Plan Review Notes
Plan Review Notes For Permit 16070802
Permit Number 16070802
Review Stop M
Sequence Number 1
Notes
Date Text
2016-07-25 15:51:13SECTION M1602 RETURN AIR
 M1602.2 PROHIBITED SOURCES.
  
 3. A ROOM OR SPACE, THE VOLUME OF WHICH IS LESS THAN 25
 PERCENT OF THE ENTIRE VOLUME SERVED BY THE SYSTEM.
 WHERE CONNECTED BY A PERMANENT OPENING HAVING AN AREA
 SIZED IN ACCORDANCE WITH ACCA MANUAL D, ADJOINING ROOMS
 OR SPACES SHALL BE CONSIDERED AS A SINGLE ROOM OR SPACE
 FOR THE PURPOSE OF DETERMINING THE VOLUME OF THE ROOMS
 OR SPACES.
  
 RETURN AIR MUST BE PERMANENTLY DUCTED FROM AHU CLOSET
 TO COMMON AREA (LIVING ROOM). CANNOT RETURN THRU A
 LOUVERED DOOR THRU A BEDROOM TO ANOTHER LOUVERED DOOR
 TO A AHU.
  
 AS PER THE SCALE LEGEND ON THE PLANS BEDROOM #1 IS 88
 SQFT (INCLUDING THE AHU CLOSET). BEDROOM #2 IS 88 SQFT.
 THE HVAC LOAD CALCULATIONS STATES 120 SQFT FOR EACH
 BEDROOM #1 AND #2..
 REVIEW YOUR LOAD CALCULATIONS AND MAKE ALL THE
 CORRECTIONS NECESSARY.
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER
 [email protected]
 561-805-6716
  