| 2016-08-09 15:41:59 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 16070837 |
| | ADD: 309/317 N. ROSEMARY AVE. |
| | CONT: TBD/ TO BE DETERMINED |
| | TEL: 305-456-7252 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 1ST REVIEW |
| | DATE: SUN. AUGUST 07/2016 |
| | ACTION: DENIED |
| | |
| | 1) PLEASE NOTE AN ADDRESSING PLAN REVIEW STOP WILL BE |
| | ADDED TO THE PLAN REVIEW CYCLE TO ASSIGN A SITE |
| | ADDRESS. IT APPEARS ON THE PALM BCH. COUNTY PROPERTY |
| | APPRAISERS WEBSITE THERE ARE 3 ACTUAL PROPERTIES THAT |
| | WILL BE MAKING UP THIS SITE. |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION OF THE |
| | PROJECT. PLEASE CONTACT MR. ORIO FOR AN SITE ADDRESS. |
| | CONTACT: MICHAEL ORIO GIS SUPPORT SPECIALIST/ |
| | INFORMATION TECHNOLOGY |
| | TEL: 561-494-1040. |
| | E-MAIL: [email protected] |
| | |
| | 2) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH |
| | ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES |
| | TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH |
| | THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/2014, |
| | AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO |
| | OR GREATER THAN $750,000 |
| | WILL NEED TO COMPLY WITH THIS ORDINANCE. |
| | PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| | CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| | ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| | 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| | PROJECT CONSTRUCTION COST. |
| | PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| | V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| | NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| | THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| | PROJECTS. |
| | FOR CONTACT INFORMATION PLEASE CONTACT: |
| | MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| | 822-1515 E-MAIL: [email protected] |
| | |
| | 3) THIS MAIN BUILDING PERMIT WILL INCLUDE THE FEES FOR |
| | THE MECHANICAL, ELECTRICAL, PLUMBING & ROOFING PERMITS. |
| | WHEN THE GENERAL CONTRACTOR COMES IN FOR A BUILDING |
| | PERMIT WITH THE SIGNED PERMIT APPLICATION FORM BY THE |
| | QUALIFIER AND OWNER AND BRINGS IN THE LISTED |
| | SUB-PERMITS M-E-P & ROOFING PERMITS SIGNED BY THE |
| | QUALIFIER OF EACH COMPANY, THEIR INSURANCES AND |
| | LICENSURE UP TO DATE, THE M-E-P AND ROOFING PERMITS ARE |
| | FREE OF CHARGE. IF THE M-E-P & ROOFING PERMITS COME IN |
| | LATER THERE WILL BE AN $80.00 ADMINISTRATIVE FEE FOR |
| | EACH PERMIT. |
| | |
| | ALL OTHER PERMITS FIRE SPRINKLER, FIRE ALARM, EXHAUST |
| | HOODS, ANSUL SYSTEMS OR ALTERNATIVE AUTOMATIC |
| | FIRE-EXTINGUISHING SYSTEMS , WALK IN COOLERS & |
| | FREEZERS, ALL LOW VOLTAGE PERMITS, GENERATORS & FUEL |
| | TANKS, GAS PERMIT, POOL, JACUZZI AND ASSOCIATED |
| | SUB-PERMITS, AWNING, CANOPY, FENCE, LANDSCAPE , |
| | IRRIGATION, AUGER CAST PILE AND OR FOUNDATION OR |
| | STRUCTURE ONLY PERMIT WILL BE SEPARATE REVIEWS AND |
| | ASSOCIATED FEES WITH EACH PERMIT. |
| | PLEASE LIST AND SUBTRACT THESE LINE ITEMS AND THEIR |
| | VALUE FROM THE OVERALL BUILDING VALUE OF $4,088000.00. |
| | THE REMAINING BALANCE WILL BE AFFECTIVELY THE VALUE OF |
| | THE BUILDING YOU WILL BE PAYING FOR THIS PERMIT. THE |
| | BUILDING DOES NOT WANT TO COLLECT TWICE FOR THE VALUE |
| | OF THESE SUB-PERMITS NOT COVERED UNDER THE PRIME OR |
| | MASTER PERMIT. |
| | |
| | 4)THIS BUILDING IS A THRESHOLD BUILDING / FL S. S. |
| | 553.71(7) ?THRESHOLD BUILDING" MEANING ANY BUILDING |
| | WHICH IS GREATER THAN (3) STORIES OR 50 FT. IN HEIGHT, |
| | OR WHICH HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS |
| | DENIED IN THE FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 |
| | SQ. FT. IN AREA AND AN OCCUPANT CONTENT OF GREATER THAN |
| | 500 PERSONS. |
| | |
| | 4A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING |
| | AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL |
| | INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A |
| | THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION |
| | PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL |
| | INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING |
| | AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR |
| | THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE |
| | OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE |
| | SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT |
| | THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| | WITH THE PERMITTED DOCUMENTS. |
| | |
| | 4B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS |
| | ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH |
| | INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND |
| | REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE |
| | PLACE. CONTACT KEN CONRAD MANAGER OF THE SPECIAL |
| | INSPECTOR PROGRAM AT (561)805-6666 FOR FURTHER |
| | INFORMATION BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | 4C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B. |
| | AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH |
| | ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT |
| | OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE |
| | BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE |
| | PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE |
| | FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL |
| | AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 4D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME' |
| | OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE |
| | RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | |
| | 4E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONSTRUCTION. |
| | |
| | 4F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE |
| | REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE, |
| | PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING |
| | ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE |
| | APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR |
| | PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN |
| | COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR |
| | THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE |
| | IN BLACK & WHITE.. |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD |
| | BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS |
| | CONCERNING SPECIAL INSPECTORS. |
| | |
| | 4G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES, |
| | PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT |
| | AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING |
| | INSTALLATION SHALL BE SUPERVISED, INSPECTED AND |
| | CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING |
| | DOCUMENTS BY THE CONTRACTOR. |
| | |
| | 4H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL |
| | BUILDING INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6 |
| | MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY. |
| | |
| | 4I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES |
| | FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER |
| | HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE |
| | MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR |
| | WALLS AND CEILINGS. |
| | |
| | 5) PERIMETER FENCING UNDER A SEPARATE PERMIT. PLEASE |
| | PROVIDE COMPLIANCE WITH: 2014 FBC-B 3306.5 BARRIERS. |
| | BARRIERS SHALL BE A MINIMUM OF 8 FEET (2438 MM) IN |
| | HEIGHT AND SHALL BE PLACED ON THE SIDE OF THE WALKWAY |
| | NEAREST THE CONSTRUCTION. BARRIERS SHALL EXTEND THE |
| | ENTIRE LENGTH OF THE CONSTRUCTION SITE. |
| | |
| | 6) 2014 FBC0B 3306.2 WALKWAYS. A WALKWAY SHALL BE |
| | PROVIDED FOR PEDESTRIAN TRAVEL IN FRONT OF EVERY |
| | CONSTRUCTION AND DEMOLITION SITE UNLESS THE APPLICABLE |
| | GOVERNING AUTHORITY AUTHORIZES THE SIDEWALK TO BE |
| | FENCED OR CLOSED. WALKWAYS SHALL BE OF SUFFICIENT WIDTH |
| | TO ACCOMMODATE THE PEDESTRIAN TRAFFIC, BUT IN NO CASE |
| | SHALL THEY BE LESS THAN 4 FEET (1219 MM) IN WIDTH. |
| | WALKWAYS SHALL BE PROVIDED WITH A DURABLE WALKING |
| | SURFACE. WALKWAYS SHALL BE ACCESSIBLE IN ACCORDANCE |
| | WITH CHAPTER 11 AND SHALL BE DESIGNED TO SUPPORT ALL |
| | IMPOSED LOADS AND IN NO CASE SHALL THE DESIGN LIVE LOAD |
| | BE LESS THAN 150 POUNDS PER SQUARE FOOT (PSF). WILL THE |
| | WALKWAYS ON THE SOUTH SIDE OF TRINITY PLACE BE CLOSED? |
| | |
| | 7) 2014 FBC-B 3306.7 COVERED WALKWAYS. COVERED WALKWAYS |
| | SHALL HAVE A CLEAR HEIGHT OF NOT LESS THAN 8 FEET (2438 |
| | MM) AS MEASURED FROM THE FLOOR SURFACE TO THE CANOPY |
| | OVERHEAD. ADEQUATE LIGHTING SHALL BE PROVIDED AT ALL |
| | TIMES. COVERED WALKWAYS SHALL BE DESIGNED TO SUPPORT |
| | ALL IMPOSED LOADS. IN NO CASE SHALL THE DESIGN LIVE |
| | LOAD BE LESS THAN 150 PSF FOR THE ENTIRE STRUCTURE. |
| | |
| | 8) PLEASE PROVIDE COMPLIANCE WITH: POLLUTION PREVENTION |
| | PLAN. 2014 FBC-B 3307.1 PROTECTION REQUIRED. ADJOINING |
| | PUBLIC AND PRIVATE PROPERTY SHALL BE PROTECTED FROM |
| | DAMAGE DURING CONSTRUCTION, REMODELING AND DEMOLITION |
| | WORK. PROVISIONS SHALL BE MADE TO CONTROL WATER RUNOFF |
| | AND EROSION DURING CONSTRUCTION OR DEMOLITION |
| | ACTIVITIES. THE PERSON MAKING OR CAUSING AN EXCAVATION |
| | TO BE MADE SHALL PROVIDE WRITTEN NOTICE TO THE OWNERS |
| | OF ADJOINING BUILDINGS ADVISING THEM THAT THE |
| | EXCAVATION IS TO BE MADE AND THAT THE ADJOINING |
| | BUILDINGS SHOULD BE PROTECTED. SAID NOTIFICATION SHALL |
| | BE DELIVERED NOT LESS THAN 10 DAYS PRIOR TO THE |
| | SCHEDULED STARTING DATE OF THE EXCAVATION. |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 109.3.10 IMPACT OF CONSTRUCTION. ALL |
| | CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE |
| | PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE |
| | CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS |
| | PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO CONSENT |
| | BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS & |
| | CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER. |
| | THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF |
| | DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE |
| | STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION |
| | ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE |
| | WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY |
| | REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH |
| | ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS |
| | OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS, |
| | CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL |
| | DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS, |
| | DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING |
| | PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ. |
| | FT. OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A |
| | PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED |
| | DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS |
| | PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A |
| | CERTIFICATION FROM A LICENSED ENGINEER SHALL BE |
| | SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL |
| | OF THE FINAL INSPECTION. |
| | |
| | 9) PLEASE PROVIDE DETAILS SHOWING HOW COMPLIANCE WITH |
| | 2014 FBC-B 3306.9 ADJACENT TO EXCAVATIONS. |
| | EVERY EXCAVATION ON A SITE LOCATED 5 FEET (1524 MM) OR |
| | LESS FROM THE STREET LOT LINE SHALL BE ENCLOSED WITH A |
| | BARRIER NOT LESS THAN 6 FEET (1829 MM) IN HEIGHT. WHERE |
| | LOCATED MORE THAN 5 FEET (1524 MM) FROM THE STREET LOT |
| | LINE, A BARRIER SHALL BE ERECTED WHERE REQUIRED BY THE |
| | BUILDING OFFICIAL. BARRIERS SHALL BE OF ADEQUATE |
| | STRENGTH TO RESIST WIND PRESSURE AS SPECIFIED IN |
| | CHAPTER 16. SHEET A2.01A & S-1 SHOW PILING RIGHT |
| | ADJACENT TO THE PROPERTY LINE SEE COLUMN 1 AND ROW A . |
| | |
| | 10A) PLEASE PROVIDE DETAILS SHOWING COMPLIANCE WITH |
| | 2014 FBC-B 3307.1 PROTECTION REQUIRED. ADJOINING PUBLIC |
| | AND PRIVATE PROPERTY SHALL BE PROTECTED FROM DAMAGE |
| | DURING CONSTRUCTION AND DEMOLITION WORK. PROTECTION |
| | SHALL BE PROVIDED FOR FOOTINGS, FOUNDATIONS, PARTY |
| | WALLS, CHIMNEYS, SKYLIGHTS AND ROOFS. WITH THE |
| | EXCAVATION AND AUGER CAST PILE HOW WILL THE BUILDING TO |
| | THE SOUTH BE PROTECTED FROM SETTLEMENT? |
| | SHEET A2.01A & S-1 SHOW PILING RIGHT ADJACENT TO THE |
| | PROPERTY LINE SEE COLUMN 1 AND ROW A . |
| | |
| | 10B) 2014 FBC-B 3307.1 THE PERSON MAKING OR CAUSING AN |
| | EXCAVATION TO BE MADE SHALL PROVIDE WRITTEN NOTICE TO |
| | THE OWNERS OF ADJOINING BUILDINGS ADVISING THEM THAT |
| | THE EXCAVATION IS TO BE MADE AND THAT THE ADJOINING |
| | BUILDINGS SHOULD BE PROTECTED. SAID NOTIFICATION SHALL |
| | BE DELIVERED NOT LESS THAN 10 DAYS PRIOR TO THE |
| | SCHEDULED STARTING DATE OF THE EXCAVATION. SHEET A2.01A |
| | & S-1 SHOW PILING RIGHT ADJACENT TO THE PROPERTY LINE |
| | SEE COLUMN 1 AND ROW A . |
| | |
| | 11) WHEN EXCAVATING WILL THE EXCESS SOILS BE STORED ON |
| | SITE? 2014 FBC-B 3304.1.2 SURCHARGE. NO FILL OR OTHER |
| | SURCHARGE LOADS SHALL BE PLACED ADJACENT TO ANY |
| | BUILDING OR STRUCTURE UNLESS SUCH BUILDING OR STRUCTURE |
| | IS CAPABLE OF WITHSTANDING THE ADDITIONAL LOADS CAUSED |
| | BY THE FILL OR SURCHARGE. EXISTING FOOTINGS OR |
| | FOUNDATIONS WHICH CAN BE AFFECTED BY ANY EXCAVATION |
| | SHALL BE UNDERPINNED ADEQUATELY OR OTHERWISE PROTECTED |
| | AGAINST SETTLEMENT AND SHALL BE PROTECTED AGAINST LATER |
| | MOVEMENT. |
| | |
| | 12) PLEASE DOCUMENT COMPLIANCE WITH: 2014 FBC-B 3313.1 |
| | WHERE REQUIRED. AN APPROVED WATER SUPPLY FOR FIRE |
| | PROTECTION, EITHER TEMPORARY OR PERMANENT, SHALL BE |
| | MADE AVAILABLE AS SOON AS COMBUSTIBLE MATERIAL ARRIVES |
| | ON THE SITE. PLEASE PROVIDE WHERE THIS CONNECTION WILL |
| | BE MADE. |
| | |
| | 13) NOTICE: 2014 FBC-B [F] 3311.1 WHERE REQUIRED. IN |
| | BUILDINGS REQUIRED TO HAVE STANDPIPES BY SECTION |
| | 905.3.1, NOT LESS THAN ONE STANDPIPE SHALL BE PROVIDED |
| | FOR USE DURING CONSTRUCTION. SUCH STANDPIPES SHALL BE |
| | INSTALLED WHEN THE PROGRESS OF CONSTRUCTION IS NOT MORE |
| | THAN 40 FEET (12 192 MM) IN HEIGHT ABOVE THE LOWEST |
| | LEVEL OF FIRE DEPARTMENT VEHICLE ACCESS. SUCH STANDPIPE |
| | SHALL BE PROVIDED WITH FIRE DEPARTMENT HOSE CONNECTIONS |
| | AT ACCESSIBLE LOCATIONS ADJACENT TO USABLE STAIRS. SUCH |
| | STANDPIPES SHALL BE EXTENDED AS CONSTRUCTION PROGRESSES |
| | TO WITHIN ONE FLOOR OF THE HIGHEST POINT OF |
| | CONSTRUCTION HAVING SECURED DECKING OR FLOORING. |
| | |
| | 14A) 2014 FBC-B [F] 3309.1 WHERE REQUIRED. ALL |
| | STRUCTURES UNDER CONSTRUCTION SHALL BE PROVIDED WITH |
| | NOT LESS THAN ONE APPROVED PORTABLE FIRE EXTINGUISHER |
| | IN ACCORDANCE WITH SECTION 906 AND SIZED FOR NOT LESS |
| | THAN ORDINARY HAZARD AS FOLLOWS: |
| | 1. AT EACH STAIRWAY ON ALL FLOOR LEVELS WHERE |
| | COMBUSTIBLE MATERIALS HAVE ACCUMULATED. |
| | 2. IN EVERY STORAGE AND CONSTRUCTION SHED. |
| | 3. ADDITIONAL PORTABLE FIRE EXTINGUISHERS SHALL BE |
| | PROVIDED WHERE SPECIAL HAZARDS EXIST, SUCH AS THE |
| | STORAGE AND USE OF FLAMMABLE AND COMBUSTIBLE LIQUIDS. |
| | |
| | 14B) 2014 FBC-B 3309.2 FIRE HAZARDS. THE PROVISIONS OF |
| | THIS CODE AND THE FLORIDA FIRE PREVENTION CODE SHALL BE |
| | STRICTLY OBSERVED TO SAFEGUARD AGAINST ALL FIRE HAZARDS |
| | ATTENDANT UPON CONSTRUCTION OPERATIONS. |
| | |
| | 15) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION 109.3.10.1 HURRICANE PROTECTION. IT |
| | SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION |
| | RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE |
| | OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 |
| | HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE |
| | HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE |
| | EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN |
| | SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH |
| | CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING |
| | DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY |
| | PERSONS WHO FAILS TO COMPLY TO COMPLY TO REMOVE OR |
| | SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS |
| | WITHIN 24 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED |
| | SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN |
| | ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO |
| | VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE |
| | PURSUANT TO SECTION 113 OF THIS CHAPTER. |
| | |
| | 16) SHEET L.S.101: |
| | 16A) FIRE PROTECTION GENERAL NOTES # 1 GC TO INSTALL |
| | FIRE/ SMOKE DETECTION SYSTEM AS APPLICABLE CODES FOR |
| | USE AND OCCUPANCY. PLEASES BE SPECIFIC TO THE 2014 |
| | FBC-B. |
| | |
| | 16B) UNDER THE HEADING CONSTRUCTION TYPE/ OCCUPANCY THE |
| | BUILDING CONSTRUCTION TYPE IS LISTED AS A TYPE IIB/ R1 |
| | OCCUPANCY TYPE. THE TYPE OF AUTOMATIC FIRE SPRINKLER |
| | SYSTEM IS NOT MENTIONED IN THE CONSTRUCTION TYPE NOR IN |
| | THE FIRE PROTECTION PLANS. PLEASE DESIGNATE WHAT TYPE |
| | OF FIRE SPRINKLER SYSTEM IS DESIGNED FOR THIS BUILDING. |
| | NOTE TABLE 503 ONLY ALLOWS 4 STORIES FOR A IIA/ R1 |
| | OCCUPANCY. DECLARE THE TYPE OF FIRE SPRINKLERS AND AREA |
| | INCREASES TAKEN UNDER FBC-B 506.1 AND EQUATION 5-1 FOR |
| | AREA AND SPRINKLER INCREASES. |
| | |
| | 16C) BUILDING OCCUPANCY CLASSIFICATION HEADING: |
| | 16C)(1) PLEASE REVIEW BASEMENT RESIDENTIAL CATEGORY & |
| | OCCUPANCY COUNT. SEE FBC-B TABLE 1004.1.2 FUNCTION |
| | ACCESSORY STORAGE AREAS AND OCCUPANT LOAD FACTOR 300 |
| | GROSS. |
| | |
| | 16C)(2) PLEASE REVIEW THE GROUND FLOOR AND THE |
| | RESIDENTIAL CATEGORY R1. THE LOBBY AREA INCLUDING THE |
| | DELI AREA ARE ALL CONSIDERED A BUSINESS OCCUPANCY @ 100 |
| | SQ. FT./ OCCUPANT. SEE FBC-B TABLE 1004.1.2. UPDATE |
| | PLANS. |
| | |
| | 16 C)(3) PLEASE PROVIDE THE TOTAL SQ. FT. OF THE |
| | BUILDING AREA AND REVISED TOTAL OCCUPANT LOAD FOR THE |
| | BUILDING. |
| | |
| | 16D) PLEASE UPDATE BOTH EGRESS REQUIREMENTS AND FIXTURE |
| | COUNT SINCE THE OCCUPANCY LOADS WILL BE INCREASED. |
| | FBC-B TABLE 1004.1.2. |
| | |
| | 16E) THE PLANS INDICATE THIS IS A R1 OCCUPANCY BUT |
| | PLEASE CONFIRM THAT THE UNITS THEMSELVES ARE TO BE |
| | CONSIDERED EITHER SLEEPING UNITS OR DWELLING UNITS. THE |
| | PLANS ARE VAGUE AS TO IF THERE IS TO BE A KITCHEN OR |
| | KITCHENETTE. IF THE SUITES ARE TO BE CONSIDERED A |
| | DWELLING UNIT THEN COMPLIANCE WITH THE FOLLOWING 3 CODE |
| | SECTIONS WOULD BE REQUIRED FOR BUILDING TYPE IIA/ R1- |
| | IF (DWELLING UNIT). |
| | FOR TILE, STONE, MARBLE AND WOOD FLOORING ALL NEED TO |
| | HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR ASSEMBLIES |
| | TO THE FOLLOWING STANDARDS AND MEET THE QUALIFICATIONS |
| | LISTED UNDER EACH OF THE STANDARDS FOR A 8 INCH |
| | CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| | PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| | |
| | 16E)(1) FBC-B 2014 1207.3 STRUCTURE-BORNE SOUND. |
| | FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| | BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| | WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| | CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| | TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| | |
| | 16E)(2) FBC-B 2014 1207.2 AIR-BORNE SOUND. |
| | WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| | SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| | PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| | CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| | FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| | E 90. |
| | |
| | 16E)(3) FLAME SPREAD- FBC-B 2014 603.1. EXCEPTION 2. |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| | |
| | FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| | A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| | MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| | MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| | |
| | 16F) PLEASE REVIEW THE TRAVEL DISTANCE FROM THE |
| | FURTHEST POINT IN THE LAUNDRY. THIS POINT IS TO BE |
| | TAKEN FROM THE FURTHEST POINT IN THE LAUNDRY ROOM AND |
| | THEN THE TRAVEL ROUTE TO BE TAKEN 1 FOOT FROM THE WALL |
| | LINE FURNITURE OR EQUIPMENT TO THE EXIT DOOR WAY. |
| | COMMON PATH OF TRAVEL, FBC-B TABLE 1014.3. STORAGE |
| | OCCUPANCY < 30 OCCUPANCY ALLOWS FOR 100 FT. TRAVEL |
| | DISTANCE/ SPRINKLERED BUILDING. |
| | |
| | 16F) THE LIFE SAFETY SHEET IS SILENT AS TO THE FIRE |
| | RATING REQUIREMENTS FOUND IN FBC-B TABLE 601 & 602. |
| | |
| | 704.2 COLUMN PROTECTION. WHERE COLUMNS ARE REQUIRED TO |
| | HAVE PROTECTION TO BE FIRE-RESISTANCE RATED, THE ENTIRE |
| | COLUMN SHALL BE PROVIDED INDIVIDUAL ENCASEMENT |
| | PROTECTION BY PROTECTING IT ON ALL SIDES FOR THE FULL |
| | COLUMN LENGTH, INCLUDING CONNECTIONS TO OTHER |
| | STRUCTURAL MEMBERS, WITH MATERIALS HAVING THE REQUIRED |
| | FIRE-RESISTANCE RATING. WHERE THE COLUMN EXTENDS |
| | THROUGH A CEILING, THE ENCASEMENT PROTECTION SHALL BE |
| | CONTINUOUS FROM THE TOP OF THE FOUNDATION OR |
| | FLOOR/CEILING ASSEMBLY BELOW THROUGH THE CEILING SPACE |
| | TO THE TOP OF THE COLUMN. |
| | |
| | 704.3 PROTECTION OF THE PRIMARY STRUCTURAL FRAME OTHER |
| | THAN COLUMNS. MEMBERS OF THE PRIMARY STRUCTURAL FRAME |
| | OTHER THAN COLUMNS THAT ARE REQUIRED TO HAVE PROTECTION |
| | TO ACHIEVE A FIRE-RESISTANCE RATING AND SUPPORT MORE |
| | THAN TWO FLOORS OR ONE FLOOR AND ROOF, OR SUPPORT A |
| | LOAD-BEARING WALL OR A NONLOAD-BEARING WALL MORE THAN |
| | TWO STORIES HIGH, SHALL BE PROVIDED INDIVIDUAL |
| | ENCASEMENT PROTECTION BY PROTECTING THEM ON ALL SIDES |
| | FOR THE FULL LENGTH, INCLUDING CONNECTIONS TO OTHER |
| | STRUCTURAL MEMBERS, WITH MATERIALS HAVING THE REQUIRED |
| | FIRE-RESISTANCE RATING. |
| | |
| | 704.4 PROTECTION OF SECONDARY MEMBERS. SECONDARY |
| | MEMBERS THAT ARE REQUIRED TO HAVE A FIRE-RESISTANCE |
| | RATING SHALL BE PROTECTED BY INDIVIDUAL ENCASEMENT |
| | PROTECTION, BY THE MEMBRANE OR CEILING OF A HORIZONTAL |
| | ASSEMBLY IN ACCORDANCE WITH SECTION 711, OR BY A |
| | COMBINATION OF BOTH. |
| | |
| | 17) SHEET A2.01B BASEMENT LEVEL; |
| | 17A) THE LAUNDRY TERMINATION ROOM, LAUNDRY ROOM ARE IN |
| | THE SAME ROOM. THE PLANS DO NOT INDICATE WHERE THE |
| | LAUNDRY TERMINATION ROOM ENDS AND WHERE THE CORRIDOR |
| | BEGINS. THE PLANS DO NOT INDICATE WHERE THE DIRTY |
| | LAUNDRY CARTS ARE GOING TO BE STORED EITHER. THE PLANS |
| | ALSO SHOW THE SAME LAUNDRY TERMINATION ROOM AS THE |
| | LAUNDRY ROOM. THE PLANS ARE SILENT AS TO WHERE THE |
| | CLEAN LINENS ARE TO BE STORED, NOR DO THE PLANS |
| | INDICATE WHAT WILL BE STORED IN THE BASEMENT LEVEL |
| | STORAGE ROOM. THIS WHOLE AREA NEEDS TO SHOW HOW |
| | COMPLIANCE WITH ALL THESE CONCERNS ARE GOING TO BE |
| | ADDRESSED. |
| | PLEASE SEE FBC-B 1014.2 EGRESS THROUGH INTERVENING |
| | SPACES. EGRESS THROUGH INTERVENING SPACES SHALL COMPLY |
| | WITH THIS SECTION. 4. EGRESS SHALL NOT PASS THROUGH |
| | STORAGE ROOMS, CLOSETS OR SPACES USED FOR SIMILAR |
| | PURPOSES. |
| | |
| | 17B) 2014 FBC-B 713.13.4 TERMINATION ROOM. REFUSE, |
| | RECYCLING, AND LAUNDRY CHUTES SHALL DISCHARGE INTO AN |
| | ENCLOSED ROOM SEPARATED FROM THE REMAINDER OF THE |
| | BUILDING BY FIRE BARRIERS CONSTRUCTED IN ACCORDANCE |
| | WITH SECTION 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED |
| | IN ACCORDANCE WITH SECTION 711, OR BOTH. |
| | |
| | 17C) 713.13.4 TERMINATION ROOM. OPENINGS INTO THE |
| | TERMINATION ROOM SHALL BE PROTECTED BY OPENING |
| | PROTECTIVES HAVING A FIRE PROTECTION RATING EQUAL TO |
| | THE PROTECTION REQUIRED FOR THE SHAFT ENCLOSURE. 2 HOUR |
| | SHAFT ENCLOSURES REQUIRE 1 ? HOUR OPENING PROTECTIVES |
| | TABLE 716.5. |
| | |
| | 17D) 713.13.4 TERMINATION ROOM. DOORS SHALL BE SELF- OR |
| | AUTOMATIC-CLOSING UPON THE DETECTION OF SMOKE IN |
| | ACCORDANCE WITH SECTION 716.5.9.3. DOOR NOT SHOWN ON |
| | THE PLANS. |
| | |
| | 17E)LAUNDRY CHUTE DETAILS. SEE SHEET A6.05 THESE |
| | DETAILS SEEM TO BE TAKEN FROM A DETAIL SHEET PAGE 2 AND |
| | 3 WHERE THEY ARE NOTE SHOWN. NOTES 1,2,3,8,9,12 & 13. |
| | 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED. |
| | |
| | 17F) PLEASE NOTE IN THIS DETAIL THE 2 HOUR FIRE RATED |
| | SHAFT IS NOT SHOWN. IT IS NOT CLEAR IF THE SHAFT |
| | CONTINUES DOWN INTO THE TERMINATION ROOM AND THE 1 ? |
| | HOUR PROTECTIVE IS THE NOTE(3) DISCHARGE DOOR. THE |
| | PLANS DO NOT INDICATE ANY FIRE RATING. |
| | |
| | 17G)(1) THE PLANS ARE NOT CLEAR WITH NOTE 7 AND NOTE 12 |
| | IF THESE ARE A SEPARATE ITEM NOT DEALING WITH THE |
| | REQUIREMENTS FOR 713.13.6 AUTOMATIC SPRINKLER SYSTEM. |
| | AN APPROVED AUTOMATIC SPRINKLER SYSTEM SHALL BE |
| | INSTALLED IN ACCORDANCE WITH SECTION 903.2.11.2. |
| | 17G)(2) FBC-B 903.2.11.2 RUBBISH AND LINEN CHUTES. AN |
| | AUTOMATIC SPRINKLER SYSTEM SHALL BE INSTALLED AT THE |
| | TOP OF RUBBISH AND LINEN CHUTES AND IN THEIR TERMINAL |
| | ROOMS. CHUTES SHALL HAVE ADDITIONAL SPRINKLER HEADS |
| | INSTALLED AT ALTERNATE FLOORS AND AT THE LOWEST INTAKE. |
| | WHERE A RUBBISH CHUTE EXTENDS THROUGH A BUILDING MORE |
| | THAN ONE FLOOR BELOW THE LOWEST INTAKE, THE EXTENSION |
| | SHALL HAVE SPRINKLERS INSTALLED THAT ARE RECESSED FROM |
| | THE DROP AREA OF THE CHUTE AND PROTECTED FROM FREEZING |
| | IN ACCORDANCE WITH SECTION 903.3.1.1. SUCH SPRINKLERS |
| | SHALL BE INSTALLED AT ALTERNATE FLOORS, BEGINNING WITH |
| | THE SECOND LEVEL BELOW THE LAST INTAKE AND ENDING WITH |
| | THE FLOOR ABOVE THE DISCHARGE. CHUTE SPRINKLERS SHALL |
| | BE ACCESSIBLE FOR SERVICING. |
| | |
| | 17H) THE SOILED LINEN WHERE TO STORE? VERSES THE CLEAN |
| | LINEN ROOMS. TABLE 509 INCIDENTAL USES. |
| | |
| | 17I) INTERIOR WALLS DO NOT HAVE IDENTIFICATION TAGS |
| | IDENTIFYING WALL TYPES. 107.3.5.1.1 MINIMUM COMMERCIAL |
| | PLAN REVIEW REQUIREMENTS. (4) FIRE RESISTANT |
| | CONSTRUCTION. |
| | |
| | 18) SHEET A2.01A. GROUND FLOOR; |
| | 18A) THIS FLOOR DOES HAVE WALL IDENTIFICATION TAGS. |
| | WALL TYPES ARE FOUND ON SHEET A8.03. |
| | THERE ARE (2) ISSUES WITH THE WALL TYPES FOUND ON THIS |
| | SHEET. |
| | |
| | 18A)(1) FOR THE METAL STUD FIRE RATED WALLS THESE WALL |
| | TYPES LIST A UL FIRE RATING AND HOUR RATING. WHAT THE |
| | DESIGNER OF RECORD DIDN?T INCLUDE WAS A SHEET THAT |
| | GIVES EACH OF THE WALL ASSEMBLY BREAK DOWNS AS IN THE |
| | UL LISTING BOOK. THE INSPECTORS NEED THIS INFORMATION |
| | TO VERIFY THE WALLS WERE BUILT CORRECTLY ACCORDING TO |
| | THE WALL ASSEMBLY AS TESTED. FBC-B 703.2 |
| | FIRE-RESISTANCE RATINGS. |
| | |
| | 18B) PLEASE SHOW THE MASONRY WALLS 4 INCH / 2 HR. RATED |
| | WITH THE CENTER CAVITY. THE DESIGN # 906 IS FOR 6INCH |
| | BLOCK EITHER HOLLOW OR SOLID BUT NOT FOR A 4 INCH BLOCK |
| | WALL. 107.2.1.3 ADDITIONAL INFORMATION REQUIRED. FBC-B |
| | TABLE 722.3.2 MINIMUM EQUIVALENT THICKNESS (INCHES) OF |
| | BEARING OR NONBEARING CONCRETE MASONRY WALLS. |
| | |
| | 18C) THE L. S. SHEET NOR THE GROUND FLOOR SHOW THE |
| | PARKING GARAGE AS DESIGNED OPEN OR ENCLOSED. THE PLANS |
| | DO NOT APPEAR TO MAKE THE REQUIREMENTS FOR AN OPEN |
| | PARKING GARAGE UNDER SECTION FBC-B 406.5.2 AND WILL |
| | NEED TO MEET THE REQUIREMENTS FOR 406.6.2 VENTILATION |
