| 2016-11-27 08:22:14 | PLUMBING PLAN REVIEW - 2ND REVIEW - 11/19/16. |
| | |
| | 1) UNITS WITH STACKED WASHER/DRYERS SHALL PROVIDE |
| | ACCESS TO THE WATER SHUTOFF VALVES FOR THE APPLIANCE |
| | PER 2014 FBC-PLUMBING SEC.606.3. SHOW ON THE PLANS HOW |
| | COMPLIANCE WILL BE ACHIEVED. |
| | 2) SHT. A312 - THE DOOR ON THE AMBULATORY STALL IN THE |
| | WOMEN'S RESTROOM SHALL SWING OUT. 2014 FBC-ACCESS. |
| | SEC.604.8.2.2. THE GRAB BARS SHALL BE A MINIMUM OF 42 |
| | INCHES. FAC SEC.604.5.1. |
| | 3) SHT. A550 - IDENTIFY THE ACCESSIBLE URINAL ON THE |
| | PLAN AND SHOW THE REQUIRED 30 INCH BY 48 INCH CLEAR |
| | FLOOR SPACE FOR THE URINAL. FAC SEC.213.3.3, 605. |
| | 4) SHT. A500 - DETAIL 6 - SHOW THE INSIDE CLEAR |
| | DIMENSIONS ( LXW ) FOR THE SHOWER. WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 5) SHT.A500 - DETAIL #6 - THE DEPTH OF THE LAVATORIES |
| | SHALL NOT EXCEED 24 INCHES PER THE FHA DESIGN MANUAL. |
| | INDICATE THE MAXIMUM DEPTH ON THE PLANS. |
| | 6) SHT. A500 - DETAIL #6 - THE LAVATORY MAY OVERLAP THE |
| | CLEAR FLOOR SPACE FOR THE SHOWER A MAXIMUM OF 6 INCHES |
| | IF THE SHOWER IS A MINIMUM OF 42 INCHES IN LENGTH PER |
| | THE FHA DESIGN MANUAL.THE PORTION OF THE LAVATORY THAT |
| | OVERLAPS THE CLEAR FLOOR SPACE MUST HAVE KNEE SPACE |
| | BELOW OR A REMOVABLE VANITY CABINET. THIRTY-SIX INCHES |
| | OF THE STALL ENTRANCE MUST ALWAYS REMAIN CCLEAR FOR |
| | MANEUVERING AND TRANSFERS PER THE FHA DESIGN MANUAL. |
| | **NOTE THAT THE PERPENDICULAR APPROACH TO THE TUB SHOWN |
| | IN DETAIL 6 IS APPLICABLE DESIGN SPECIFICATION "A" |
| | BATHROOMS ONLY. |
| | 7) SHT. A501 - UNIT 01 - SHOW THE WIDTH DIMENSION |
| | BETWEEN THE KITCHEN SINK CABINET AND THE BASE CABINET |
| | ON THE OPPOSITE WALL. COMPLY WITH FHA DESIGN MANUAL. |
| | 8) SHT. A502 - UNIT 03 - INDICATE ON THE PLAN WHICH |
| | FIXTURE, THE TUB OR SHOWER, COMPLIES WITH THE FAIR |
| | HOUSING DESIGN MANUAL GUIDELINES. IF IT IS THE TUB, THE |
| | CLEAR FLOOR SPACE SHALL BE FLUSH WITH THE CONTROL WALL |
| | SURFACE PER THE GUIDELINES. THIS IS TO BE SHOWN ON ALL |
| | "B" UNITS AS THE LOCATION OF THE CLEAR FLOOR SPACE AS |
| | SHOWN DOES NOT COMPLY WITH THE GUIDELINES. |
| | 9) SHT. A 502 - CLEARLY SHOW THE DIMENSION OF THE |
| | TURNING DIAMETER CIRCLE IN THE KITCHEN AND THE |
| | DIMENSIONS OF THE OTHER CLEAR FLOOR SPACES. A TYPICAL |
