| Plan Review Notes For Permit 16070797 |
| Permit Number |
16070797 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-27 14:14:23 | 1ST REVIEW MECHANICAL | | | PERMIT #16070797 | | | 7/27/16 | | | | | | 1) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE WALK-IN | | | COOLER AND REFRIGERATION EQUIPMENT WITH APPROVAL | | | SIGNATURES BY THE ARCHITECT OF RECORD. | | | | | | 2) PROVIDE A REFRIGERATION EQUIPMENT SCHEDULE ON THE | | | PLAN INCLUDING MAKES AND MODELS OF THE CONDENSER AND | | | EVAPORATOR AND COOLING CAPACITIES. | | | | | | 3) SUBMIT A FL. PRODUCT APPROVAL FOR THE CONDENSER | | | STAND WITH APPROVAL SIGNATURE BY THE ARCHITECT OF | | | RECORD. | | | | | | 4) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE | | | EVAPORATOR- SHOW PIPING RUN, DISCHARGE LOCATION, TYPE | | | AND SIZE OF PIPING. | | | | | | 5) PLEASE REVIEW THE BUILDING REVIEW COMMENTS AND | | | REVISE THE PLANS ACCORDINGLY. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|