| 2016-07-28 07:17:33 | INITIAL ELECTRICAL PLAN REVIEW |
| | |
| | APPLICABLE CODES IN EFFECT: |
| | FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| | EDITION |
| | NFPA 70- 2011 |
| | COMMENTS: |
| | |
| | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE |
| | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE |
| | PERMITS AND DATA CUT SHEET SUBMITTALS FOR ALL SITE |
| | LIGHTING AND ASSOCIATED EQUIPMENT, ALL LOW VOLTAGE |
| | SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE ALARM, |
| | ACCESS CONTROLS, CCTV, PHONE AND DATA, SIGNAGE, |
| | WIRELESS SYSTEMS, ELEVATORS, CAR CHARGING STATIONS, |
| | POOLS IN UNITS, ETC. A NOTE WILL SUFFICE. |
| | 2. SHEET E1.00- PLEASE ADD A GENERAL NOTE TO SHEET TO |
| | INDICATE THE REQUIREMENTS OF NEC 300.5D3 AND TABLE |
| | 300.5 FOR MINIMUM COVER REQUIREMENTS FOR CONDUITS AND |
| | THE PLACEMENT OF A WARNING RIBBON FOR THE SERVICE |
| | LATERAL CONDUCTORS SHOWN FOR THIS PROJECT. A NOTE WILL |
| | SUFFICE |
| | 3. SHEET E1.00- ADD A NOTE TO MAINTAIN ALL ELECTRICAL |
| | EQUIPMENT ABOVE THE BASELINE FLOOD ELEVATION PER STATE |
| | AND CITY REGULATORY AGENCIES. |
| | 4. ADDRESS ALL FIRE COMMENTS RELATED TO ELECTRICAL |
| | DESIGN. FBC 107.3.5 |
| | 5. PER FBC ENERGY CONSERVATION 2014 C405.7 PROVIDE |
| | REQUIRED VOLTAGE DROP CALCULATIONS FOR FEEDERS AND |
| | BRANCH CIRCUIT |
| | 6. PER NEC 110.16 ARC FLASH WARNING- SEE CODE. GENERAL |
| | NOTE WILL SUFFICE AT RISER DIAGRAM |
| | 7. PER NEC 110.24A- AVAILABLE FAULT CURRENT- FIELD |
| | MARKINGS. ADD GENERAL NOTE INDICATING REQUIREMENTS AT |
| | THE SERVICE. A NOTE WILL SUFFICE |
| | 8. PROVIDE AIC CALCULATIONS PER NEC 110.9 AND 110.10- |
| | SHOW AIC AT THE FPL TRANSFORMER WITH FPL LETTERHEAD |
| | INDICATING AVAILABLE FAULT CURRENT. FBC 107.3.5 |
| | 9. SUBMIT 1/2" DETAIL OF MAIN ELECTRICAL ROOM NOT 1/4" |
| | AS SHOWN. NEED TO VERIFY IF PER NEC 110.26C2 |
| | UNOBSTRUCTED EGRESS IS MET PER DEPTH OF DISTANCE FROM |
| | EQUIPMENT TO DOOR PER AHJ PERMISSION. |
| | 10. CORRECT TYPO AT RISER DIAGRAM TO SHOW ID PANEL MDPB |
| | NOT MDBA FOR MAIN #2. |
| | 11. ADD A NOTE TO UNITS PER NEC 406.13- ALL GUEST UNITS |
| | TO HAVE TAMPER RESISTANT RECEPTACLES. |
| | 12. PROVIDE A GENERAL NOTE TO UNITS TO INDICATE FOR NOW |
| | THE REQUIREMENTS OF NEC 680 POOLS EQUIPMENT LOCATION TO |
| | MAINTAIN DISTANCES REQUIRED FOR RECEPTACLES AND |
| | LIGHTING (DIMENSIONS MAY REQUIRE GFCI PROTECTION). |
| | SEPARATE POOL PERMITS WILL THEN BE REVIEWED PER SCOPE. |
| | FBC 107.3.5 |
| | 13. PLEASE CONFIRM IF PARKING AREA WILL HAVE |
| | VENTILATION FOR CO EXHAUST, SEE FIRE REVIEW AND ADDRESS |
| | ELECTRICAL SCOPE. FBC 107.3.5 |
| | 14. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL |
| | FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS |