| 2016-09-08 11:15:53 | 1ST REVIEW |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER LL |
| | CITY OF WEST PALM BEACH |
| | DEVELOPMENT SERVICES |
| | BUILDING DIVISION |
| | 561-805-6711 |
| | [email protected] |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE INDICATE ON THE PLAN WHICH DESIGN |
| | SPECIFICATION FOR THE BATHROOMS YOUR USING FOR THE FHA. |
| | PER WPB AMEND. TO FBC 107.2.1 |
| | |
| | 2.SHT. A550 AMBULATORY TOILET STALLS IN WOMENS AMENITY |
| | BATHROOMS SHALL BE MIN 35IN AND 37IN MAX WIDE. PER FBC |
| | ACC 604.8.2.1 |
| | |
| | 3. IF AMENITY BATHROOMS SERVE THE ASSEMBLY OCCUPANCY |
| | THEY SHALL COMPLY WITH FBC PL 403.1.3 POTTY PARITY. |
| | IN ASSEMBLY OCCUPANCIES, RESTROOMS WHICH ARE OPEN TO |
| | THE PUBLIC MUST HAVE A RATIO OF 3:2 WATER CLOSETS |
| | PROVIDED FOR WOMEN AS THE COMBINED TOTAL OF WATER |
| | CLOSETS AND URINALS PROVIDED FOR MEN, UNLESS THESE ARE |
| | TWO OR FEWER SUCH FIXTURES FOR MEN, IN ACCORDANCE WITH |
| | SECTION 553.86, FLORIDA STATUTES. |
| | |
| | 4. DOORS IN BATHROOM S 0-201,1206,1207 SHALL COMPLY |
| | WITH FBC ACC 603.2.3 DOOR SWING. |
| | DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR |
| | CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE |
| | PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE. |
| | |
| | 5. SHT A1206 DETAIL #3 REINFORCING FOR GRAB BARS IN THE |
| | SHOWERS SHALL BE MAX 32IN TO THE BOTTOM O.F.F. AND A |
| | MIN 38IN TO THE TOP. PER FHA CH.6 PG.6.12 |
| | |
| | 6. SHT.A1206 REINFORCEMENT FOR GRAB BARS AT TOILET |
| | SHALL BE MAX 32IN TO THE BOTTOM O.F.F. AND A MIN 38IN |
| | TO THE TOP. PER FHA CH.6 PG.6.4-5 |
| | |
| | 7. SHT.P200A LABEL SANITARY PIPING FOR BATHROOM IN |
| | LOBBY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 8. IN THE LEASING OFFICE AND LOBBY SEPARATE FACILITIES |
| | ARE REQUIRED FOR EACH SEX. FBC ACC. 403.2 SEPARATE |
| | FACILITIES. |
| | WHERE PLUMBING FIXTURES ARE REQUIRED, SEPARATE |
| | FACILITIES SHALL BE PROVIDED FOR EACH SEX. |
| | |
| | 9. PLEASE LABEL FLOOR LEVELS ON SANITARY RISER |
| | DIAGRAMS. PER WPB AMEND. TO FBC 107.2.1 |
| | |
| | 10. PROVIDE DETAIL FOR WASH-RING IN TRASH CHUTE. PER |
| | WPB AMEND. TO FBC 107.2.1 |
| | |
| | 11. PROVIDE TAG NUMBERS ON EACH STACK SHTS. P201A THRU |
| | P219B. PER WPB AMEND. TO FBC 107.2.1 |
| | |
| | 12. PLEASE INDICATE ON THE PLAN THE SLOPE OF ALL |
| | HORIZONTAL STORM AND SANITARY PIPING. PER WPB AMEND. TO |
| | FBC 107.2.1 |
| | |
| | 13. PROVIDE MANUFACTURE SPECS FOR BACKWATER VALVE ON |
| | CONDENSATE DRAINS. PER WPB AMEND. TO FBC 107.2.1 |
| | |
| | 14. PROVIDE DETAIL FOR EMERGENCY OVER FLOW SCUPPER. PER |
| | WPB AMEND. TO FBC 107.2.1 |
| | |
| | 15. PLEASE PROVIDE SIZING CALCULATIONS FOR THE OIL SAND |
| | SEPARATOR. PER WPB AMEND. TO FBC 107.2.1 |
| | |
| | 16. PLEASE PROVIDE MANUFACTURE SPECS FOR OIL MINDER |
| | ELEVATOR SUMP PUMP, DOMESTIC WATER PUMP, KITCHEN GREASE |
| | HEAT TRACE SYSTEM. PER WPB AMEND. TO FBC 107.2.1 |
| | |
| | 17.TRAP PRIMERS ARE REQUIRED ON FLOOR DRAINS AND THE |
| | STAND PIPES FOR ELEVATOR SUMP PUMP AND FIRE SPRINKLER |
| | BLOW DOWN. PER FBC PL 1002.4 TRAP SEALS. |
| | EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS |
| | THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102 |
| | MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO |
| | ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO |
| | LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE |
| | INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE |
| | TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A |
| | TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR |
| | ASSE 1044. |
| | |
| | 18. PLEASE PROVIDE RISER DIAGRAMS FOR CONDENSATE DRAINS |
| | AND WATER HEATER PAN DRAINS. PER WPB AMEND. TO FBC |
| | 107.3.5.1.3(13) |
| | |
| | 19. ALL THE PLUMBING SHEETS ARE MARKED NOT FOR |
| | CONSTRUCTION THEY CAN NOT BE APPROVED THIS WAY PLEASE |
| | CLARIFY. PER WPB AMEND. TO FBC 107.2.1 |
| | |
| | |
| | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND |
| | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON |
| | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. |
| | |
| | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES |
| | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE |
| | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |