| 2016-07-25 15:51:13 | SECTION M1602 RETURN AIR | | | M1602.2 PROHIBITED SOURCES. | | | | | | 3. A ROOM OR SPACE, THE VOLUME OF WHICH IS LESS THAN 25 | | | PERCENT OF THE ENTIRE VOLUME SERVED BY THE SYSTEM. | | | WHERE CONNECTED BY A PERMANENT OPENING HAVING AN AREA | | | SIZED IN ACCORDANCE WITH ACCA MANUAL D, ADJOINING ROOMS | | | OR SPACES SHALL BE CONSIDERED AS A SINGLE ROOM OR SPACE | | | FOR THE PURPOSE OF DETERMINING THE VOLUME OF THE ROOMS | | | OR SPACES. | | | | | | RETURN AIR MUST BE PERMANENTLY DUCTED FROM AHU CLOSET | | | TO COMMON AREA (LIVING ROOM). CANNOT RETURN THRU A | | | LOUVERED DOOR THRU A BEDROOM TO ANOTHER LOUVERED DOOR | | | TO A AHU. | | | | | | AS PER THE SCALE LEGEND ON THE PLANS BEDROOM #1 IS 88 | | | SQFT (INCLUDING THE AHU CLOSET). BEDROOM #2 IS 88 SQFT. | | | THE HVAC LOAD CALCULATIONS STATES 120 SQFT FOR EACH | | | BEDROOM #1 AND #2.. | | | REVIEW YOUR LOAD CALCULATIONS AND MAKE ALL THE | | | CORRECTIONS NECESSARY. | | | | | | JORGE VALIDO | | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | | [email protected] | | | 561-805-6716 | | | |
|