| | AND 406.6.3 AUTOMATIC SPRINKLER SYSTEM. |
| | THE M1.1 SHEET ALSO DOES NOT SHOW ANY MECHANICAL |
| | EQUIPMENT FOR MECHANICAL EQUIPMENT. THERE SEAMS TO BE A |
| | OPENING MISSING IN THE GARAGE CEILING (HIDDEN DASHED |
| | LINE) ON THE GRID LINE C/ 5 THAT GOES VERTICALLY |
| | THROUGH TO THE ROOF. IF THE DESIGNERS INTENT IS O TAKE |
| | CREDIT FOR THE 3 VERTICAL OPENS IN THE CEILING AS WELL |
| | AS THE ONE ON GRID LINE C/5 AS EQUAL TO CROSS |
| | VENTILATION FOR AN OPEN PARKING GARAGE, THEN |
| | CALCULATIONS WILL BE NEEDED TO PROVIDE CODE COMPLIANCE |
| | UNDER SECTION 104.11 ALTERNATE MATERIALS, DESIGN AND |
| | METHODS OF CONSTRUCTION AND EQUIPMENT. A LETTER TO THE |
| | BUILDING OFFICIAL WOULD ALSO NEED TO FOLLOW ASKING THIS |
| | DESIGN TO BE REVIEWED UNDER 104.11 ALTERNATE MATERIALS, |
| | DESIGN AND METHODS OF CONSTRUCTION AND EQUIPMENT. |
| | |
| | 104.11.1 RESEARCH REPORTS. SUPPORTING DATA, WHERE |
| | NECESSARY TO ASSIST IN THE APPROVAL OF MATERIALS OR |
| | ASSEMBLIES NOT SPECIFICALLY PROVIDED FOR IN THIS CODE, |
| | SHALL CONSIST OF VALID RESEARCH REPORTS FROM APPROVED |
| | SOURCES. |
| | |
| | 18D) THE NORTH PROPERTY LINE THERE IS A GATE MARKED # |
| | 3, THIS MOTORIZED GATE SHOWS IN THE OPEN POSITION ON |
| | BOTH THE GRADE PLAN AND LIFE SAFETY SHEET LS1.01. WHEN |
| | YOU LOOK AT THE ELEVATION SHEET A3.04 WHEN THE GATE IS |
| | IN THE CLOSED POSITION IT BLOCKS THE MEANS OF EGRESS |
| | FROM THE NORTH STAIR TOWER. |
| | |
| | 2014 FBC-B 1008.2 GATES. GATES SERVING THE MEANS OF |
| | EGRESS SYSTEM SHALL COMPLY WITH THE REQUIREMENTS OF |
| | THIS SECTION. GATES USED AS A COMPONENT IN A MEANS OF |
| | EGRESS SHALL CONFORM TO THE APPLICABLE REQUIREMENTS FOR |
| | DOORS. |
| | 2014 FBC-B 1008.1.2 DOOR SWING. EXCEPTION 9. IN OTHER |
| | THAN GROUP H OCCUPANCIES, MANUALLY OPERATED HORIZONTAL |
| | SLIDING DOORS ARE PERMITTED IN A MEANS OF EGRESS FROM |
| | SPACES WITH AN OCCUPANT LOAD OF 10 OR LESS. |
| | |
| | DOORS SHALL SWING IN THE DIRECTION OF EGRESS TRAVEL |
| | WHERE SERVING A ROOM OR AREA CONTAINING AN OCCUPANT |
| | LOAD OF 50 OR MORE PERSONS OR A GROUP H OCCUPANCY. |
| | |
| | 18E) THIS SAME AREA THERE IS A DELIVERY SERVICE AREA 10 |
| | FT. X 25 FT. PLEASE SHOW WHERE THE EXIT DISCHARGE PATH |
| | OF EGRESS WILL OCCUR SINCE THE DELIVERY LANE IS 10 FEET |
| | WIDE AND FROM THE BUILDING TO THE PROPERTY LINE |
| | THERE IS ONLY 11 FEET . |
| | |
| | 1027.4.1 WIDTH. THE MINIMUM WIDTH OF EGRESS COURTS |
| | SHALL BE DETERMINED AS SPECIFIED IN SECTION 1005.1, BUT |
| | SUCH WIDTH SHALL NOT BE LESS THAN 44 INCHES (1118 MM), |
| | EXCEPT AS SPECIFIED HEREIN. EGRESS COURTS SERVING GROUP |
| | R- 3 AND U OCCUPANCIES SHALL NOT BE LESS THAN 36 INCHES |
| | (914 MM) IN WIDTH. THE REQUIRED WIDTH OF EGRESS COURTS |
| | SHALL BE UNOBSTRUCTED TO A HEIGHT OF 7 FEET (2134 MM). |
| | |
| | 1027.4.2 CONSTRUCTION AND OPENINGS. WHERE AN EGRESS |
| | COURT SERVING A BUILDING OR PORTION THEREOF IS LESS |
| | THAN 10 FEET (3048 MM) IN WIDTH, THE EGRESS COURT WALLS |
| | SHALL HAVE NOT LESS THAN 1-HOUR FIRE-RESISTANCE-RATED |
| | CONSTRUCTION FOR A DISTANCE OF 10 FEET (3048 MM) ABOVE |
| | THE FLOOR OF THE COURT. OPENINGS WITHIN SUCH WALLS |
| | SHALL BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE |
| | PROTECTION RATING OF NOT LESS THAN 3/4 HOUR. |
| | |
| | 18F) THE SOUTH STAIRWAY THE WALKWAY IS NOT DIMENSIONED |
| | AS TO WIDTH. PLEASE NOTE THE STORAGE DOORS 121 BEING 3 |
| | FOOT WIDE DOORS. SEE SECTION 1005.7.1 DOORS. DOORS IN |
| | ANY POSITION SHALL NOT REDUCE THE REQUIRED WIDTH BY |
| | MORE THAN ONE-HALF THE REQUIRED EGRESS PATH. |
| | |
| | 18G) THE GATE # 101 IS A OUT SWING GATE AND HAS LESS |
| | THAN 18 INCHES ON THE PULL SIDE OF THE LATCH. SEE 2014 |
| | ACCESS. CODE 404.2.4 MANEUVERING CLEARANCES. |
| | |
| | 18H) PLEASE REVIEW THE ENTRY INTO THE PARKING GARAGE |
| | SOUTH SIDE OF THE BUILDING THERE IS A MOTORIZED GATE. |
| | THE LOCATION OF THE GATE MOTOR WILL BLOCK ACCESS FOR |
| | PEOPLE EXITING THE GARAGE TO THE PUBLIC WAY, THE GATE |
| | IN THE CLOSED POSITION WOULD STILL HAVE TO HAVE A FRAME |
| | WORK OVER THIS EXIT DISCHARGE. WHEN THE GATE IS IN THE |
| | OPEN POSITION THE GATE FRAMEWORK WOULD EXTEND PAST THE |
| | PROPERTY LINE. THE SECOND ISSUE IS FOR THIS WALKWAY TO |
| | BE ACCESSIBLE THERE CANNOT BE A STEP FROM THE GARAGE UP |
| | TO THE LANDING FOR THE VERTICAL EXIT. |
| | THIS IS THE ONLY EXIT OUT OF THE GARAGE. 2014 |
| | FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS |
| | SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| | INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| | SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| | BUILDING CODE (2003 EDITION). |
| | |
| | 18I) THERE SEEMS TO BE A DISCREPANCY IN PLANS WITH THE |
| | LOCATION OF GATE # 101. PLEASE ALSO SEE THE SOUTH |
| | ELEVATION A4.03 107.2.1.3 ADDITIONAL INFORMATION IS |
| | REQUIRED. |
| | |
| | 18J) GATE # 103 SWINGS BACK IN THE FLOW OF EGRESS. |
| | FBC-B 1008.2 GATES. GATES SERVING THE MEANS OF EGRESS |
| | SYSTEM SHALL COMPLY WITH THE REQUIREMENTS OF THIS |
| | SECTION. GATES USED AS A COMPONENT IN A MEANS OF EGRESS |
| | SHALL CONFORM TO THE APPLICABLE REQUIREMENTS FOR DOORS. |
| | 1008.1.2 DOOR SWING. DOORS SHALL SWING IN THE DIRECTION |
| | OF EGRESS TRAVEL WHERE SERVING A ROOM OR AREA |
| | CONTAINING AN OCCUPANT LOAD OF 50 OR MORE PERSONS OR A |
| | GROUP H OCCUPANCY. |
| | |
| | 18K) THE PLANS DO NOT INDICATE A CUT SECTION THROUGH |
| | THE FRONT COUNTER FOR REGISTERING. PLEASE SHOW HOW |
| | COMPLIANCE WITH ACCESS. CODE 904.3.2 COUNTER & 904.4 |
| | SALES AND SERVICE COUNTERS. , 904.3.3 CHECK WRITING |
| | SURFACES & WHERE PROVIDED, CHECK WRITING SURFACES SHALL |
| | COMPLY WITH 902.3. |
| | |
| | 19) SHEET A2.02 THE SECOND FLOOR LEVEL: |
| | 19A) THE ACCESSIBLE SUITE # 2 IS MISSING THE 18 INCHES |
| | ON THE INTERIOR SIDE OF THE MAIN ENTRY DOOR. SEE 2014 |
| | ACCESS. CODE 404.2.4. |
| | |
| | 19B) THE ACCESSIBLE SUITE SHOWS A DETAIL # 1/ A7.2 |
| | SHOULD INCLUDE THE KITCHENETTE UNIT SINCE IT IS WITHIN |
| | THE DETAIL, NOT INCLUDED. PLEASE PROVIDE ELEVATION |
| | DETAILS FOR THE KITCHENETTE AREA AND COMPLIANCE WITH; |
| | ACCESS. CODE 606.3 HEIGHT. LAVATORIES AND SINKS SHALL |
| | BE INSTALLED WITH THE FRONT OF THE HIGHER OF THE RIM OR |
| | COUNTER SURFACE 34 INCHES (865 MM) MAXIMUM ABOVE THE |
| | FINISH FLOOR OR GROUND. |
| | 606.2 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE COMPLYING |
| | WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE |
| | AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED. |
| | |
| | 19C) THE ACCESSIBLE SUITE DOES NOT INDICATE HOW |
| | COMPLIANCE WITH 242.2 ACCESSIBLE SWIMMING POOLS ARE |
| | GOING TO BE ACHIEVED. SEE EXCEPTION 1 REQUIREMENT. |
| | WHERE A SWIMMING POOL HAS LESS THAN 300 LINEAR FEET OF |
| | SWIMMING POOL WALL, NO MORE THAN ONE ACCESSIBLE MEANS |
| | OF ENTRY SHALL BE REQUIRED PROVIDED THAT THE ACCESSIBLE |
| | MEANS OF ENTRY IS A SWIMMING POOL LIFT COMPLYING WITH |
| | 1009.2 OR SLOPED ENTRY COMPLYING WITH 1009.3. |
| | |
| | 19D) THIS IS GOING TO BE A COMMENT FOR ALL UNITS NOT |
| | JUST THE ACCESSIBLE UNIT. THE PLANS SHOW SLIDING GLASS |
| | DOORS THAT LED FROM WITHIN THE SUITE OUT TO THE TERRACE |
| | DECK. THE COMPLETE OPENING BEING 14 FOOT 10 INCHES WIDE |
| | DIVIDE BY 3 EQUALS OR EACH PANEL 4 FT. 11 ? INCHES |
| | APPROXIMATELY. THIS SIZE DOOR CAN BE USED IN A MEANS OF |
| | EGRESS WHEN THE OCCUPANT LOAD IS 10 OR LESS, 1008.1.2 |
| | EXCEP. #9. THE DOOR IS 19/32 IN. LAMINATED GLASS. |
| | 2014 FBC-B 1008.1.3 DOOR OPENING FORCE. THE FORCE FOR |
| | PUSHING OR PULLING OPEN INTERIOR SWINGING EGRESS DOORS, |
| | OTHER THAN FIRE DOORS, SHALL NOT EXCEED 5 POUNDS (22 |
| | N). FOR OTHER SWINGING DOORS, AS WELL AS SLIDING AND |
| | FOLDING DOORS, THE DOOR LATCH SHALL RELEASE WHEN |
| | SUBJECTED TO A 15-POUND (67 N) FORCE. THE DOOR SHALL BE |
| | SET IN MOTION WHEN SUBJECTED TO A 30-POUND (133 N) |
| | FORCE. THE DOOR SHALL SWING TO A FULL-OPEN POSITION |
| | WHEN SUBJECTED TO A 15-POUND (67 N) FORCE. |
| | FOR THE ACCESSIBLE UNIT THE OPENING FORCE FOR THE |
| | SLIDING GLASS DOOR WILL BE FBC-ACCESS. CODE 404.2.9 |
| | DOOR AND GATE OPENING FORCE. FIRE DOORS SHALL HAVE A |
| | MINIMUM OPENING FORCE ALLOWABLE BY THE APPROPRIATE |
| | ADMINISTRATIVE AUTHORITY. THE FORCE FOR PUSHING OR |
| | PULLING OPEN A DOOR OR GATE OTHER THAN FIRE DOORS SHALL |
| | BE AS FOLLOWS: 2. SLIDING OR FOLDING DOORS: 5 POUNDS |
| | (22.2 N) MAXIMUM. |
| | |
| | 19E) THE OTHER ISSUE COMMON TO ALL UNITS WITH THE |
| | SLIDING DOOR TO THE POOL DECK IS: 404.2.7 DOOR AND GATE |
| | HARDWARE. HANDLES, PULLS, LATCHES, LOCKS, AND OTHER |
| | OPERABLE PARTS ON DOORS AND GATES SHALL COMPLY WITH |
| | 309.4. OPERABLE PARTS OF SUCH HARDWARE SHALL BE 34 |
| | INCHES (865 MM) MINIMUM AND 48 INCHES (1220 MM) MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND. WHERE SLIDING DOORS |
| | ARE IN THE FULLY OPEN POSITION, OPERATING HARDWARE |
| | SHALL BE EXPOSED AND USABLE FROM BOTH SIDES. |
| | EXCEPTIONS: 2. ACCESS GATES IN BARRIER WALLS AND FENCES |
| | PROTECTING POOLS, SPAS, AND HOT TUBS SHALL BE PERMITTED |
| | TO HAVE OPERABLE PARTS OF THE RELEASE OF LATCH ON |
| | SELF-LATCHING DEVICES AT 54 INCHES (1370 MM) MAXIMUM |
| | ABOVE THE FINISH FLOOR OR GROUND PROVIDED THE |
| | SELF-LATCHING DEVICES ARE NOT ALSO SELF-LOCKING DEVICES |
| | AND OPERATED BY MEANS OF A KEY, ELECTRONIC OPENER, OR |
| | INTEGRAL COMBINATION LOCK. |
| | |
| | THE DOORS ARE TO BE SELF-CLOSING AND SELF-LATCHING. |
| | FBC-B 454.1.3.1.9 ACCESS THROUGH THE BARRIER OR FENCE |
| | FROM DWELLING UNITS, SUCH AS HOMES, APARTMENTS, MOTEL |
| | ROOMS AND HOTEL ROOMS, SHALL BE THROUGH SELF-CLOSING, |
| | SELF-LATCHING LOCKABLE GATES OF 48 INCH (1219 MM) |
| | MINIMAL HEIGHT FROM THE FLOOR OR GROUND WITH THE LATCH |
| | LOCATED A MINIMUM OF 54 INCHES (1372 MM) FROM THE |
| | BOTTOM OF THE GATE OR AT LEAST 3 INCHES (76 MM) BELOW |
| | THE TOP OF THE GATE ON THE POOL SIDE. IF THE |
| | SELF-CLOSING, SELF-LATCHING GATE IS ALSO SELF-LOCKING |
| | AND IS OPERATED BY A KEY LOCK, ELECTRONIC OPENER OR |
| | INTEGRAL COMBINATION LOCK, THEN THE OPERABLE PARTS OF |
| | SUCH LOCKS OR OPENERS SHALL BE 34 INCHES MINIMUM (864 |
| | MM) AND 48 INCHES MAXIMUM (1219 MM) ABOVE THE FINISHED |
| | FLOOR OR GROUND. |
| | |
| | 19F) PLEASE NOTE THE SLIDING GLASS DOOR, THE THRESHOLD |
| | INDICATES ONLY TO BE ? INCH HIGH. 404.2.5 THRESHOLDS. |
| | THRESHOLDS, IF PROVIDED AT DOORWAYS, SHALL BE 1/2 INCH |
| | (13 MM) HIGH MAXIMUM. RAISED THRESHOLDS AND CHANGES IN |
| | LEVEL AT DOORWAYS SHALL COMPLY WITH ACCESS. CODE 302 |
| | AND 303. HOW WILL WATER INTRUSION BE HANDLED IN A |
| | HURRICANE? |
| | |
| | 19G) COMMON COMMENT FOR ALL FLOORS. THE SHAFT WALLS FOR |
| | THE LAUNDRY CHUTE DO NOT HAVE WALL IDENTIFICATION TAGS. |
| | FBC-B 713.4 FIRE-RESISTANCE RATING. SHAFT ENCLOSURES |
| | SHALL HAVE A FIRE-RESISTANCE RATING OF NOT LESS THAN 2 |
| | HOURS WHERE CONNECTING FOUR STORIES OR MORE, AND NOT |
| | LESS THAN 1 HOUR WHERE CONNECTING LESS THAN FOUR |
| | STORIES. |
| | |
| | 19H) COMMON COMMENT FOR ALL FLOORS. PLEASE SEE DOOR # 8 |
| | TO THE HOSE KEEPING ROOM IN THE DOOR SCHEDULE MISSING |
| | THE FIRE RATING. FBC-B 713.13.3 REFUSE, RECYCLING AND |
| | LAUNDRY CHUTE ACCESS ROOMS. |
| | ACCESS OPENINGS FOR REFUSE, RECYCLING AND LAUNDRY |
| | CHUTES SHALL BE LOCATED IN ROOMS OR COMPARTMENTS |
| | ENCLOSED BY NOT LESS THAN 1-HOUR FIRE BARRIERS |
| | CONSTRUCTED IN ACCORDANCE WITH SECTION 707 OR |
| | HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 711, OR BOTH. OPENINGS INTO THE ACCESS ROOMS |
| | SHALL BE PROTECTED BY OPENING PROTECTIVES HAVING A FIRE |
| | PROTECTION RATING OF NOT LESS THAN 3/4 HOUR. DOORS |
| | SHALL BE SELF- OR AUTOMATIC-CLOSING UPON THE DETECTION |
| | OF SMOKE IN ACCORDANCE WITH SECTION 716.5.9.3. |
| | |
| | 20) THE ACCESSIBLE SUITE SHOWS A DETAIL # 1/ A7.2. THE |
| | ACCESSIBLE BATHROOM: |
| | 20A) THIS SHEET STATES MANY TIMES ON THE SHEET THIS IS |
| | A ADA COMPLIANT. PLEASE NOTE THE DESIGN MAYBE ADA |
| | COMPLIANT BUT THE STATE OF FLORIDA USES THE 2014 |
| | FLORIDA ACCESSIBILITY CODE THAT HAS BEEN APPROVED BY |
| | THE DEPARTMENT OF JUSTICE. THE FLORIDA ACCESSIBILITY |
| | CODE IS A MORE STRINGENT CODE THAN THE ADA. PLEASE |
| | REVIEW THE CLEAR FLOOR SPACE REQUIRED FOR THE WATER |
| | CLOSET. |
| | 2014 FBC-ACCESS. CODE 604.3.2 OVERLAP. THE REQUIRED |
| | CLEARANCE AROUND THE WATER CLOSET SHALL BE PERMITTED TO |
| | OVERLAP THE WATER CLOSET, ASSOCIATED GRAB BARS, |
| | DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT HOOKS, |
| | SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE AND |
| | CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE TURNING |
| | SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL BE |
| | LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE. |
| | 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE |
| | 60 INCHES (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM |
| | THE SIDE WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL. |
| | |
| | 20B) DETAIL D NOTE 11 INDICATES BACKING IS REQUIRED FOR |
| | ADAPTABLE BATHROOMS. TABLE 224.2 WILL REQUIRE AT LEAST |
| | ONE GUESTROOM/ BATHROOM TO COMPLY WITH GUEST ROOM WITH |
| | MOBILITY FEATURES, 609.8 STRUCTURAL STRENGTH. ALLOWABLE |
| | STRESSES SHALL NOT BE EXCEEDED FOR MATERIALS USED WHEN |
| | A VERTICAL OR HORIZONTAL FORCE OF 250 POUNDS IS APPLIED |
| | AT ANY POINT ON THE GRAB BAR, FASTENER, MOUNTING |
| | DEVICE, OR SUPPORTING STRUCTURE. |
| | |
| | 20C) PLEASE NOTE ON THE GRAB BAR DIMENSIONS THE 2014 |
| | FBC-ACCESSIBILITY CODE TAKES THE DIMENSIONS FROM THE |
| | TOP OF THE GRASPING SURFACE NOT CENTERLINE. 609.4. |
| | |
| | 20D) TOWEL BARS ARE NOT DIMENSIONED BUT SHOULD BE IN |
| | THE REACH RANGES FOR EITHER FORWARD OR SIDE APPROACH |
| | SEE FBC-ACCESS. CODE 308.1. |
| | 20E) COAT HOOKS AND SHELVING TO COMPLY WITH 604.2. |
| | |
| | 20F) THE STEAM SHOWER IN THE ACCESSIBLE GUEST UNIT WILL |
| | ALSO NEED TO SHOW COMPLIANCE WITH THE 2014 FBC-ACCESS. |
| | CODE ; |
| | 20F)(1) 612.2 BENCH. WHERE SEATING IS PROVIDED IN |
| | SAUNAS AND STEAM ROOMS, AT LEAST ONE BENCH SHALL COMPLY |
| | WITH 903. DOORS SHALL NOT SWING INTO THE CLEAR FLOOR |
| | SPACE REQUIRED BY 903.2. EXCEPTION: A READILY REMOVABLE |
| | BENCH SHALL BE PERMITTED TO OBSTRUCT THE TURNING SPACE |
| | REQUIRED BY 612.3 AND THE CLEAR FLOOR OR GROUND SPACE |
| | REQUIRED BY 903.2. |
| | |
| | 20F)(2) 612.3 TURNING SPACE. A TURNING SPACE COMPLYING |
| | WITH 304 SHALL BE PROVIDED WITHIN SAUNAS AND STEAM |
| | ROOMS. |
| | |
| | 21) SHEET A2.07 THESE COMMENTS WILL BE COMMON TO ALL |
| | FLOORS 2-5; |
| | 21A) NOTE # 14 INDICATES THE USE OF TREX DECK TERRACE |
| | AND CEILING. THERE IS NO PRODUCT INFORMATION FOR THE |
| | TREX DECK SYSTEM. PLEASE PROVIDE THE MANUFACTURERS |
| | SPECIFICATION, IF THIS IS A COMBUSTIBLE PRODUCT AND IF |
| | SO THE FLAME SPREAD AND TO WHAT STANDARD THE PRODUCT |
| | WAS TESTED TOO? SEE FBC-B SECTION 603 COMBUSTIBLE |
| | MATERIAL IN TYPE I AND II CONSTRUCTION. 603.1 ALLOWABLE |
| | MATERIALS. |
| | |
| | 21B) THERE ARE NO PLANS FOR THE TREX DECK DROP CEILING |
| | ASSEMBLY. TYPE OF FRAMING, MATERIAL, SPACING, SIZE OF |
| | FRAMING MEMBERS, ANCHORAGE TO THE DECK ABOVE IF STIFF |
| | BACKS ARE REQUIRED. 107.3.5 MINIMUM PLAN REVIEW |
| | CRITERIA FOR BUILDINGS. 107.3.5.1 COMMERCIAL BUILDINGS: |
| | DROPPED EXTERIOR CEILING ASSEMBLIES. |
| | |
| | 21C) DETAILS 3 & 4 BOTH INDICATE THE USE OF INSULATION |
| | IN BOTH THE MECHANICAL PLENUM AS WELL AS THE DROPPED |
| | CEILING WITHIN THE TYPICAL SUITE. THE PLANS DOES NOT |
| | DECLARE WHAT TYPE OF INSULATION IS GOING TO BE |
| | INSTALLED? IS THIS INSULATION GOING TO BE FOR BOTH |
| | SOUND AND THERMAL VALUES? SEE FBC-B 720.1 & 720.2. |
| | |
| | 21D) DETAILS 3 & 4 WITHIN THE SUITE SHOW A DROPPED |
| | CEILING ASSEMBLY, FASTENED TO THE CONCRETE DECK ABOVE |
| | AS WELL AS A DROPPED CEILING ASSEMBLY WITH WHAT MAYBE A |
| | LIGHT TROUGH. THE INSULATION ABOVE WOULD STILL BE |
| | WITHIN THE ROOM PROPER. PLEASE PROVIDE ADDITIONAL |
| | DETAILS AS TO THE TYPE OF FRAMING MATERIALS, ANCHORAGE |
| | TO THE DECK ABOVE, SIZE OF FRAMING MEMBERS, SPACING OF |
| | FRAMING MEMBERS THE TYPE OF INSULATION, THE THICKNESS |
| | AND TYPE OF FINISH MATERIAL FOR THE DROPPED CEILING. . |
| | 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | 107.3.5.1 COMMERCIAL BUILDINGS: DROPPED EXTERIOR |
| | CEILING ASSEMBLIES. |
| | FBC-B 720.3 EXPOSED INSTALLATION. INSULATING MATERIALS, |
| | WHERE EXPOSED AS INSTALLED IN BUILDINGS OF ANY TYPE OF |
| | CONSTRUCTION, SHALL HAVE A FLAME SPREAD INDEX OF NOT |
| | MORE THAN 25 AND A SMOKE-DEVELOPED INDEX OF NOT MORE |
| | THAN 450. |
| | FBC-B 803.11.2 SET-OUT CONSTRUCTION. WHERE WALLS AND |
| | CEILINGS ARE REQUIRED TO BE OF FIRE-RESISTANCE-RATED OR |
| | NONCOMBUSTIBLE CONSTRUCTION AND WALLS ARE SET OUT OR |
| | CEILINGS ARE DROPPED DISTANCES GREATER THAN SPECIFIED |
| | IN SECTION 803.11.1, CLASS A FINISH MATERIALS, IN |
| | ACCORDANCE WITH SECTION 803.1.1 OR 803.1.2, SHALL BE |
| | USED. |
| | |
| | 21E) PLEASE NOTE THE PLANS DO NOT ADDRESS THE FRAMING |
| | MEMBERS FOR THE POOL DECK. SHEET S-13 SECTION SHOWS |
| | 3X12?S AT 16 INCHES ON CENTER. THIS BUILDING IS |
| | CLASSIFIED AS A BUILDING TYPE IIA. |
| | |
| | FBC-B SECTION 603 COMBUSTIBLE MATERIAL IN TYPE I AND II |
| | CONSTRUCTION. 603.1 ALLOWABLE MATERIALS. EXCEPTION; 12. |
| | STAGES AND PLATFORMS CONSTRUCTED IN ACCORDANCE WITH |
| | SECTIONS 410.3 AND 410.4, RESPECTIVELY. |
| | 410.4 PLATFORM CONSTRUCTION. PERMANENT PLATFORMS SHALL |
| | BE CONSTRUCTED OF MATERIALS AS REQUIRED FOR THE TYPE OF |
| | CONSTRUCTION OF THE BUILDING IN WHICH THE PERMANENT |
| | PLATFORM IS LOCATED. PERMANENT PLATFORMS ARE PERMITTED |
| | TO BE CONSTRUCTED OF FIRE-RETARDANT-TREATED WOOD FOR |
| | TYPES I, II AND IV CONSTRUCTION WHERE THE PLATFORMS ARE |
| | NOT MORE THAN 30 INCHES (762 MM) ABOVE THE MAIN FLOOR, |
| | AND NOT MORE THAN ONE-THIRD OF THE ROOM FLOOR AREA AND |
| | NOT MORE THAN 3,000 SQUARE FEET (279 M2) IN AREA. WHERE |
| | THE SPACE BENEATH THE PERMANENT PLATFORM IS USED FOR |
| | STORAGE OR ANY PURPOSE OTHER THAN EQUIPMENT, WIRING OR |
| | PLUMBING, THE FLOOR ASSEMBLY SHALL BE NOT LESS THAN |
| | 1-HOUR FIRE-RESISTANCE-RATED CONSTRUCTION. WHERE THE |
| | SPACE BENEATH THE PERMANENT PLATFORM IS USED ONLY FOR |
| | EQUIPMENT, WIRING OR PLUMBING, THE UNDERSIDE OF THE |
| | PERMANENT PLATFORM NEED NOT BE PROTECTED. |
| | |
| | 21F) THE S-13 SHEET DOES NOT PROVIDE THE TYPE OF |
| | ANCHORS TO HOLD THE LEDGER BOARD NOR THE TYPE OF |
| | BUCKETS TO HOLD THE FRAMING MEMBERS. 107.3.5 MINIMUM |
| | PLAN REVIEW CRITERIA FOR BUILDINGS. 107.3.5.1 |
| | COMMERCIAL BUILDINGS. FLOOR SYSTEMS. |
| | |
| | 21G) POOLS AND ASSOCIATED EQUIPMENT WILL BE UNDER |
| | SEPARATE PERMITS FOR EACH UNIT FOR THE RECORDING OF |
| | INSPECTIONS. 105.1. PERMITS REQUIRED. |
| | |
| | 22) SHEET A3.03 THE GREEN SCREEN SYSTEM PANELS CAN BE A |
| | SUBMITTAL THAT COULD QUALIFY AS A DEFERRED SUBMITTAL, |
| | PLEASE PROVIDE THE WIND DESIGN PARAMETERS FOR THE |
| | SPECIALTY ENGINEERS CAN DESIGN TO THE PROPER WIND |
| | SPEED. 107.3.4.2 DEFERRED SUBMITTALS. 2014 FBC-B |
| | 1603.1.4 WIND DESIGN DATA. |
| | |
| | 23) SHEET A2.05 ROOF PLAN. |
| | |
| | 23A) THE ROOF DRAINS 2 & 3 BOTH ARE MISSING |
| | SECONDARY(EMERGENCY OVERFLOW) DRAINS OR SCUPPERS. FBC-B |
| | 1503.4.1. |
| | |
| | 23B) STAIR TOWER 1 & 2 BOTH SHOW OVERFLOW SCUPPERS BUT |
| | NO SECONDARY (EMERGENCY OVERFLOW) DRAINS OR SCUPPERS. |
| | FBC-B 1503.4.1. |
| | |
| | 23C) PLEASE PROVIDE DETAILS FOR SCUPPERS AND OVERFLOW |
| | SCUPPERS, THE BOTTOM OF EACH UNIT IN RELATIONSHIP WITH |
| | THE ROOF. FBC-B 1503.4.2 SCUPPERS. OVERFLOW SCUPPERS |
| | ARE SHOWN. |
| | |
| | 23D) PLEASE PROVIDE A ANCHORING DETAIL FOR THE ROOF TOP |
| | A/C STANDS FOR THE APPROPRIATE SIZE OF ROOF TOP |
| | COMPRESSOR. PLEASE ALSO INCLUDE THE ATTACHMENT OF THE |
| | COMPRESSOR TO THE STAND. FBC-B 2014 FBC-B 1604.4 |
| | ANALYSIS. LOAD EFFECTS ON STRUCTURAL MEMBERS AND THEIR |
| | CONNECTIONS SHALL BE DETERMINED BY METHODS OF |
| | STRUCTURAL ANALYSIS THAT TAKE INTO ACCOUNT EQUILIBRIUM, |
| | GENERAL STABILITY, GEOMETRIC COMPATIBILITY AND BOTH |
| | SHORT- AND LONG-TERM MATERIAL PROPERTIES. EVERY |
| | STRUCTURE SHALL BE DESIGNED TO RESIST THE OVERTURNING |
| | EFFECTS CAUSED BY THE LATERAL FORCES SPECIFIED IN THIS |
| | CHAPTER. SEE SECTION 1609 FOR WIND LOADS? |
| | |
| | 23E) PLEASE PROVIDE THE MINIMUM HEIGHT REQUIREMENTS FOR |
| | THE A/C STANDS IN COMPLIANCE WITH FBC-B TABLE 1509.6.5. |
| | |
| | 23F) ROOFTOP SKYLIGHTS. SECTION 603 COMBUSTIBLE |
| | MATERIAL IN TYPE I AND II CONSTRUCTION. 603.1 ALLOWABLE |
| | MATERIALS. 15. LIGHT-TRANSMITTING PLASTICS AS PERMITTED |
| | BY CHAPTER |
| | 26. PLEASE PROVIDE COMPLIANCE WITH: 2609.4 AREA |
| | LIMITATIONS. ROOF PANELS SHALL BE LIMITED IN AREA AND |
| | THE AGGREGATE AREA OF PANELS SHALL BE LIMITED BY A |
| | PERCENTAGE OF THE FLOOR AREA OF THE ROOM OR SPACE |
| | SHELTERED IN ACCORDANCE WITH TABLE 2609.4. CC1 OR CC2? |
| | |
| | 23G) SHEET A4.03 SHOWS A CUT SECTION THROUGH THE |
| | SKYLIGHT WITH A CMU CURB. THERE ARE NO DETAILS OF THIS |
| | CURB IN THE ARCHITECTURAL SHEETS NOR THE STRUCTURAL |
| | SHEETS. 107.2.1.3 ADDITIONAL INFORMATION IS ENQUIRED. |
| | |
| | 23H) PLEASE REVIEW NOTES ON THE RIGHT SIDE OF THE PAGE |
| | 1-15 THESE DEAL WITH THE FLOORS BELOW. NEED TO BE |
| | DELETED. 107.2.1.3 DISCREPANCY IN PLANS. |
| | |
| | 24) SHEET A6.03, ELEVATOR, PLEASE SHOW COMPLIANCE WITH |
| | FBC-B 3002.4 ELEVATOR CAR TO ACCOMMODATE AMBULANCE |
| | STRETCHER. THE ELEVATOR CAR SHALL BE OF SUCH A SIZE AND |
| | ARRANGEMENT TO ACCOMMODATE AN AMBULANCE STRETCHER 24 |
| | INCHES BY 76 INCHES (610 MM BY 2134 MM) WITH NOT LESS |
| | THAN 5-INCH RADIUS CORNERS, IN THE HORIZONTAL, OPEN |
| | POSITION AND SHALL BE IDENTIFIED BY THE INTERNATIONAL |
| | SYMBOL FOR EMERGENCY MEDICAL SERVICES (STAR OF LIFE). |
| | |
| | DO NOT QOUTE CODE. 107.2.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. SUCH INFORMATION SHALL BE SPECIFIC, AND THE |
| | TECHNICAL CODES SHALL NOT BE CITED AS A WHOLE OR IN |
| | PART,? |
| | |
| | 25) SHEET A4.03 PLEASE PROVIDE DETAILS FOR THE EYEBROW, |
| | ANCHORING AND TYPE OF MATERIALS CONSTRUCTED AT |
| | ELEVATION 71.416 FT. 1406.2.1 TYPE I, II, III AND IV |
| | CONSTRUCTION. ON BUILDINGS OF TYPE I, II, III AND IV |
| | CONSTRUCTION, EXTERIOR WALL COVERINGS SHALL BE |
| | PERMITTED TO BE CONSTRUCTED OF COMBUSTIBLE MATERIALS, |
| | COMPLYING WITH THE FOLLOWING LIMITATIONS: 2. |
| | COMBUSTIBLE EXTERIOR WALL COVERINGS SHALL BE LIMITED TO |
| | 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE PLANE. |
| | |
| | 26) SHEET A8.11: DETAILS SHOULD BE TO THE 2014 FLORIDA |
| | ACCESSIBILITY CODE NOT THE ADA. |
| | |
| | 26A) THE TOWEL BAR IS INDICATED TO BE 54 INCHES HIGH |
| | (ADA). MUST BE IN THE REACH RANGES FOR ACCESSIBILITY. |
| | SEE ACCESS. CODE 308.2.1 UNOBSTRUCTED FORWARD. 308.3.2 |
| | OBSTRUCTED SIDE REACH. |
| | |
| | 26B) ALL OF THE DETAILS FOR GRAB BARS ARE TAKEN AT THE |
| | CENTERLINE. PLEASE BE AWARE OF THE 2014 |
| | FBC-ACCESSIBILITY CODE 609.4 THE MEASUREMENTS ARE TO BE |
| | TAKEN FROM FINISH FLOOR TO THE TOP OF THE GRASPABLE |
| | SURFACE 33-36 INCHES. |
| | |
| | 26C) HIGH/ LOW DRINKING FOUNTAIN. 602.4 SPOUT HEIGHT. |
| | SPOUT OUTLETS SHALL BE 36 INCHES (915 MM) MAXIMUM ABOVE |
| | THE FINISH FLOOR OR GROUND. 602.7 DRINKING FOUNTAINS |
| | FOR STANDING PERSONS. |
| | |
| | SPOUT OUTLETS OF DRINKING FOUNTAINS FOR STANDING |
| | PERSONS SHALL BE 38 INCHES (965 MM) MINIMUM AND 43 |
| | INCHES (1090 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | |
| | 27) SHEETS S-16 THROUGH S-19 INDICATE POSITIVE AND |
| | NEGATIVE PRESSURES FOR THE COMPONENTS AND CLADDING. THE |
| | PLANS DO NOT PROVIDE THE WIND DESIGN CRITERIA NOR DOES |
| | THE PLANS INDICATE IF THE PRESSURES ARE IN VULT OR |
| | VASD. |
| | 2014 FBC-B 1603.1.4 WIND DESIGN DATA. >60 FT. TALL/ |
| | ASCE 7-10. |
| | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| | DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| | STRUCTURE: |
| | 1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST), |
| | MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED, |
| | VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 1609.3.1. |
| | 2. RISK CATEGORY. |
| | 3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| | THAN ONE WIND EXPOSURE IS UTILIZED. |
| | 4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| | 5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| | COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY |
| | DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| | RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/ |
| | M2). |
| | TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| | EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| | BUILDING. |
| | 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| | |
| | 28) PLEASE PROVIDE WHERE ON THE STRUCTURAL SHEETS THE |
| | PRESSURES FOR ROOF ZONES 1, 2 & 3. MISSING IN THE |
| | PLANS. 2014 FBC-B 1603.1.4 WIND DESIGN DATA. >60 FT. |
| | TALL/ ASCE 7-10. |
| | |
| | 29) FOR THE PRODUCT APPROVALS WITH GLAZED OPENINGS AND |
| | MULLIONS , PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, |
| | TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED, |
| | ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING |
| | SIZE THE SUBMITTED PRODUCT APPROVALS THERE ARE TO MANY |
| | VARIABLE, CIRCLE TO IDENTIFY EACH COMPONENT. COMPONENTS |
| | & CLADDING. |
| | |
| | 30) THE NOA 15-0731.06 MIAMI ROLLING DOOR SUBMITTED |
| | REPORT GOOD FOR +/- 65 SHEET S-18 SHOWS PRESSURES OF |
| | -87, VASD OR VULT NOT GIVEN ON THE SHEET. ALL PRODUCT |
| | APPROVALS ARE IN VASD. 1609.3.1 WIND SPEED CONVERSION |
| | VULT TO VASD. |
| | |
| | 31) .(2) ROOFING APPROVALS WERE SUBMITTED FOR THIS |
| | REVIEW. |
| | CARLISLE MIRASEAL FLUID APPLIED WATERPROOFING MEMBRANE |
| | NOA 13-0129.22 |
| | CARLISLE CCW-500-R HOT APPLIED LIQUID MEMBRANE NOA |
| | 12-0801.01 |
| | IN BOTH APPROVALS THERE ARE MULTIPLE SUB-SYSTEMS AND |
| | ASSOCIATED PRESSURES. IN NEITHER REPORT WAS A |
| | SUB-SYSTEM AND ASSOCIATED PRESSURES INDICATED. ALSO IN |
| | BOTH REPORTS LIMITATION # 9 IS INDICATED NO ENHAANCED |
| | FASTENING CAN OCCUR. THE PLANS DO NOT INDICATE ROOF TOP |
| | PRESSURES FOR ZONES 1,2 & 3. PLEASE PROVIDE PRESSURES |
| | IN VASD SINCE THE PRODUCT APPROVALS ARE IN VASD. 2014 |
| | FBC- B 1603.1.4 WIND DESIGN DATA. |
| | |
| | 32) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.4.1 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (F) SKYLIGHTS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 33) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 34) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| | REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| | AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |