| 2016-07-20 13:17:42 | 217 BUTLER STREET | | | PERMIT #16070697 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | NOTE: A CHANGE OF OCCUPANCY PERMIT IS NEEDED TO CONVERT | | | THE BUILDING FROM APARTMENTS TO A PLACE OF | | | REHABILITATION. | | | | | | NO NOTIFICATION DEVICES INSTALLED IN BEDROOMS. HOW WILL | | | 75 DB AT THE PILLOW BE OBTAINED? | | | | | | NO NOTIFICATION DEVICES INSTALLED IN FIRST FLOOR COMMON | | | KITCHEN, DINING, RESTROOMS, LAUNDRY AND SECOND FLOOR | | | LARGE OFFICE AREA. | | | | | | NO BATTERY CALCULATIONS OR VOLTAGE DROP CALCULATIONS | | | SUBMITTED. | | | | | | A CERTIFICATE OF COMPLETION AND A THIRD PARTY | | | MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL | | | BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION. | | | | | | WESLEY JOLIN | | | ASSISTANT FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | | | | | | | | | | | | | | | | | | | | | | |
|