| Date |
Text |
| 2016-08-11 10:05:21 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: REHAB HOUSE |
| | JOB ADDRESS: 217 BUTLER ST. |
| | DESCRIPTION: FIRE ALARM PER PLANS |
| | MASTER PERMIT: 16070697 |
| | REVISION: |
| | |
| | BELOW ARE COMMENTS RELATED TO THE FAILED ELECTRICAL |
| | REVIEW: |
| | |
| | IN ADDITION TO THE FIRE REVIEWER?S COMMENTS, BELOW ARE |
| | ADDITIONAL ELECTRICAL REVIEW COMMENTS. THE FIRE ALARM |
| | SYSTEM AS DESIGNED DOES NOT MEET THE MINIMUM FIRE ALARM |
| | SYSTEM FBC REQUIREMENTS AS INDICATED BELOW: |
| | |
| | 1. FBC-B 308.3: ACCORDING TO THIS CODE AND CONFIRMED BY |
| | YOUR LETTER THE OCCUPANCY CLASSIFICATION OF THESE |
| | PREMISES IS I1. |
| | 2. FBC-B 907.2.6: THIS SECTION REQUIRES THAT A FIRE |
| | ALARM SYSTEM IN ACCORDANCE WITH FBC-B 907.5 BE |
| | INSTALLED. THIS FURTHER REQUIRES SMOKE DETECTOR |
| | COMPLIANCE PER FBC-B 907.2.6.1, 907.2.6.2, 907.2.6.3.3. |
| | 3. FBC-B 907.1.2: BELOW AS SPECIFIC SUBMITTAL |
| | REQUIREMENTS MISSING FROM YOUR PLANS: |
| | A) INDICATE THE USE OF THE ROOM BEHIND THE LAUNDRY ROOM |
| | ON THE FIRST FLOOR, THE ROOM INSIDE OF THE KITCHENS OF |
| | UNITS 3 & 6. PROVIDE A FLOOR PLAN FOR THE TWO |
| | APARTMENTS SHOWN ON THE DETACHED STRUCTURE. SHOW THE |
| | INTER-CONNECTION OF THE FIRE ALARM CONDUCTORS BETWEEN |
| | BOTH BLDGS. |
| | B) PER OCCUPANCY CLASSIFICATION REQUIREMENTS THERE ARE |
| | ADDITIONAL INITIATION AND NOTIFICATION DEVICES MISSING |
| | FROM THE SYSTEM AS DESIGNED. |
| | C) SHOW THE LOCATION OF THE ELECTRICAL PANEL PROVIDING |
| | THE ELECTRICAL POWER FOR THE FIRE ALARM SYSTEM. |
| | D) PROVIDE VOLTAGE DROP CALCULATIONS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |