| 2016-07-29 06:48:58 | BUILDING PLAN REVIEW |
| | W. P. B. REVISION: 16070831 |
| | W. P. B. PERMIT: 25120611 |
| | ADD: 700 S. ROSEMARY AVE. SUITE # 212 |
| | CONT: ADCON ADVANCED CONSTRUCTION |
| | TEL: 561-856-6655 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | |
| | 1ST REVIEW |
| | DATE: FRI. JULY 29/2016 |
| | ACTION: DENIED |
| | |
| | 1) REVIEWED THE 45 SHEETS PERMITED UNDER THE MAIN |
| | PERMIT SET. THERE WERE NO STRUCTURAL SHEETS WITHIN THAT |
| | SET. SHEET S-1 INDICATES THIS IS A NEW ROOF TOP A/C |
| | MECHANICAL UNIT. THERE HAS BEEN NO INFORMATION |
| | SUBMITTED FOR THE MAKE, MODEL, PHYSICAL DIMINSIONS, |
| | WEIGHT OF UNIT, NOR THE CURB PRODUCT APPROVAL NOR CLIP |
| | SYSTEM THAT THE STRUCTURAL ENGINEER INDICATES TO BE |
| | INSTALLED UNDER THE MECHANICAL UNITROOF ATTACHMENT. |
| | |
| | FOR ALL ROOF TOP EQUIPMENT, CURBS OR A/C STANDS, |
| | DETAILED ATTACHMENT TO THE ROOF FRAMING & DECK AS WELL |
| | AS FROM THE CURB OR ROOF STAND TO THE EQUIPMENT ABOVE. |
| | 2014 FBC-M- 301.15 WIND RESISTANCE. MECHANICAL |
| | EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE EXPOSED TO |
| | WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND |
| | PRESSURES DETERMINED IN ACCORDANCE WITH THE FLORIDA |
| | BUILDING CODE, BUILDING. |
| | |
| | 2) 2014 FBC-B 1604.4 ANALYSIS. LOAD EFFECTS ON |
| | STRUCTURAL MEMBERS AND THEIR CONNECTIONS SHALL BE |
| | DETERMINED BY METHODS OF STRUCTURAL ANALYSIS THAT TAKE |
| | INTO ACCOUNT EQUILIBRIUM, GENERAL STABILITY, GEOMETRIC |
| | COMPATIBILITY AND BOTH SHORT- AND LONG-TERM MATERIAL |
| | PROPERTIES. EVERY STRUCTURE SHALL BE DESIGNED TO RESIST |
| | THE OVERTURNING EFFECTS CAUSED BY THE LATERAL FORCES |
| | SPECIFIED IN THIS CHAPTER. |
| | |
| | THE BRACKET ASSEMBLY THAT HOLDS THE A/C CONDENING UNIT |
| | TO THE CURB INDICATES THAT THEY ARE TO BE EQUALLY |
| | SPACED. PLEASE PROVIDE THE LOADS TO BE RESISTED AND THE |
| | ALLOWABLE LOADS OF EACH OF THE BRACKETS, HOW MANY |
| | BRACKETS IT WILL TAKE TO RESIST THE LATERAL LOADS AND |
| | UPLIFT LOADS. |
| | |
| | 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |