| Date |
Text |
| 2016-09-15 18:01:36 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | 1. UPDATE PLANS WITH THE CHANGES MADE TO PERMIT |
| | 16040755, STRUCTURE PERMIT. SOME OF THE COMMENTS IN |
| | THIS LIST HAVE ALREADY BEEN CORRECTED IN THE STRUCTURE |
| | PERMIT AND HAVE BEEN FOUND CODE COMPLIANT. |
| | |
| | 2. FOR C.O. INFORMATION, PROVIDE THE FOLLOWING: |
| | TOTAL NUMBER OF BEDROOMS |
| | TOTAL NUMBER OF BATHROOMS |
| | TOTAL NUMBER OF ROOMS |
| | |
| | 3. FBC TABLE 705.8. SHEET A100 SHOWS THE NORTH |
| | ELEVATION (PARTIAL) AS 12FT 1IN FROM THE BUILDING TO |
| | THE CENTER LINE OF THE ALLEY; SHEET A200 INCLUDES THE |
| | LIMITATION OF 45 PERCENT UNPROTECTED OPENINGS ALLOWED. |
| | REVISE THE PLAN TO INCLUDE THE PERCENTAGE OF |
| | UNPROTECTED OPENINGS FOR THIS BUILDING, NORTH |
| | ELEVATION. |
| | |
| | 4. A100 SITE PLAN SHOWS THE APPROX CENTER OF ALLEY. |
| | REVISE TO INCLUDE EXACT DIMENSION BASED ON THE SURVEY |
| | OR PLAT SO COMPLIANCE WITH FBC TABLE 602, 705.8 CAN BE |
| | DETERMINED. |
| | |
| | 5. FBC TABLE 602, BASED ON FIRE SEPARATION DISTANCE |
| | (CHAPTER 2), THE NORTH WALL REQUIRES A 1 HOUR RATING. |
| | A. REVISE TO INCLUDE ON SHEET A201 AND ALL OTHER SHEETS |
| | AFFECTED OR REVISE SITE PLAN ON A100 TO CLARIFY FIRE |
| | SEPARATION DISTANCE. |
| | B. REVISE DOOR SCHEDULE TO COMPLY WITH FBC TABLE 716.5 |
| | FOR AFFECTED DOORS. |
| | |
| | 6. FBC TABLES 601, 602, PROVIDE DETAILS FOR THE FIRE |
| | RATED ELEMENTS, INCLUDING THE NORTH WALL WHICH HAS A |
| | FIRE SEPARATION DISTANCE LESS THAN 30FT, FBC 703, 704. |
| | |
| | 7. A200, STRUCTURAL FIRE RESISTANCE RATING |
| | REQUIREMENTS, REVISE STRUCTURE AND ROOF REQUIREMENTS TO |
| | BE CONSISTENT WITH TABLE 601 OR REVISE PLAN TO INCLUDE |
| | APPLICABLE EXCEPTION. |
| | |
| | 8. A200, STRUCTURAL FIRE RESISTANCE RATING |
| | REQUIREMENTS, A TABLE FROM THE FBC WAS INCLUDED BUT |
| | DOES NOT INDICATE HOW THE TABLE APPLIES TO THIS |
| | PROJECT. REVISE TO INCLUDE THE WALLS AFFECTED, FBC |
| | TABLE 602, FBC 107. |
| | |
| | 9. FBC 403.5.3 AND 403.5.3(1), REVISE PLAN TO CLARIFY |
| | PROPOSED EXIT STAIR DOOR OPERATION (OR ADVISE WHERE |
| | THIS INFORMATION CAN BE FOUND). |
| | |
| | 10. A200 SPECIFIES BOTH OCCUPANCY SEPARATION AND NON |
| | SEPARATED OCCUPANCIES. REVISE PLAN TO CLARIFY WHICH OF |
| | THE TWO METHODS IS PROPOSED, FBC 508. THIS INFORMATION |
| | IS ALSO REQUIRED FOR THE TENANT BUILD OUTS, FBC 107. |
| | |
| | 11. A200 OCCUPANCY SEPARATION REFERS TO ASSEMBLY WITHIN |
| | EDUCATIONAL OCCUPANCIES (NOTE 1), REMOVE THIS AND OTHER |
| | NOTES WHICH DO NOT APPLY TO THIS PROJECT, OR CLARIFY |
| | WHERE THIS IS OR MAY BE APPLICABLE. |
| | |
| | 12. A200 OCCUPANCY CLASSIFICATION INCLUDES A1 THEATER; |
| | ADVISE WHERE THIS CAN BE LOCATED, OR IS THIS A FUTURE |
| | IMPROVEMENT? FBC 107. REMOVE IF NOT APPLICABLE. |
| | |
| | 13. A200 AND OTHER PAGES, FIRE RESISTANCE REQUIREMENTS |
| | WALLS, ITEM C, IS NOT CLEAR WHERE THIS IS APPLICABLE. |
| | REVISE TO REFLECT THE REQUIREMENT FOR THIS PROJECT. IT |
| | WOULD BE HELPFUL IF THE ACTUAL FIRE RATING REQUIREMENTS |
| | SPECIFIC TO THIS PROJECT WERE INCORPORATED INTO THIS |
| | TABLE (SUGGESTED, NOT REQUIRED). |
| | |
| | 14. SPECIFY ACCESSIBLE MEANS OF EGRESS SELECTED, FBC |
| | BUILDING 1007, FBC ACCESSIBILITY 207. REVISE PLAN TO |
| | SHOW COMPLIANCE WITH METHOD SELECTED IF ALL ITEMS ARE |
| | NOT IMMEDIATELY APPARENT (FOR EXAMPLE, IBC2000 ELEVATOR |
| | AS MEANS OF EGRESS COMPONENT). |
| | |
| | 15. A200 REGARDING SIGNAGE ITEM 2; CLARIFY ACCESSIBLE |
| | MEANS OF EGRESS SELECTED AND REVISE NOTE IF APPLICABLE. |
| | |
| | 16. A200, SIGNAGE NOTE 3, THE LANGUAGE, LOCATION AND |
| | CODE REFERENCE ARE NOT CONSISTENT WITH FBC 703.7; |
| | REVISE OR CLARIFY. VERIFY THAT ALL NOTES HAVE |
| | SPECIFICATIONS AND CODE REFERENCES CONSISTENT WITH FBC |
| | 2014, FBC 107. IT APPEARS THAT SEVERAL REFERENCES ARE |
| | FROM A PREVIOUS CODE VERSION. |
| | |
| | 17. A200 FIRE EXTINGUISHER NOTES DO NOT REFERENCE FBC |
| | 906, REVISE. |
| | |
| | 18. A200 INCIDENTAL USE AREAS AND NON PROTECTED SHAFT |
| | DO NOT APPEAR TO BE APPLICABLE. EITHER REMOVE OR REVISE |
| | TO CLARIFY LOCATIONS PROPOSED, FBC 107. |
| | |
| | 19. FOR C.O., AN ACCURATE OCCUPANT LOAD FOR THE |
| | BUILDING IS REQUIRED. SEE A202; GARAGE OCC LOAD IN THE |
| | CHART IS NOT CONSISTENT WITH THE GARAGE OCC LOAD ON THE |
| | PLAN. THE TOTAL OCCUPANTS PER LEVEL AND OCCUPANT LOAD |
| | CATEGORY ARE LACKING SEVERAL FLOORS (15 TO 23), |
| | PLEASE CORRELATE AND UPDATE TO REFLECT CORRECTED |
| | OCCUPANT LOAD ON THE POOL DECK AND ANY OTHER CHANGES. |
| | |
| | 20. FBC 406.4, CLASSIFY THE PARKING GARAGE AS EITHER |
| | ENCLOSED OR OPEN. IT IS SUGGESTED THAT THIS BE |
| | INCORPORATED WITH THE BUILDING GENERAL DATA A201. IF |
| | OPEN, PROVIDE PERCENTAGE OF OPENINGS PROVIDED TO SHOW |
| | COMPLIANCE WITH FBC 406.5. IF ENCLOSED, PROVIDE |
| | VENTILATION 406.6.2. |
| | |
| | 21. A202, LIFE SAFETY TCO NOTES INCLUDES FOUR TCO |
| | PHASES; PLAN SHOWS TWO, PLEASE CORRELATE. |
| | |
| | 22. A202, THE LIFE SAFETY PLAN LACKS STAIR NUMBER |
| | DESIGNATIONS. PROVIDE IN ORDER TO CORRELATE WITH |
| | DETAILS ON A701-A712, FBC 107. CHECK ALL SHEETS. |
| | |
| | 23. IT IS NOT CLEAR WHERE THE EXIT DISCHARGE IS LOCATED |
| | FOR STAIR LOCATED AT GRIDLINES H3 SHEET A202, FBC 107. |
| | (ITEM ADDRESSED IN STRUCTURE PERMIT, PLEASE UPDATE.) |
| | |
| | 24. AS301 LEVEL 1, THE ACCESSIBLE ROUTE FOR THE |
| | ACCESSIBLE VAN PARKING SPACE IS NOT CLEAR; THIS WAS |
| | ADDRESSED IN STRUCTURE PERMIT, PLEASE UPDATE PLANS. |
| | |
| | 25. AVIS, LEASING OFFICE, RETAIL/RESTAURANT, AND |
| | PASSENGER PARKING MINIMUM REQUIREMENTS ARE COVERED BY |
| | FBC 5TH EDITION ACCESSIBILITY 208, RESIDENTIAL PARKING |
| | MINIMUM REQUIREMENTS DETERMINED BY FBC 5TH EDITION |
| | ACCESSIBILITY FAIR HOUSING. |
| | |
| | A100, PARKING SCHEDULE, AND OTHER PAGES, REVISE TO SHOW |
| | COMPLIANCE WITH THE FOLLOWING ITEMS: |
| | |
| | THE OPERATION OF THE AVIS BUSINESS AND SPACES IS NOT |
| | CLEAR. REVISE THE PLAN TO CLARIFY HOW THIS BUSINESS |
| | WILL OPERATE. WILL CUSTOMERS PICK UP THE CARS, OR WILL |
| | THE CAR BE BROUGHT TO THE CUSTOMER? IT APPEARS THAT AN |
| | ACCESSIBLE AVIS SPACE OR A PASSENGER LOADING ZONE MAY |
| | BE REQUIRED. REVISE PLAN TO DEMONSTRATE COMPLIANCE (OR |
| | EXEMPTION), INCLUDING APPLICABLE DETAILS. IF THE |
| | PARKING SPACES ARE FOR AUTO STORAGE ONLY, REVISE PLAN |
| | TO INCLUDE THIS INFORMATION AS WELL AS DETAILS FOR THE |
| | PASSENGER LOADING ZONE (FBC ACCESSIBILITY 208.1, 503), |
| | OR REVISE PLAN TO INCORPORATE INFORMATION REGARDING |
| | FUNCTION OF THE AUTO RENTAL AREA AND HOW THIS AREA |
| | COMPLIES WITH (OR IS EXEMPT FROM) ACCESSIBILITY. |
| | |
| | 26. FBC ACCESSIBILITY 208, PARKING FOR THE RETAIL AND |
| | RESTAURANT AREAS IS NOT CLEAR. REVISE PLAN TO INDICATE |
| | NUMBER OF SPACES, ACCESSIBLE SPACES, VAN SPACES, AND |
| | LOCATION OR NOTE IF NONE OF THE PARKING SPACES IN THIS |
| | STRUCTURE ARE FOR THE RETAIL/RESTAURANT AREAS. |
| | |
| | 27. SEE PLUMBING COMMENTS REGARDING ACCESSIBILITY AND |
| | REVISE PLAN TO SHOW COMPLIANCE. |
| | |
| | 28. A212, CLARIFY USE OF THE AMENITIES ROOM, FBC 107. |
| | |
| | 29. LEASING OFFICE PARKING PROVIDED IS NOT CLEAR. |
| | REVISE PLAN TO DESIGNATE NUMBER OF PARKING SPACES |
| | DEDICATED TO LEASING, ACCESSIBLE AND VAN SPACES (NUMBER |
| | AND LOCATIONS), FBC ACCESSIBILITY 208. IT MAY BE |
| | HELPFUL TO DESIGNATE WHICH FLOORS OR AREAS ARE FOR |
| | RESIDENTS, RETAIL VISITORS, AND TRANSIT. |
| | |
| | 30. ONE GUEST SPACE IS SHOWN ON THE PARKING SCHEDULE. |
| | REVISE TO DESIGNATE WHETHER THIS IS FOR PASSENGER, |
| | LEASING, RETAIL OR RESIDENT PARKING AND NOTE LOCATION |
| | ON PLAN, FBC ACCESSIBILITY 208. |
| | |
| | 31. A212, POOL DECK OCCUPANT LOAD SHOULD BE CALCULATED |
| | AT 15SF GROSS PER PERSON, PLEASE REVISE TABLES AND |
| | OCCUPANT LOAD FOR THE POOL DECK. IT DOES NOT APPEAR |
| | THAT EXITING IS ADEQUATE FOR THIS ASSEMBLY AREA; FBC |
| | 5TH EDITION TABLE 1004.1.2. THIS ITEM WAS ADDRESSED IN |
| | THE STRUCTURE PERMIT; PLEASE REVISE TO BE CONSISTENT |
| | WITH 16040755. |
| | 32. REVISE PLAN TO SHOW THE 18IN MANEUVERING CLEARANCE, |
| | PULL SIDE (FBC ACCESSIBILITY 404.2.4), DOOR LOCATED ON |
| | SHEET A301, DOOR R03H (FBC 5TH ED. ACCESSIBILITY |
| | 206.4.5), OR OTHERWISE INDICATE THAT THIS WILL NOT BE |
| | THE ONLY DOOR SERVING A TENANT SPACE, OR PROVIDE AN |
| | OPENER. |
| | |
| | 33. SHEET AS212A, DOORS TO LOBBY FROM POOL AREA SWING |
| | AGAINST PATH OF TRAVEL, FBC 1008.1.2. |
| | |
| | 34. ADVISORY; SHEET AS203, THE SOUTH ACCESSIBLE PARKING |
| | SPACE (GRIDLINE G4) REQUIRES THE OCCUPANT TO TRAVEL |
| | BEHIND THE VAN PARKING SPACE TO ACCESS THE LOBBY, AVIS, |
| | AND RESIDENTIAL LOBBY. THIS WILL BE REQUIRED TO BE |
| | CORRECTED ON THE BUILDING PERMIT. |
| | |
| | 35. FBC 505, LEVEL 12.5 IS NOT SHOWN AS A STORY ON THE |
| | BUILDING DATA. EITHER REVISE PLAN TO SHOW COMPLIANCE |
| | WITH REQUIREMENTS FOR MEZZANINES, OR REVISE BUILDING |
| | DATA INFORMATION. |
| | |
| | 36. COMPLIANCE WITH FBC 5TH EDITION ACCESSIBILITY, FAIR |
| | HOUSING IS NOT CLEAR. IF DESIGNING USING THE FAIR |
| | HOUSING ACT DESIGN MANUAL, PROVIDE UNIT LAYOUTS WITH |
| | UNIT TYPE AND DIMENSIONS SHOWING COMPLIANCE. |
| | |
| | IF USING ANOTHER METHOD, PROVIDE DETAILS AND DIMENSIONS |
| | TO SHOW COMPLIANCE. |
| | |
| | 37. F202 AND E202 SHOW A MEZZANINE, PROVIDE AN |
| | ARCHITECTURAL FLOOR PLAN; LOCATION IS NOT CLEAR, AND IS |
| | THIS A MEZZANINE PER FBC505? INCLUDE ALL INFORMATION |
| | REQUIRED TO DETERMINE CODE COMPLIANCE FOR THIS AREA, |
| | FBC 107. IF THIS IS NOT A MEZZANINE, IT IS SUGGESTED |
| | THAT THE NAME OF THE AREA BE REVISED FOR CLARITY. |
| | |
| | 38. UNIT NAMES ON LIFE SAFETY SHEETS ARE NOT THE SAME |
| | AS FLOOR PLANS (FOR INSTANCE, SEE A202 AND A302), |
| | CORRELATE. |
| | |
| | 39. A FIRE ALARM SYSTEM IN COMPLIANCE WITH FBC |
| | 907.2.13.1 IS REQUIRED PER FBC 403.4.2. SMOKE DETECTORS |
| | IN COMPLIANCE WITH FBC 907.2.13.1 IS REQUIRED PER FBC |
| | 403.4.1. REVISE PLAN TO INCLUDE NOTES, OR ADVISE WHERE |
| | COMPLIANCE WITH THESE STANDARDS CAN BE LOCATED ON THE |
| | PLAN. BOTH ITEMS REQUIRE SEPARATE APPLICATIONS, |
| | PERMITS, PLANS AND FEES, FBC 107, AND WILL BE REVIEWED |
| | AT THAT TIME. |
| | |
| | 40. FBC 403.4.5, EMERGENCY RESPONDER RADIO COVERAGE, |
| | REVISE PLAN TO INCLUDE A NOTE TO SHOW COMPLIANCE WITH |
| | THIS SECTION. |
| | |
| | NFPA 1, CHAPTER 11, BUILDING SERVICES; 11.10 TWO-WAY |
| | RADIO ENHANCEMENT SERVICES. |
| | 11.10.1 IN ALL NEW AND EXISTING BUILDINGS, MINIMUM |
| | RADIO SIGNAL STRENGTH FOR FIRE DEPARTMENT |
| | COMMUNICATIONS SHALL BE MAINTAINED AT A LEVEL |
| | DETERMINED BY THE AHJ. |
| | MAINTAIN A MINIMUM RADIO SIGNAL STRENGTH OF 102.0 DBM |
| | FOR THE RADIO SYSTEM USED BY WEST PALM BEACH FIRE |
| | RESCUE. IF THE MINIMUM CANNOT BE MAINTAINED, A |
| | BI-DIRECTIONAL AMPLIFIED SYSTEM SHALL BE INSTALLED WITH |
| | A MINIMUM 2-HOUR RUN TIME BATTERY BACK-UP. |
| | |
| | 41. STANDBY POWER, FBC 403.4.8, EMERGENCY POWER 403.4.9 |
| | REQUIRED. REVISE PLAN TO SHOW COMPLIANCE OR ADVISE AS |
| | TO WHERE THIS CAN BE LOCATED. CLARIFY WHICH ITEMS WILL |
| | BE ON EMERGENCY POWER. WHICH ELEVATOR(S) WILL BE |
| | INCLUDED (FBC 1007)? |
| | |
| | 42. FBC 403.5.4 SMOKEPROOF EXIT, THE NEW STAIR (5?) |
| | DOES NOT APPEAR ON THE MECHANICAL SHEETS (MEZZANINE |
| | LEVEL AS SHOWN ON FIRE AND ELEC PAGES, M704, OTHER |
| | PAGES). |
| | |
| | 43. FBC 905.4, STANDPIPE REQUIRED IN STAIRS, UNABLE TO |
| | LOCATE THIS FOR THE NEW STAIR. |
| | |
| | 44. FBC 403.6.1, COMPLIANCE WITH FIRE SERVICE ACCESS |
| | ELEVATOR REQUIREMENTS IS NOT CLEAR. SHEET A202 (AND |
| | OTHER LIFE SAFETY SHEETS) SHOW A FIRE SERVICE LOBBY ON |
| | THE WEST SIDE WHICH IS NOT INCLUDED IN TCO AREA 1. ALL |
| | LIFE SAFETY SYSTEMS ARE TO BE IN PLACE FOR TCO. |
| | |
| | THE ELEVATORS DESIGNATED AS FIRE SERVICE IS NOT CLEAR. |
| | FOR INSTANCE, SEE LEVEL 8. IT APPEARS THAT ONLY THE |
| | NORTH ELEVATOR, WEST SIDE IS DESIGNATED AS THE FIRE |
| | SERVICE ELEVATOR, BUT AT LEAST TWO ARE REQUIRED PER FBC |
| | 403.6.1. |
| | REVISE PLAN TO SHOW COMPLIANCE WITH THE FIRE SERVICE |
| | ELEVATORS REQUIREMENT, INCLUDING THE WEIGHT CAPACITY |
| | REQUIREMENT. FIRE SERVICE ELEVATORS ARE TO COMPLY WITH |
| | FBC 3007. REVISE PLAN TO SHOW COMPLIANCE WITH 3007.2 |
| | RECALL, 3007.7.5 SIGNAGE, 3007.3 SPRINKLERS, 3007.4 |
| | WATER PROTECTION, 3007.6.1, 3007.6.2 HOISTWAY LIGHTING, |
| | 3007.7.2 1 HOUR SMOKE BARRIER FOR LOBBY, 3007.7.3 LOBBY |
| | DOORS, 3007.8 MONITORING, 3007.9 ELECTRICAL POWER, |
| | 3007.9.1 PROTECTION OF WIRING AND CABLES. |
| | |
| | 45. SOME LEVELS (FOR INSTANCE, LEVELS 12.5, 13) LACK A |
| | FIRE SERVICE ELEVATOR FBC 403. |
| | |
| | 46. FBC 3004, HOISTWAY VENTING NOT CLEAR, REVISE PLAN |
| | TO SHOW COMPLIANCE. |
| | |
| | 47. FBC 3002.4, SHOW LOCATION OF STRETCHER ELEVATOR |
| | SIGNAGE. |
| | |
| | 48. FBC 908.7, CARBON MONOXIDE DETECTORS ARE REQUIRED, |
| | REVISE. |
| | |
| | 49. PRODUCT APPROVALS FOR COMPONENTS AND CLADDING HAVE |
| | NOT BEEN SUBMITTED. THEY MAY BE A DEFERRED SUBMITTAL. |
| | THEY MAY BE SUBMITTED, PRIOR TO INSTALLATION, AS A |
| | REVISION, PRIOR TO INSTALLATION. |
| | |
| | 50. FLOORING UNDERLAYMENT IS TO COMPLY WITH FBC 1207.2, |
| | 1207.3, AND 603.1. THIS MAY BE A DEFERRED SUBMITTAL. IF |
| | DEFERRED, THE TEST REPORTS ARE TO BE SUBMITTED AS A |
| | REVISION PRIOR TO INSTALLATION. AS STRUCTURAL PLANS |
| | SHOW AN 8 INCH SLAB, PRODUCTS TESTED WITH EITHER A 6 |
| | INCH OR AN 8 INCH SLAB ARE ACCEPTABLE. |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |
| | 51. SMOKE CONTROL REFERENCED, BUT REPORT NOT PROVIDED, |
| | FBC 909.4. |
| | |
| | 52. A SPOT CHECK ON THE ENERGY CALCS WAS DONE. PLEASE |
| | CLARIFY THE FOLLOWING: |
| | EXTERNAL LIGHTING SHOWS NO ENTRY. |
| | |
| | 53. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING |
| | PROVISOS: |
| | |
| | A. PROVISO: TCO AT EACH PHASE IS SUBJECT TO APPROVAL OF |
| | THE BUILDING OFFICIAL (OR HIS REPRESENTATIVE) AND FIRE |
| | DEPARTMENT, AND MAY INCLUDE ITEMS NOT WITHIN THE SCOPE |
| | OF THIS REVIEW. A TCO REQUEST FORM AND FEE WILL BE |
| | REQUIRED. THIS FORM IS AVAILABLE UPON REQUEST BY EMAIL. |
| | |
| | C. SEPARATE PERMITS (APPLICATION, PLANS, REVIEWS, AND |
| | FEES) REQUIRED FOR ALL ITEMS OTHER THAN MECHANICAL, |
| | ELECTRICAL, AND PLUMBING FOR THE BUILDING AS SHOWN ON |
| | THE PLANS. THIS INCLUDES SIGNS, FIRE ALARM, FIRE |
| | SPRINKLERS, LANDSCAPING. |
| | |
| | SUB PERMITS (APPLICATION, SUB PERMIT FEE) ARE REQUIRED |
| | FOR MECHANICAL, ELECTRICAL, AND PLUMBING PRIOR TO |
| | COMMENCEMENT OF WORK. |
| | |
| | A ROOFING SUB PERMIT IS REQUIRED PRIOR TO COMMENCEMENT |
| | OF ROOFING WORK. AS ROOF DOCUMENTS HAVE NOT BEEN |
| | PROVIDED, THIS IS A DEFERRED SUBMITTAL. PRODUCT |
| | APPROVALS REVIEWED BY DESIGNER OF RECORD, SELECTED |
| | ASSEMBLY, ENGINEERING IF APPLICABLE ARE TO BE SUBMITTED |
| | AS A REVISION WITH A ROOF PERMIT APPLICATION. |
| | |
| | D. COMPONENTS AND CLADDING PRODUCT APPROVALS ARE TO BE |
| | REVIEWED BY DESIGNER OF RECORD AND SUBMITTED AS A |
| | REVISION PRIOR TO INSTALLATION. |
| | |
| | E. PROVISO, THIS STUCTURE SERVES A BUILDING WHICH HAS |
| | NOT BEEN REVIEWED BY THIS DEPARTMENT (TRAIN STATION). |
| | ACCESSIBLE ROUTE IN COMPLIANCE WITH FBC 5TH EDITION |
| | ACCESSIBILITY IS REQUIRED AND WILL BE VERIFIED IN THE |
| | FIELD. |
| | |
| | |