| 2016-10-11 18:51:08 | REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 & |
| | NFPA 70 2011 (NEC) |
| | |
| | BELOW ARE THE ELECTRICAL COMMENTS FOR THE FAILED PLAN |
| | REVIEW: |
| | |
| | TYPICAL COMMENT: CITY OF WEST PALM BEACH AMENDMENTS TO |
| | THE FBC-B SECTION 107.2.1.4 REQUIRES THAT BUILDING |
| | PLANS BE DRAWN TO A MINIMUM 1/8? SCALE. THE SUBMITTED |
| | DRAWINGS ARE DRAWN TO A 3/32? SCALE MAKING THEM A BIT |
| | SMALLER THAN THE REQUIRED. PLEASE CORRECT ACCORDINGLY. |
| | |
| | SHEET E000 |
| | 1. CLARIFY THE FRONT OF PANEL WHEN RECESSED IN THE |
| | DISTRIBUTION EQUIPMENT BOX |
| | 2. IS IT YOUR INTENT TO SHARE THESE SYMBOLS IN THE |
| | LIGHTING LEGEND |
| | 3. IS IT YOUR INTENT TO SHARE THIS SYMBOL IN THE POWER |
| | CONNECTIONS BOX |
| | 4. FIRE ALARM WORK SHALL BE UNDER SEPARATE PERMIT & |
| | SUBMITTAL |
| | SHEET E001 |
| | 5. PLEASE TRY TO BE CONSISTENT WITH THE ABBREVIATIONS |
| | THROUGHOUT THE SET. I SEE MULTIPLE SYMBOLS W/THE SAME |
| | DESIGNATION. SYMBOLS NOT ALIGNED TO DESCRIPTION. |
| | 6. IS IT YOUR INTENT TO SHARE THIS SYMBOL IN THE |
| | DEMOLITION NOTES BOX |
| | SHEET E201A |
| | 7. NEC 422.31: EWH-4 REQUIRES A DISCONNECT |
| | 8. NEC 210.8(B): RECEPTACLE OUTLETS IN GARAGES OR |
| | INDOOR WET LOCATIONS SHALL BE GFI PROTECTED |
| | 9. SEE NEC 430 FOR THE REQUIRED DISCONNECTS AND |
| | ADDITIONAL CONTROLS AND SAFETY DEVICES REQUIRED, |
| | TYPICAL TO ALL MOTOR LOADS |
| | SHEET E202 |
| | 10. HIGHLY UNLIKELY THAT THERE WILL ONLY BE 2 OUTLETS |
| | IN THE MEZZANINE |
| | SHEET E203 |
| | 11. THE FOLLOWING MOTORS AND APPLIANCES REQUIRED |
| | DISCONNECTS AS MENTIONED ABOVE AHU2-1, FCU2-2, EWH-8, |
| | FCU2-1.1, FCU2-3, FCU2-1.2, EWH-4 |
| | SHEET E204 |
| | 12. SAME AS ABOVE FOR FCU3-1 |
| | SHEET E208 |
| | 13. SAME AS ABOVE FOR FCU7-1 |
| | SHEET E210 |
| | 14. SAME AS ABOVE FOR FCU9-3, SF9-3, AS WELL AS EVERY |
| | MOTOR & HVAC EQUIPMENT ON ROOF |
| | SHEET E211 |
| | 15. SAME AS ABOVE FOR FCU10-1 |
| | SHEET E212 |
| | 16. SAME AS ABOVE FOR UNITS SF11-1, FCU12.5-1, FCU11-2 |
| | & CU12.5-1 |
| | SHEET E213 |
| | 17. SAME AS ABOVE FOR AHU12-6, EF12-1 |
| | SHEET E214 |
| | 18. SAME AS ABOVE FOR ALL MOTORS AND ELECTRIC WATER |
| | HEATER IN ROOM 12.508 |
| | SHEET E301A |
| | 19. RETAIL R02 ? LIGHTING ARRANGEMENT AS DESCRIBED DOES |
| | NOT MEET THE DAYLIGHT ZONE CONTROL REQUIREMENTS OF THE |
| | FBC-E405.2.2.3 |
| | 20. FBC-B 1011.1 EXITS AND EXIT ACCESS SHALL BE MARKED |
| | BY AN APPROVED EXIT SIGN READILY VISIBLE FROM ANY |
| | DIRECTION OF EGRESS TRAVEL. THE PATH OF EGRESS SHALL BE |
| | CLEARLY MARKED WHEN NOT READILY VISIBLE. THERE SHALL |
| | NOT BE MORE 100? BETWEEN EXIT SIGN ALONG THE PATH OF |
| | EGRESS. |
| | 21. RETAIL R01 ? LIGHTING ARRANGEMENT AS DESCRIBED DOES |
| | NOT MEET THE DAYLIGHT ZONE CONTROL REQUIREMENTS OF THE |
| | FBC-E405.2.2.3 |
| | 22. RETAIL R03 ? LIGHTING ARRANGEMENT AS DESCRIBED DOES |
| | NOT MEET THE DAYLIGHT ZONE CONTROL REQUIREMENTS OF THE |
| | FBC-E405.2.2.3 |
| | 23. DUE TO THE LACK OF ROOM LABELS, ADDITIONAL LIGHTING |
| | CONTROLS MAY BE REQUIRED |
| | SHEET E303, E304, E305, E306, E307, E308, E309, E310, |
| | E311, E312 |
| | 24. THIS SHEET DOES NOT CLEARLY INDICATE THE LOCATION |
| | OF EGRESS DOORS OR UP/DOWN RAMP, THEREFORE PROPER EXIT |
| | LIGHT LOCATION IS NOT IDENTIFIABLE |
| | SHEET E314 |
| | 25. THIS AREA IS NOT IDENTIFIED ON THE PLANS, THEREFORE |
| | EXIT LIGHTING AND LIGHTING CONTROL REQUIREMENTS CAN?T |
| | BE PROPERLY DETERMINED |
| | SHEET E318 |
| | 26. EXIT LIGHT REQUIRED BY ROOF EXIT DOORWAY |
| | SHEET E501 |
| | 27. NEC 210.52(C)(4): (UNITS 6, 2, 04,) AN OUTLET IS |
| | REQUIRED ON EITHER SIDE OF THIS SINK |
| | 28. NEC 210.70: (UNIT 04) THE AREA LEADING TO THE |
| | BEDROOM IS MISSING ILLUMINATION |
| | SHEET E503 |
| | 29. NEC 210.52(A)(2): WALL SPACE. ANY WALL SPACE 2 FT. |
| | OR MORE IN WIDTH SHALL REQUIRE A RECEPTACLE. SEE LIVING |
| | ROOM OF UNIT 20 |
| | 30. NEC 210.52(C)(4): (UNITS 20 ) AN OUTLET IS REQUIRED |
| | ON EITHER SIDE OF THIS SINK |
| | 31. NEC 110.26(D): ILLUMINATION SHALL BE PROVIDED FOR |
| | ALL WORKING SPACES ABOUT SERVICE EQUIPMENT, |
| | SWITCHBOARDS, AND PANELBOARDS. THIS LIGHT SHALL NOT BE |
| | CONTROLLED BY AUTOMATIC MEANS ONLY. CHECK THE SMC |
| | CLOSET OF UNIT 20 |
| | 32. NEC 210.52(C)(4): (UNITS 18) AN OUTLET IS REQUIRED |
| | ON EITHER SIDE OF THIS SINK |
| | 33. NEC 210.52 (A)(1): RECEPTACLES SHALL BE INSTALLED |
| | SUCH THAT NO POINT MEASURED HORIZONTALLY ALONG THE |
| | FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 FT. FROM A |
| | RECEPTACLE OUTLET. THIS INCLUDES THE DISTANCE FROM THE |
| | EDGE OF THE WALL. A FLOOR BOX IS REQUIRED ALONG THE |
| | WALL WITH ALL THE WINDOWS IN THE LIVING ROOM OF UNIT 18 |
| | 34. NEC 210.52(H): IN DWELLING UNITS, HALLWAYS OF 10 FT |
| | OR MORE IN LENGTH SHALL HAVE AT LEAST ONE RECEPTACLE |
| | OUTLET. SEE THE MASTER BEDROOM CORRIDOR OF UNIT 18 |
| | 35. NEC 210.52(A)(2): WALL SPACE. ANY WALL SPACE 2 FT. |
| | OR MORE IN WIDTH SHALL REQUIRE A RECEPTACLE. SEE WALL |
| | BEHIND MASTER BEDROOM SINK OF UNIT 18 |
| | 36. NEC 110.26(D): ILLUMINATION SHALL BE PROVIDED FOR |
| | ALL WORKING SPACES ABOUT SERVICE EQUIPMENT, |
| | SWITCHBOARDS, AND PANELBOARDS. THIS LIGHT SHALL NOT BE |
| | CONTROLLED BY AUTOMATIC MEANS ONLY. SEE AREA IN FRONT |
| | OF ELECTRICAL PANEL OF UNIT 18. |
| | SHEET E504, UNIT L1 |
| | 37. FBC-RE3901.4: IF THE AREA ADJACENT TO THE |
| | REFRIGERATOR IS COUNTER SPACE, AN OUTLET IS REQUIRED. |
| | 38. FBC-ER3901.4.1: KITCHEN RECEPTACLE REQUIRED |
| | 39. ARE YOU SURE THAT YOU WANT THE SWITCH FOR THE |
| | DISPOSAL THAT FAR AWAY FROM THE SINK |
| | 40. FBC-RE3901.2.1: A RECEPTACLE IS REQUIRED NO MORE |
| | THAN 6? FROM THE WALL EDGE OF THE KITCHEN TO THE LR. |
| | 41. FBC-RE3901.2.1: THE LINEAR WALL SPACE BETWEEN THESE |
| | TWO OUTLETS EXCEEDS THE 12? RULE OF THE CODE. THIS |
| | APPLIES TO THE BEDROOM OUTLETS. |
| | SHEET E504, UNIT L2 |
| | 42. SEE UNIT L1 KITCHEN COMMENTS. |
| | SHEET E504, UNIT L3 |
| | 43. SEE UNIT L1 KITCHEN COMMENTS. |
| | 44. SEE UNIT L1 COMMENT 41. |
| | 45. SEE COMMENTS 40 & 41 FOR UNIT L1. |
| | |
| | SHEET E505, UNIT L4 |
| | 46. SEE COMMENT 37 ABOVE FOR UNIT L1. |
| | 47. SEE COMMENTS 41 ABOVE FOR UNIT L1. LOWER BEDROOM. |
| | 48. PLEASE ABIDE BY THE 6 - 12 RECEPTACLE SPACING RULE |
| | AND RELOCATE YOUR RECEPTACLES ACCORDINGLY. (UPSTAIRS |
| | SITTING AREA). |
| | 49. SEE COMMENT 41 ABOVE. UPPER BEDROOM. |
| | SHEET E505, UNIT L5 |
| | 50. SEE COMMENT 39 ABOVE. KITCHEN DISPOSAL |
| | 51. SEE COMMENT 41 ABOVE FOR UNIT L1. LOWER BEDROOM. |
| | 52. SEE COMMENT 41 ABOVE FOR UNIT L1. UPPER BEDROOM. |
| | 53. SEE COMMENT 48 ABOVE FOR UNIT L4. UPPER SITTING |
| | AREA. |
| | SHEET E506, UNIT L6 |
| | 54. FBC-RE3901.2.1SPACING. RECEPTACLES SHALL BE |
| | INSTALLED SUCH THAT NO POINT MEASURED HORIZONTALLY |
| | ALONG THE FLOOR LINE IN ANY WALL SPACE IS MORE THAN 6 |
| | FT. FROM A RECEPTACLE OUTLET. THIS INCLUDES THE |
| | DISTANCE FROM THE EDGE OF THE WALL. LOWER BEDROOM |
| | 55. FBC-RE3903.4 STORAGE OR EQUIPMENT SPACES. AT LEAST |
| | ONE LIGHTING OUTLET CONTAINING A SWITCH OR CONTROLLED |
| | BY A WALL SWITCH SHALL BE INSTALLED WHERE THESE SPACES |
| | ARE USED FOR STORAGE OR CONTAIN EQUIPMENT REQUIRING |
| | SERVICING. THE LIGHTING OUTLET SHALL BE PROVIDED AT OR |
| | NEAR THE EQUIPMENT REQUIRING SERVICING. EWH CLOSET |
| | 56. CAREFUL NOT TO PLACE THIS SWITCH BEHIND THE DOOR TO |
| | THIS BEDROOM. DOOR TO ROOM NOT DRAWN PLAN. UPPER |
| | BEDROOM. |
| | 57. FBC-RE3901.2.1: RELOCATE THIS OUTLET TO MEET CODE |
| | SPACING REQUIREMENTS. UPPER SITTING AREA. |
| | 58. SEE NOTE 54 ABOVE. UPPER BEDROOM. |
| | SHEET E506, UNIT L7 |
| | 59. SEE COMMENT 55 ABOVE. EWH CLOSET |
| | 60. FBC-ER3901.4.4/NEC 210.52(C)(4) COUNTERTOP SPACES |
| | SEPARATED BY RANGETOPS, REFRIGERATORS, OR SINKS SHALL |
| | BE CONSIDERED AS SEPARATE COUNTERTOP SPACES IN APPLYING |
| | THE REQUIREMENTS OF 210.52(C)(1). THEREFORE AN OUTLET |
| | IS MISSING FROM THIS END OF THE PENINSULA. |
| | 61. SEE COMMENT 57 ABOVE. |
| | |
| | 62. SHEET E506, UNIT L8 |
| | 63. SEE COMMENT 55 ABOVE. |
| | 64. SEE COMMENT 57 ABOVE. BEDROOM & LIVING ROOM |
| | SHEET E506, UNIT L9 |
| | 65. SEE COMMENT 55 ABOVE |
| | 66. SEE COMMENT 57 ABOVE. BEDROOM & LIVING ROOM |
| | SHEET E507, PENTHOUSE |
| | 67. THIS IS AN INTERIOR BATHROOM AND IT REQUIRES AN |
| | EXHAUST FAN. IF A NON-CONTINUOUS UNIT IS USED, IT SHALL |
| | BE CONTROLLED WITH THE LIGHT SWITCH. HALF BATH |
| | 68. ADJUST OUTLETS ALONG THESE WALLS TO MEET CODE |
| | COMPLIANCE. CURTAIN WALL LIVING ROOM & DINING ROOM. |
| | 69. IN THE INTEREST OF LIFE SAFETY, CONVENIENCE AND |
| | ENERGY CONSERVATION THESE LIGHTS SHOULD BE ON A 3 WAY |
| | SWITCH. |
| | SHEET E507, UNIT 8B |
| | 70. SEE COMMENT 55 ABOVE. |
| | 71. FBC-RE3901.2.2: ANY WALL SPACE 2 FT. OR MORE IN |
| | WIDTH SHALL REQUIRE A RECEPTACLE. ROOM ADJACENT TO |
| | KITCHEN |
| | SHEET E601, E602, E610, APPROVED W/PROVISO |
| | 72. NEC110.26 (D) ILLUMINATION: ILLUMINATION SHALL BE |
| | PROVIDED FOR ALL WORKING SPACES ABOUT ELECTRICAL |
| | SERVICE EQUIPMENT INSTALLED INDOORS AND SHALL NOT BE |
| | CONTROLLED BY AUTOMATIC MEANS ONLY. THIS APPLIES TO ALL |
| | ROOMS ENLARGED ON THIS SHEET. |
| | SHEET E701 |
| | 73. NEC 110.24: ALL SERVICE EQUIPMENT SHALL BE LEGIBLY |
| | MARKED IN THE FIELD WITH THE MAXIMUM AVAILABLE FAULT |
| | CURRENT. THE FIELD MARKING(S) SHALL INCLUDE THE DATE |
| | THE FAULT CURRENT CALCULATION WAS PERFORMED AND BE OF |
| | SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT |
| | INVOLVED. |
| | 74. CLARIFY FEEDER LABELED AS E702D'S DESTINATION. I |
| | CAN?T FIND IT ON SHEET E702. |
| | SHEET E703, APPROVED W/PROVISO |
| | 75. FIRE ALARM WORK UNDER SEPARATE PERMIT |
| | SHEET E1401 |
| | 76. THE PANEL SCHEDULE OF N1MSBHA DOES NOT MATCH THE |
| | RISER DIAGRAM OF SHEET E701. |
| | 77. CORRECT CKT. 17, 19. 21 OF LS1DPH TO MATCH SHEET |
| | E702 (LS21HA) |
| | 78. PANEL SCHEDULE OF E1DPH DOES NOT MATCH RISER |
| | DIAGRAM OF SHEET E702 |
| | SHEET E1406 |
| | 79. OCP FOR UNIT PENT PANEL DOES NOT MATCH WHAT IS |
| | REFLECTED ON RISER OF SHEET E701 |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |