| 2016-07-22 11:42:07 | 2223 PALM BEACH LAKES BOULEVARD |
| | PERMIT #16070628 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE PLANS INDICATE THIS IS A BUSINESS OCCUPANCY; |
| | HOWEVER, THE LIFE SAFETY CODE WILL CLASSIFY THIS |
| | OCCUPANCY AS AN ASSEMBLY. |
| | |
| | EVERY ASSEMBLY OCCUPANCY ROOM NOT HAVING FIXED SEATS |
| | SHALL HAVE THE OCCUPANT LOAD OF THE ROOM POSTED IN A |
| | CONSPICUOUS PLACE NEAR THE MAIN EXIT FROM THE ROOM. |
| | SIGNS SHALL BE DURABLE AND INDICATE THE NUMBER OF |
| | OCCUPANTS PERMITTED FOR EACH ROOM. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | THE NORTH GATE OF THE FRONT ENTRANCE/FRONT DESK AREA |
| | SWINGS AGAINST THE FLOW OF EGRESS. GATES SHALL BE |
| | EQUIPPED WITH PANIC HARDWARE. |
| | |
| | THE EXISTING DOUBLE DOORS EQUIPPED WITH MAG-LOCKS |
| | INDICATE "EXIST LOCK." THESE DOORS SHALL FEATURE |
| | OBVIOUS SIGNAGE INDICATING "NOT AN EXIT." |
| | |
| | OVER THE YEARS, EMERGENCY LIGHTING HAS BEEN INSTALLED |
| | AND REMOVED FROM THIS SUITE. PROVIDE AN ELECTRICAL |
| | PHOTOMETRICS PLAN SHOWINGAT LEAST 1-FT CANDLE IS BEING |
| | PROVIDED ALONG ALL EGRESS PATHS. |
| | |
| | WHAT TYPE OF WALL FINISHES ARE INTENDED TO BE |
| | INSTALLED? |
| | |
| | THE ONLY FLOORING MATERIAL INDICATED IN THIS SPACE IS |
| | THE "TURF" AREA. PROVIDE PRODUCT DATA FOR THIS |
| | MATERIAL. FLOORING SHALL BE AT LEAST CLASS I. PER NFPA |
| | 10.2.7.4 CLASS I INTERIOR FLOOR FINISH SHALL BE |
| | CHARACTERIZED BY A CRITICAL RADIANT FLUX NOT LESS THAN |
| | 0.45 W/CM2. |
| | |
| | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE |
| | ALARM SYSTEM. |
| | |
| | WESLEY JOLIN |
| | ASSISTANT FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | [email protected] |
| | |
| | |