| Notes |
| Date |
Text |
| 2016-07-25 15:04:48 | REVIEW 2014 5TH FBC ED. NEC 2011 | | | MARIO VALDES | | | ELECTRICAL PLAN EXAMINER | | | 561-805-6713 | | | [email protected] | | | | | | - WEST PALM BEACH CITY AMENDMENTS REQUIRE PLANS TO BE | | | SIGNED AND DATED BY DESIGN PROFFESIONAL RESPONSIBLE FOR | | | THE DRAWINGS. | | | | | | - PLEASE IDENTIFY CIRCUITS FEEDING NEW EQUIPMENT ON THE | | | FLOOR PLANS AND PROVIDE A PANEL SCHEDULE MATCHING IN | | | ORDER TO VERIFY OCPD,CONDUCTOR, AND CONDUIT SIZES TO BE | | | IN ACCORDANCE WITH NAME PLATE RATING. FBC 107 MINIMUM | | | PLAN REVIEW. | | | | | | - NEC 210.63 HVAC EQUIPMENT SERVICE OUTLET. A 125 VOLT, | | | SINGLE-PHASE, 15 OR 20-AMPERE-RATED RECEPTACLE OUTLET | | | SHALL BE INSTALLED AT AN ACCESSIBLE LOCATION FOR THE | | | SERVICING OF HVAC EQUIPMENT. THE RECEPTACLE SHALL BE | | | LOCATED WITHIN 25 FT. OF THE EQUIPMENT. | | | THE OUTDOOR RECEPTACLE OUTLET BY THE CONDENSING UNITS | | | SHALL BE GFCI PROTECTED PER NEC 210.8(B)(4). | | | | | | - ELECTRICAL SUB PERMIT REQUIRED ! |
|