| 2016-12-14 09:49:51 | ELECRTRICAL SCOPE NOW SHOWN ON CONSTRUCTION DOCUMENTS | | | INDICATING NEW LOADS BEING ADDED TO EXISTING | | | PANELBOARD, PLEASE PROVIDE A REVISED ELECTRICAL PANEL | | | SCHEDULE AND CALCULATIONS TO VERIFY ADDED LOADS TO | | | PANELBOARD. FBC 107.3.5 | | | | | | RECEPTACLE ADDED TO BE GFCI PROTECTED | | | | | | ADDRESS ZONING COMMENTS | | | | | | VAL PEREZ\ | | | *6717 |
|