| Plan Review Notes For Permit 16070695 |
| Permit Number |
16070695 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2016-08-03 14:35:26 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | | | | PASSED WITH THE FOLLOWING PROVISO ( RED LINED ON PLANS | | | ) | | | | | | 1) NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 | | | VOLT, SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE | | | OUTLET SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR | | | THE SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL | | | BE LOCATED WITHIN 25 FT. OF THE EQUIPMENT. |
|