| 2016-11-27 08:14:02 | 1) SHT. P717 SHOWS( 2 )-2 1/2 INCH LINES TO THE RETAIL |
| | SPACE. SHOW HOW THESE LINES CONNECT TO THE GAS MAIN. |
| | WPB AMEND. TO FBC SEC. 107.3.5.1.5. FUTURE LINES SHALL |
| | BE EQUIPPED WITH REGULATORS AND THE OUTLET FROM THE |
| | REGULATOR SHALL HAVE A NIPPLE, VALVE AND CAP INSTALLED. |
| | THE REGULATOR VENT OUTLET SHALL BE CAPPEDOR PLUGGED |
| | UNTIL PUT INTO USE. |
| | 2) SHOW THE APPROXIMATE DISTANCE OF THE RUN OF THE PIPE |
| | TO THE RETAIL SPACE FROM THE METER.WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 3) SHT.P718 REFERS TO A DETAIL FOR THE SHUTOFF VALVE |
| | FOR THE APPLIANCE AT THE AMENITIES AND ALSO FOR THE |
| | SHUTOFF VALVE FOR THE POOL EQUIPMENT. SPECIFIY THE |
| | SHEET WHERE THIS DETAIL CAN BE FOUND. I DID NOT FIND IT |
| | ON ANY OF THE DETAIL SHEETS. |
| | 4) PLACE THE TOTAL BTU LOAD FOR EACH SYSTEM IN THE |
| | APPROPRIATE SYSTEM SIZING BOX ( SYSTEM #1, #2 #3 ). IT |
| | IS TIME CONSUMNING ADDDING IT UP ON THE RISERS AND THIS |
| | WILL AID IN THE RE-EVIEW TIME FOR THE GAS.WPB AMEND. TO |
| | FBC SEC. 107.2.1. |
| | 5) REFER TO THE SHEET NUMBER FOR THE CONTINUATION OF |
| | THE GAS RISERS, NOT JUST THE LETTER.WPB AMEND. TO FBC |
| | SEC. 107.2.1. |
| | 6) SHOW THE CONNECTION POINT OF THE RISER Q-Q TO THE |
| | MAIN GAS SYSTEM AND REFERENCE THE SHEET NUMBER.WPB |
| | AMEND. TO FBC SEC. 107.2.1. |
| | 7) SHT.P719 - THE SIZING SYSTEM BOXES REFER TO THE 2009 |
| | IFC. THE FUEL GAS CODE IN EFFECT IS THE 2014 FBC-FUEL |
| | GAS. |
| | 8) SHT. P719 - SIZING SYSTEM #1 BOX - THE GAS TABLE |
| | REFERENCED, 402.3 (3) IS FOR LESS THAN 2 PSI IN THE FBC |
| | FUEL GAS BUT THE TEXT IN THE BOX STATES THE SYSTEM IS A |
| | 2 PSI SYSTEM WITH A PRESSURE DROP OF 1.0 PSI. CLARIFY. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |