| 2016-07-21 14:58:17 | 1ST REVIEW MECHANICAL, EXISTING BUILDING CODES. |
| | PERMIT #16070628 |
| | 7/21/16 |
| | |
| | 1) SHEET ME-1: REFER TO SECTION 809.2 FBC-14 EXISTING |
| | BUILDING CODE AND PROVIDE MINIMUM VENTILATION |
| | CALCULATIONS FOR ALL ROOMS AND SPACES PER TABLE 403.3 |
| | FBC-14 MECHANICAL. IDENTIFY ALL ROOMS AND SPACES ON THE |
| | PLANS AND PROVIDE A SCHEDULE THAT INDICATES THE |
| | REQUIRED AND PROVIDED CFMS OF OUTDOOR AIR. PLEASE NOTE |
| | THAT THIS IS NOT A BUSINESS OCCUPANCY AS INDICATED ON |
| | NTHE FLOOR PLAN NOTE- THIS IS AN A3 ASSEMBLY OCCUPANCY |
| | PER SECTION 303.4 FBC-14 BUILDING. |
| | |
| | 2) ME-1: REFER TO TABLE 403.3 AND PROVIDE EXHAUST |
| | VENTILATION CALCULATIONS FOR THE ALTERED AND MEN'S AND |
| | WOMEN'S TOILET AND LOCKER ROOMS. |
| | |
| | 3) ME-1: THE AC DRAWINGS ARE INCOMPLETE. A) SHOW THE AC |
| | SUPPLY AND EXHAUST DUCT RUNS, DIFFUSERS AND GRILLS IN |
| | THE TOILET POOMS, THE LOCKER ROOMS, B) SHOW POINTS OF |
| | CONNECTIONS FOR NEW BRANCH DUCTS TO EXISTING TRUNKS. C) |
| | PROVIDE EQUIPMENT SCHEDULES FOR THE EXISTING AC SYSTEMS |
| | AND SHOW THEIR LOCATIONS ON THE PLANS. |
| | |
| | 4) ME-1: THE RETURN DUCT SIZES FROM THE AEROBICS AND |
| | BREAKROOM ARE NOT SHOWN. |
| | |
| | 5) ME-1: INDICATE THE SUPPLY CFMS AT THE BREAKROOM |
| | DIFFUSER. |
| | |
| | 6) ME-1: THE 12" DUCT SUPPLYING 1250 CFMS OF AIR TO THE |
| | AEROBICS ROOM IS UNDERSIZED PER ASHRAE/ACCA APPROVED |
| | DUCTULATOR- MINI,UM 16" REQUIRED. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |