| 2017-06-26 12:42:34 | 16070715 - BUILDING DATA FOR C.O. AND REPORTING |
| | USC-404 TYPE 105 - NEW:RES FIVE OR MORE UNITS |
| | SQUARE FEET - 641051 |
| | |
| | CONSTRUCTION TYPE: 14-1-A |
| | UNITS: 290 |
| | FLOORS: 25 |
| | BEDROOMS: 391 |
| | ROOMS: 3101 |
| | SQ FT LIVABLE: 641051 |
| | SQ FT FOOTPRINT: 38078 |
| | SQ FT ROOF: 38078 |
| | |
| | SETBACKS FRONT (USE THIS TO ENTER VERTICAL DATUM IF |
| | KNOWN): |
| | SETBACKS BACK (USE THIS TO ENTER FIRST FLOOR IF KNOWN): |
| | XX.XX |
| | SETBACKS LEFT (USE THIS TO ENTER SECOND FLOOR IF KNOWN: |
| | XX.XX |
| | OCC LOAD: 4837 |
| | PROP USE: GAR/R2/M/A |
| | SPRINKLER SYS? Y |
| | SPRK REQ'D? Y |
| | BATHRMS: 391 |
| | |
| | BLDG CODE: FL 2014 |
| | OCC CLASS: 5TH ED R-2 |
| 2017-01-17 14:43:45 | ****PROVISOS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | A. PROVISO: TCO AT EACH PHASE IS SUBJECT TO APPROVAL OF |
| | THE BUILDING OFFICIAL (OR HIS REPRESENTATIVE) AND FIRE |
| | DEPARTMENT, AND MAY INCLUDE ITEMS NOT WITHIN THE SCOPE |
| | OF THIS REVIEW. A TCO REQUEST FORM AND FEE WILL BE |
| | REQUIRED. THIS FORM IS AVAILABLE UPON REQUEST BY EMAIL. |
| | |
| | C. SEPARATE PERMITS (APPLICATION, PLANS, REVIEWS, AND |
| | FEES) REQUIRED FOR ALL ITEMS OTHER THAN MECHANICAL, |
| | ELECTRICAL, AND PLUMBING FOR THE BUILDING AS SHOWN ON |
| | THE PLANS. THIS INCLUDES SIGNS, FIRE ALARM, FIRE |
| | SPRINKLERS, LANDSCAPING. |
| | |
| | SUB PERMITS (APPLICATION, SUB PERMIT FEE) ARE REQUIRED |
| | FOR MECHANICAL, ELECTRICAL, AND PLUMBING PRIOR TO |
| | COMMENCEMENT OF WORK. |
| | |
| | A ROOFING SUB PERMIT IS REQUIRED PRIOR TO COMMENCEMENT |
| | OF ROOFING WORK. AS ROOF DOCUMENTS HAVE NOT BEEN |
| | PROVIDED, THIS IS A DEFERRED SUBMITTAL. PRODUCT |
| | APPROVALS REVIEWED BY DESIGNER OF RECORD, SELECTED |
| | ASSEMBLY, ENGINEERING IF APPLICABLE ARE TO BE SUBMITTED |
| | AS A REVISION WITH A ROOF PERMIT APPLICATION. |
| | |
| | D. COMPONENTS AND CLADDING PRODUCT APPROVALS ARE TO BE |
| | REVIEWED BY DESIGNER OF RECORD AND SUBMITTED PRIOR TO |
| | INSTALLATION. |
| | |
| | E. PROVISO, THIS STUCTURE SERVES A BUILDING WHICH HAS |
| | NOT BEEN REVIEWED BY THIS DEPARTMENT (TRAIN STATION). |
| | ACCESSIBLE ROUTE IN COMPLIANCE WITH FBC 5TH EDITION |
| | ACCESSIBILITY IS REQUIRED AND WILL BE VERIFIED IN THE |
| | FIELD. |
| | |
| | F. PROVISO, THE PROJECT MANUAL HAS NOT BEEN REVIEWED. |
| | DOOR HARDWARE TO COMPLY WITH FBC BUILDING, FBC |
| | ACCESSIBILITY. |
| | G. PROVISO, ALL DOORS AND GATES IN THE MEANS OF EGRESS |
| | FOR ASSEMBLY OCCUPANCY ARE TO INCLUDE PANIC DEVICES OR |
| | FIRE EXIT HARDWARE, FBC 1008. |
| | H. PROVISO, PRODUCT APPROVALS FOR COMPONENTS AND |
| | CLADDING HAVE NOT BEEN SUBMITTED. THEY MAY BE |
| | SUBMITTED, PRIOR TO INSTALLATION, AS A REVISION, PRIOR |
| | TO INSTALLATION. |
| | |
| | I. PROVISO, FLOORING UNDERLAYMENT IS TO COMPLY WITH FBC |
| | 1207.2, 1207.3, AND 603.1. THIS MAY BE A DEFERRED |
| | SUBMITTAL. IF DEFERRED, THE TEST REPORTS ARE TO BE |
| | SUBMITTED AS A REVISION PRIOR TO INSTALLATION. AS |
| | STRUCTURAL PLANS SHOW AN 8 INCH SLAB, PRODUCTS TESTED |
| | WITH EITHER A 6 INCH OR AN 8 INCH SLAB ARE ACCEPTABLE. |
| | |
| | 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |
| | J. FBC ACCESSIBILITY 207, MEANS OF EGRESS SHALL COMPLY |
| | WITH IBC 2000 WITH 2001 SUPPLEMENT 1003.2.13 OR IBC |
| | 2003 1007. |
| | |
| | PER ARCHITECT, BOTH BANKS OF ELEVATORS (EAST SIDE AND |
| | WEST SIDE) WILL HAVE A MINIMUM OF ONE ELEVATOR OPERABLE |
| | ON STANDBY POWER. |
| | |
| | K. STANDBY POWER, FBC 403.4.8, EMERGENCY POWER 403.4.9 |
| | REQUIRED. |
| | |
| | L. FBC ACCESSIBILITY 208.3.1(2) ADVISORY, EV SPACE WITH |
| | AN ACCESS AISLE, LOCATED ON AN ACCESSIBLE ROUTE, IS |
| | REQUIRED. A REVISION IS TO BE SUBMITTED, REVIEWED AND |
| | ISSUED PRIOR TO C.O. |
| | |