| | ENLARGED FLOOR PLAN FOR EACH BATHROOM SPECIFICATION (A |
| | OR B ) & KITCHEN SHOWING THE DIMENSIONS OF THE CLEAR |
| | FLOOR SPACES AND COMPLIANCE WITH THE GUIDELINES ON THE |
| | PLANS WOULD HELP EXPEDITE THE REVIEW AT RESUBMITTAL. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | 10)THE LOCATION OF THE CLEAR FLOOR SPACE FOR THE |
| | BATHTUBS IN ALL "B" UNITS AS SHOWN DOES NOT COMPLY WITH |
| | THE GUIDELINES. THE EDGE OF THE CLEAR FLOOR SPACE SHALL |
| | BE FLUSH WITH THE CONTROL WALL SURFACE PER THE |
| | GUIDELINES. |
| | 11) SHT. A508 - THE DEPTH OF THE CHASE ADJACENT TO THE |
| | WATER CLOSET CANNOT EXCEED 24 INCHES PER THE |
| | GUIDELINES. CLEARLY SHOW THE DEPTH OF THE CHASE FROM |
| | THE FACE OF THE REAR WALL AT THE WATER CLOSET TO THE |
| | FACE OF THE CHASE. |
| | 12) SHT. A508 - CLEARLY SHOW / DEFINE THE CLEAR FLOOR |
| | SPACE AND DIMENSIONS OF THE CLEAR FLOOR SPACE FOR THE |
| | WATER CLOSET ON THE PLANS. AS SHOWN, IT DOES NOT APPEAR |
| | TO COMPLY WITH THE GUIDELINES. |
| | 13) SHT.A518 - SHOW THE LENGTH OF THE WING WALL |
| | ADJACENT TO THE WATER CLOSET IN THE "B" BATHROOM.THE |
| | WING WALL SHALL NOT EXCEED 24 INCHES PER THE |
| | GUIDELINES.SEE ALSO SHT. A519. |
| | 14) SHOW THE DIMENSION BETWEEN THE BASE CABINETS AND |
| | THE ISLAND IN THE TYPICAL PASS THROUGH KITCHENS. COMPLY |
| | WITH REQUIREMENT #7 OF THE FHA. |
| | 15) SHT. A522 & A523 - THE WING WALL ADJACENT TO THE |
| | WATER CLOSET AND THE BATHTUB ARE ENCROACHING MORE THAN |
| | 24 INCHES INTO THE CLEAR FLOOR SPACE FOR THE WATER |
| | CLOSET IN VIOLATION OF THE GUIDELINES AND REQ. #7 OF |
| | THE FHA. |
| | 16) SHT. A530 - THE DOOR TO THE LAUNDRY ROOM (T31) |
| | SHALL PROVIDE A 32 INCH CLEAR OPENING PER THE |
| | GUIDELINES. |
| | 17) SHT. A532 - THE DOOR APPEARS TO SWING INTO THE |
| | CLEAR FLOOR SPACE FOR THE WATER CLOSET, SHOWER AND |
| | LAVATORY. A 30 INCH BY 48 INCH MINIMUM CLEAR FLOOR |
| | SPACE SHALL BE PROVIDED OUTSIDE THE SWING OF THE DOOR |
| | PER THE GUIDELINES. CLEARLY SHOW THIS REQUIRED CLEAR |
| | FLOOR SPACE OUTSIDE THE SWING OF THE DOOR. |
| | 18) SHT. A535 - A 30 INCH BY 48 INCH CLEAR FLOOR SPACE |
| | SHALL BE PROVIDED AT SHOWER STALLS, PARALLEL TO THE |
| | FIXTURE AND FLUSH WITH THE CONTROL WALL. SHOW THE |
| | REQUIRED CLEAR FLOOR SPACE ON THE PLAN IN THE BATHROOM |
| | BY THE LAUNDRY. THE OTHER BATHROOM DOES NOT COMPLY WITH |
| | DESIGN SPECIFICATION "A" BECAUSE THE CLEAR FLOOR SPACE |
| | IS NOT PARALLEL TO THE SHOWER AND FLUSH WITH THE |
| | CONTROL WALL DUE TO THE DOUBLE LAVATORIES. THERE IS NO |
| | ALLOWANCE FOR A CLEAR FLOOR SPACE PERPENDICULAR TO THE |
| | SHOWER, ONLY FOR A BATHTUB IN THE "A" SPECIFICATION |
| | DESIGN. SHOW THE LENGTH OF THE WING WALL ADJACENT TO |
| | THE WATER CLOSET IN THIS BATHROOM. |
| | 19) SHT. A535 - THE DOORS FOR THE LAUNDRY ROOM (T30A) |
| | SHALL PROVIDE A 32 INCH CLEAR OPENING PER THE |
| | GUIDELINES. |
| | 20) SHT.A535 -THE POWDER ROOM DOOR SHALL HAVE A 32 INCH |
| | CLEAR OPENING AND COMPLY WITH THE GUIDELINES FOR |
| | SWITCHES,OUTLETS AND CONTROLS. |
| | 21) SHT. A552 - THE BREAK ROOM SINK IN THE LEASING |
| | OFFICE SHALL COMPLY WITH 2014 FBC ACCESS. SECS. 212 & |
| | 606. |
| | 22) SHTS. A553 THROUGH A555 - THERE IS A BOX ON ALL |
| | THREE SHEETS FOR EMERGENCY OVERFLOW DRAINAGE |
| | CALCULATIONS BUT THE CALCULATIONS HAVE NOT BEEN DONE |
| | AND THE INFORMATION IS MISSING. SUBMIT ALL REQUIRED |
| | INFORMATION IN THESE AREAS FOR THE EMERGENCY OVERFLOW |
| | DRAINAGE PROVISIONS.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 23) SHTS. A201 & A601 REFER TO A BATHROOM ON THE FIRST |
| | LEVEL NEAR THE WEST RESSIDENTIAL LOBBY / WEST ELEVATORS |
| | BUT IT IS NOT REFERENCED ON SHT. A301. THE UNDERGROUND |
| | SANITARY FOR THIS BATHROOM IS NOT SHOWN ON SHT. 200A. |
| | CLARIFY. |
| | 24) SHT. A1206 - DETAILS #1 & #2 - ARE THESE DETAILS |
| | FOR THE WATER CLOSETS IN THE COMMON AREA RESTROOMS / |
| | TOILET ROOMS? IF IN THE COMMON AREAS THE GRAB BARS |
| | SHALL BE MEASURED FROM THE FINISH FLOOR TO THE TOP OF |
| | THE GRIPPING SURFACE PER 2014 FBC-ACCESS. 609.4. |
| | CLARIFY. THE GOVERNING ACCESSIBILITY CODE IN FLORIDA IS |
| | THE 2014 FBC-ACCESSIBILITY, NOT THE ADA. THE FBC IS AN |
| | ADA COMPLIANT CODE AND HAS BEEN APPROVED BY THE DOJ. |
| | 25) SHT. A1206 - DETAIL #5 - THE LENGTH OF THE BACKING |
| | AT THE TUB SHALL BE 48 INCHES MINIMUM PER THE FHA |
| | DESIGN MANUAL. |
| | 26) SHT. A1207 - DETAILS #2 &L #7 - SHOW THE DIMENSIONS |
| | (LXW) OF THE SCUPPERS. |
| | 27) THE SANITARY RISERS SHOW A SOVENT DESIGN SYSTEM BUT |
| | IT IS MY UNDERSTANDING FROM A MEETING THAT A PROVENT |
| | SYSTEM IS TO BE INSTALLED.IF A PROVENT DESIGN IS TO BE |
| | UTILIZED, SUBMIT ALL NEW RISER DIAGRAMS DESIGNED USING |
