| 2016-07-26 13:31:40 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) SHEET D 1.0 - THE PLAN INDICATES THE REMOVAL 9AND |
| | NON-REPLACEMENT) OF THE ELEVATOR LOBBY DOORS. ELEVATOR |
| | DOORS CAN BE REMOVED UNDER CERTAIN EXEMPTIONS. SOME |
| | ELEVATORS DOORS ARE REQUIRED TO ASSIST IN FIRE |
| | PROTECTION, PRESSURIZATION, SMOKE CONTROL , ETC. |
| | |
| | PLEASE PROVIDE A REVIEW FROM THE ENGINEER OF RECORD |
| | THAT THE PURPOSE AND FUNCTION OF ELEVATOR LOBBY DOORS |
| | HAS BEEN REVIEWED AND VERIFIED. ADDITIONALLY, THE |
| | REMOVEAL OF THESE DOORS IS WITHIN CODE REQUIRMENTS,( |
| | PROVIDE THE CODE) AND WILL NOT AFFECT THE PREVIOUSLY |
| | ENGINEERED LIFE SAFETY FIRE PROTECTIONS SYSTEMS OF THE |
| | BUILDING. |
| | |
| | |
| | 2) SHEET E 2.1 - NOTE # 2 INDICATES WORK ON FIRE ALARM |
| | DEVICES. |
| | |
| | PLEASE PROVIDE A NOTE INDICATING THAT ALL WORK THE FIRE |
| | ALARM SYSTEM SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS |
| | BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| | |
| | |
| | |
| | 3) SHEET E 2.1 - INFORMATIONAL PURPOSES ONLY : |
| | |
| | THERE DOES NOT APPEAR ANY VISUAL FIRE ALARM DEVICES. |
| | THOUGH THIS IS A CONCEPTUAL DRAWING, ENSURE THAT THE |
| | FIRE ALARM SHOP DRAWINGS INCLUDE ANY APPLICABLE VISUAL, |
| | AS WELL AS, AUDIBLE DEVICES. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | |
| | PETER LEDUC |