| 2016-10-05 09:22:22 | PLEASE RESPOND TO COMMENTS IN WRITING. |
| | |
| | BACKFLOWS MUST BE AS CLOSE TO CITY OF WPB SOURCE AS |
| | POSSIBLE. |
| | |
| | IF BACKFLOWS ARE SHOWN IN THE CLOSEST LOCATION AS |
| | POSSIBLE, REPLY IN WRITING TO THIS COMMENT SO THAT A |
| | MEETING CAN BE ARRANGED WITH UTILITIES CUSTOMER SERVICE |
| | TO GET A VARIANCE IF THERE IS LEGITIMATE HARDSHIP. AN |
| | ENLARGE VIEW OF THE WATER METER AND BACLFLOWS LOCATIONS |
| | MAY BE ADEQUATE TO BETTER DESCRIBE THE CLEARANCES |
| | AROUND THESE CONSTRICTED AREAS. ENOUGH CLEARANCE SHALL |
| | BE (18") AROUND THE DEVICES TO ALLOW PROPER MAINTENANCE |
| | SPACE. BACKFLOWS JUST INSIDE BUILDING OR HARD SURFACE |
| | SHALL HAVE A FLOOR DRAIN TO AVOID FLOODING WHEN |
| | BACKFLOWS ARE NOT WORKING PROPERLY OR WHEN ROUTINE |
| | MAINTENANCE IS REQUIRED. |
| | |
| | SUBMIT SHOP DRAWINGS FOR DCDA AND RPPA FOR DOMESTIC, |
| | FIRE, IRRGIGATION. ETC./IMPORTANT MESSAGE: AS OF |
| | DECEMBER 20, 2015 THE CITY OF WEST PALM BEACH. |
| | CROSS-CONNECTION CONTROL MANUAL HAS BEEN REVISED MAKING |
| | KNOWN THAT "ALL BACKFLOW DEVICES MUST BE LEAD FREE." |
| | FOR MORE INFORMATION REFER TO THE LINK BELOW: HTTP://WP |
| | B.ORG/DEPARTMENTS/PUBLIC-UTILITIES/FORMS-PUBLICATIONS/B |
| | ACKFLOW-CROSS-CONNECTION-CONTROL-MANUAL |
| | |
| | MANUEL JULIAN GONZALEZ |
| | ENGINEERING PROJECT COORDINATOR |
| | PUBLIC WORKS DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1085 |
| | FAX: (561) 494-1116 |
| | EMAIL: [email protected] |
| | HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS |
| | /FORMS,-PERMITS-APPLICATIONS |
| | |
| | |