| | THE PROVENT SYSTEM AND THE DESIGN SPECIFICATIONS AND |
| | MANUAL.IF THE DESIGN OF THE SANITARY SYSTEM IS INDEED A |
| | SOVENT SYSTEM, INDICATE THE SYSTEM MANUFACTURER AND THE |
| | DESIGN STANDARD THAT WAS USED IN THE DESIGN OF THE |
| | SYSTEM.A COMPREHENSIVE REVIEW WAS NOT DONE ON THE |
| | SOVENT SYTEM DUE TO THE QUESTION OF THE TYPE OF SYSTEM |
| | BEING USED. WPB AMEND. TO FBC SEC. 107.2.1 & |
| | 107.3.5.1.3. |
| | 28) SHT. M706 SHOWS THE 2 INCH CONDENSATE LINE DRAINING |
| | INTO AN 1 1/4 INCH AND AN 1 1/2 CONDENSATE LINE. THE |
| | PIPE SIZE CANNOT BE REDUCED IN THE DIRECTION OF FLOW. |
| | 2014 FPC SEC.314.2.2. |
| | 29) SHOW COMPLIANCE WITH 2014 FPC SEC.314.2.3 FOR THE |
| | REQUIREMENTS FOR AUXILARY AND SECONDARY DRAIN SYSTEMS |
| | FOR THE CONDENSATE SYSTEMS. |
| | 30) IDENTIFY THE FLOOR LEVELS ON THE CONDENSATE RISERS. |
| | WPB AMEND. TO FBC SEC. 107.2.1. |
| | 31) SHT.P200A - THE 3 INCH SUMP FOR THE ELEVATOR - |
| | WHERE IS THE PIPING RISER? PLANS REFER TO A "DETAIL" |
| | FOR FURTHER INFO. IDENTIFY THE DRAWING SHEET NUMBER |
| | WHERE THIS DETAIL CAN BE FOUND. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 32) IDENTIFY THE FLOOR LEVELS ON ALL RISERS.2ND |
| | REQUEST.THIS WAS PARTIALLY DONE. WPB AMEND. TO FBC |
| | SEC.107.2.1 |
| | 33) THE SPECIFICATIONS FOR THE BACKWATER VALVE ON THE |
| | CONDENSATE DRAINS HAVE NOT BEEN SUBMITTED AS PREVIOUSLY |
| | REQUESTED. THIS CAN BE A DEFERRED SUBMITTAL. THE |
| | SPECIFICATIONS CAN BE SUBMITTED FOR THE REVIEW AT THE |
| | TIME OF INSTALLATION. |
| | 34) INDICATE ON THE PLANS WHAT STANDARD / CODE WAS USED |
| | IN SIZING THE OIL INTERCEPTOR. SUBMIT DETAILS/ COPIES |
| | OF THE STANDARD USED FOR THE SIZING. WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 35) SHTS. 203A, 204A - SUBMIT A DETAIL OF THE SURGE |
| | TANK AND ASSOCIATED PIPING THAT IS LOCATED ON THE |
| | SECOND PARKING LEVEL. THE TANK IS NOT SHOWN ON THE |
| | ARCITECTURAL OR LIFE SAFETY PLANS. CLARIFY.ALSO, |
| | EXPLAIN THE OPERATIONS OF THE SURGE TANK. SHT. 204A HAS |
| | A NOTE THAT READS"SET VALVE FOR SLOW DRAIN OFF OF SURGE |
| | TANK. 24 HOUR MAX." WHERE DOES THIS TANK DRAIN? .WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 36) A COMPRHENSIVE REVIEW COULD NOT BE PERFORMED ON THE |
| | SANITARY AND WATER RISERS. THE METHOD USED TO TAG THE |
| | RISERS IS EXTRERMELY CONFUSING. I CANNOT FIGURE OUT |
| | WHAT RISER GOES WHERE OR WHAT METHODOLOGY IS BEING |
| | USED. PLEASE CONTACT THIS PLAN REVIEWER TO SET UP A |
| | MEETING TO REVIEW AND DISCUSS THE SANITARY AND WATER |
| | RISER TAGGING SYSTEM. A RISER TAG LEGEND THAT CLEARLY |
| | CORRELATES WITH EACH PLUMBING PLAN SHEET AND RISER |
| | SHALL BE SUBMITTED. |
| | 37) PLEASE EXPLAIN THE MATCH LINES OF ZONE #1 & ZONE |
| | #2. |
| | 38) CLEANOUTS ARE REQUIRED IN THE STORM DRAINAGE SYSTEM |
| | IN ACCORDANCE WITH FPC SEC.1101.8. |
| | 39) FULL -OPEN VALVES SHALL BE INSTALLED ON THE BASE OF |
| | OF EVERY WATER RISER PIPE IN ACCORDANCE WITH THE 2014 |
| | FPC SEC.606.1 (4). |
| | 40) A FULL-OPEN VALVE SHALL BE INSTALLED ON THE |
| | DISCHARGE SIDE OF EVERY WATER METER. FPC SEC. 606.1. |
| | 41) SUBMIT A COMPLETE UNDERGROUND COLLECTION RISER |
| | DIAGRAM FOR THE SANITARY SYSTEM SHOWING THE INDIVIDUAL |
| | RISER BRANCHES WITH TAG NUMBERS THAT CLEARLY REFLECT |
| | THE SCOPE OF WORK. WPB AMEND. TO FBC SEC. 107.2.1. |
| | 42) ALL FLOOR DRAINS SHALL BE EQUIPPED WITH TRAP |
| | PRIMERS. 2014 FPC SEC.1002.4. |
| | 43) SHT. P301 - NOTE #1 REFERS TO A WATER LINE YET THE |
| | NOTE IS ALSO LOCATED ON THE 2 1/2 INCH GAS LINE ON THE |
| | PLAN. CLARIFY. |
| | 44) THE PLANS NOTE THAT THE PIPE SLOPE FOR PIPE SIZES 8 |
| | INCH OR LARGER SHALL BE 1/16 OF AN INCH.THE MINIMUM |
| | SLOPE FOR STORM DRAINAGE PIPING PER FPC TABLE 1106.3 IS |
| | 1/8 OF AN INCH. CLARIFY. |
| | 45) POINT OF USE WATER HEATERS SUPPLYING TEMPERED WATER |
| | SHALL BE EQUIPPED WITH A WATER TEMPERATURE LIMITING |
| | DEVICE THAT COMPLIES WITH ASSE 1070 THAT LIMITS THE |
| | TEMPERED WATER TO A MAXIMUM TEMPERATURE OF 110 DEGREES. |
| | FPC SEC. 607.1.2. |
| | 46) SHT. P311B - NOTE #2 REFERS TO A 6 INCH WATER LINE |
| | IN A CHASE BUT THERE IS NO CHASE AND THERE IS NO |
| | CONTINUATION OF THE WATER LINE. CLARIFY. |
| | 47) SHT. 314B - NOTE ON PLAN IN MECH. ROOM 12.507 CALLS |
| | OUT CHASE FOR WATER RISER BUT RISER APPEARS TO BE IN |
| | DOORWAY. CLARIFY. |
| | 48) THE DE-AERATOR FITTINGS SHALL BE LOCATED AT THE |
| | BASE OF THE VERTICAL STACK BEFORE IT ENTERS THE |
| | HORIZONTAL BUILDING DRAIN. THERE ARE SOME THAT ARE |
| | LOCATED IN THE STACKS. |
| | 49) SUBMIT EXPANDED SANITARY RISERS FOR REVIEW. THE |
| | RISERS ARE DIFFICULT TO REVIEW. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |