THIS ROOM. |
| | B. HOW WILL THE WATER HEATERS BE POWERED? |
| | C. WHERE IS THE TRASH RECEPTICLE LOCATED ON THIS FLOOR. |
| | |
| | |
| | |
| | |
| | 14) SHEETS FP 2.01 - 2.03 - THE ROOMS INDICATED AS |
| | SUANA ARE NOT PROVIDED WITH FIRE SPRINKLER PROTECTION. |
| | |
| | CHAPTER 4 GENERAL REQUIREMENTS |
| | 4.1 LEVEL OF PROTECTION. A BUILDING, WHERE PROTECTED BY |
| | AN AUTOMATIC SPRINKLER SYSTEM INSTALLATION, SHALL BE |
| | PROVIDED WITH SPRINKLERS IN ALL AREAS EXCEPT WHERE |
| | SPECIFIC SECTIONS OF THIS STANDARD PERMIT THE OMISSION |
| | OF SPRINKLERS. |
| | |
| | THERE IS NO OMISSION OF SPRINKLERS FOR THIS ROOM. |
| | |
| | PLEASE PROVIDE FOR FIRE SPRINKLER PROTECTION. |
| | |
| | |
| | |
| | |
| | 15) COMMENT # 6 RESTATED FOR SHEETS FP - THE IS NO |
| | INDICATIONS OF FIRE PROTECTION OF THE VERITCAL OPENINGS |
| | ALONG THE WEST SIDE AND FLOORS 2-5 OPENING IN THE NORTH |
| | INTRERIOR AREA. |
| | |
| | 28.3 PROTECTION. |
| | 28.3.1 PROTECTION OF VERTICAL OPENINGS. |
| | 28.3.1.1 VERTICAL OPENINGS SHALL COMPLY WITH 28.3.1.1.1 |
| | THROUGH 28.3.1.2. |
| | 28.3.1.1.1 VERTICAL OPENINGS SHALL BE ENCLOSED OR |
| | PROTECTED IN ACCORDANCE WITH SECTION 8.6. |
| | 28.3.1.1.2 VERTICAL OPENINGS IN ACCORDANCE WITH 8.6.9.1 |
| | SHALL BE PERMITTED. |
| | 28.3.1.1.3 IN BUILDINGS, OTHER THAN HIGH-RISE |
| | BUILDINGS, THAT ARE PROTECTED THROUGHOUT BY AN |
| | APPROVED, SUPERVISED AUTOMATIC SPRINKLER SYSTEM IN |
| | ACCORDANCE WITH 28.3.5, THE WALLS ENCLOSING VERTICAL |
| | OPENINGS SHALL HAVE A MINIMUM 1-HOUR FIRE RESISTANCE |
| | RATING, AND DOORS SHALL HAVE A MINIMUM 1-HOUR FIRE |
| | PROTECTION RATING. |
| | |
| | 8.6 VERTICAL OPENINGS. |
| | 8.6.1 FLOOR SMOKE BARRIERS. EVERY FLOOR THAT SEPARATES |
| | STORIES IN A BUILDING SHALL MEET THE FOLLOWING |
| | CRITERIA: |
| | (1) IT SHALL BE CONSTRUCTED AS A SMOKE BARRIER IN |
| | ACCORDANCE WITH SECTION 8.5. |
| | (2) IT SHALL BE PERMITTED TO HAVE OPENINGS AS DESCRIBED |
| | BY 8.6.6, 8.6.7, 8.6.8, 8.6.9, OR CHAPTERS 11 THROUGH |
| | 43. 8.6.2* CONTINUITY. OPENINGS THROUGH FLOORS SHALL BE |
| | ENCLOSED WITH FIRE BARRIER WALLS, SHALL BE CONTINUOUS |
| | FROM FLOOR TO FLOOR, OR FLOOR TO ROOF, AND SHALL BE |
| | PROTECTED AS APPROPRIATE FOR THE FIRE RESISTANCE RATING |
| | OF THE BARRIER. |
| | |
| | PLEASE PROVIDE THE REQUIRED PROTECTION AS INDICATED. |
| | |
| | |
| | |
| | 16) SHEET FP 1.04 - A ROOF MANIFOLD IS INDICATED ON THE |
| | NORTH WEST SIDE OF THE ROOF. THE IS INSUFFICIENT AREA |
| | IN FRONT OF THE MANIFOLD TO ALLOW FOR FIRE OPERATIONS. |
| | |
| | 13.1.3 OBSTRUCTIONS SHALL NOT BE PLACED OR KEPT NEAR |
| | FIRE HYDRANTS, FIRE DEPARTMENT INLET CONNECTIONS, OR |
| | FIRE PROTECTION SYSTEM CONTROL VALVES IN A MANNER THAT |
| | WOULD PREVENT SUCH EQUIPMENT OR FIRE HYDRANTS FROM |
| | BEING IMMEDIATELY VISIBLE AND ACCESSIBLE. |
| | 13.1.4 A MINIMUM 36 IN. (91 MM) OF CLEAR SPACE SHALL BE |
| | MAINTAINED TO PERMIT ACCESS TO AND OPERATION OF FIRE |
| | PROTECTION EQUIPMENT, FIRE DEPARTMENT INLET |
| | CONNECTIONS, OR FIRE PROTECTION SYSTEM CONTROL VALVES. |
| | THE FIRE DEPARTMENT SHALL NOT BE DETERRED OR HINDERED |
| | FROM GAINING IMMEDIATE ACCESS TO FIRE PROTECTION |
| | EQUIPMENT. |
| | 13.1.4.1 AN APPROVED CLEAR AND UNOBSTRUCTED PATH SHALL |
| | BE PROVIDED AND MAINTAINED FOR ACCESS TO THE FIRE |
| | DEPARTMENT INLET CONNECTIONS. |
| | |
| | PLEASE PROVIDE FOR THE MINMIMUM REQUIREMENT BY |
| | REPOSITIONING, TURNING, RELOCATION OTHER OTHER SIMILAR |
| | REMEDY. |
| | |
| | |
| | |
| | 17) ROOF SHEETS - THE ROOF IS INDICATED WITH A SPACE |
| | THAT IS OPEN TO THE 2ND FLLOR BELOW. FOR FIREFIGHTER |
| | FIRE OPERATIONAL SAFETY, THOUGH THIS OPENING APPEARS TO |
| | HAVE A PARAPET WALL, PLEASE PROVIDE REFLECTIVE SIGNAGE |
| | ON ALL FOUR SIDES "DANGER, OPENING THROUGH TO 2ND |
| | FLOOR" OR SIMILAR. |
| | |
| | |
| | |
| | 18) ROOF SHEETS - THERE IS A PARAPET WALL INDICATED ON |
| | THE EAST AND WEST SIDES WITH OPEN TRELLIS CONSTRUCTION |
| | ON THE OTHER SIDE. FOR FIREFIGHTER FIRE OPERATIONAL |
| | SAFETY, PLEASE PROVIDE REFLECTIVE SIGNAGE, "DANGER, |
| | OPEN TRELLS BEAMS ON OTHER SIDE" OR SIMILAR IN MULTIPLE |
| | LOCATIONS. |
| | |
| | |
| | |
| | 19) SHEET A 2.01A & A 9.02 - GATE DOORS AND GATES ARE |
| | INDICATED ON THE PERIMETER OF THE BUILDING SITE. THESE |
| | GATES ARE LOCATED IN THE EGRESS PATH OF TRAVEL. THE |
| | DOOR SCHEDULE INDICATES THERE ARE LOCKED. THESE GATES |
| | SHALL IMPEDE EGRESS AND SHALL COMPLY WITH NFPA |
| | 101,CHAPTER 28 & CHAPTER 7, MEANS OF EGRESS |
| | |
| | 28.2.2.2 DOORS. |
| | 28.2.2.2.1 DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | 28.2.2.2.2 DOOR-LOCKING ARRANGEMENTS SHALL COMPLY WITH |
| | 28.2.2.2.2.1, 28.2.2.2.2.2, 28.2.2.2.2.3, OR |
| | 28.2.2.2.2.4. |
| | 28.2.2.2.2.1 NO DOOR IN ANY MEANS OF EGRESS SHALL BE |
| | LOCKED AGAINST EGRESS WHEN THE BUILDING IS OCCUPIED. |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS |
| | OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER |
| | EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE |
| | LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR |
| | OPERATION FROM THE EGRESS SIDE. |
| | 7.2.1.5.4 THE REQUIREMENTS OF 7.2.1.5.1 AND 7.2.1.5.3 |
| | SHALL NOT APPLY WHERE OTHERWISE PROVIDED IN CHAPTERS 18 |
| | THROUGH 23. |
| | |
| | PLEASE PROVIDE LOCKS/LATCHES IN COMPLIANCE WITH THE |
| | REQUIRMENT. |
| | |
| | |
| | |
| | 20) SHEET A 8.02 - A GREEN SCREEN PANEL IS INDICATED ON |
| | THE WEST OUTSIDE WALL ATTACHED TO AN ALUMINUM |
| | STRUCTURE. |
| | |
| | PLEASE PROVIDE THE SCREEN FABRIC SPECIFICATION SHEET |
| | THAT INDICATES ANY FLAME AND SMOKE SPREAD RATING, FIRE |
| | RATINGS, FIRE PROTECTION FEATURES, ETC. |
| | |
| | |
| | |
| | 21) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |
| | 561-804-4709 |
| | [email protected] |
| | |
| | |