| Plan Review Notes For Permit 16070622 |
| Permit Number |
16070622 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-19 09:59:40 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | 1) THE PRODUCT APPROVAL IS MISSING REQUIRED PAGES 10 | | | AND 33. FBC 107.2.1 | | | | | | 2) THE PROJECT IS A LOW SLOPE (FLAT) ROOF LOCATED IN | | | EXPOSURE C. THE MAXIMUM DESIGN PRESSURE ON FOR THE | | | PROPOSED ASSEMBLY ON PAGE 11 IS -52.5 PSF. THE UPLIFT | | | PRESSURES AT THE PERIMETER AND CORNER AREAS WILL | | | REQUIRE INCREASED FASTENER DENSITIES. SUBMIT TWO SETS | | | OF SIGNED AND SEALED RAS 117 CALCULATIONS AS REQUIRED | | | BY LIMITATION NUMBER 7 OF THE PRODUCT APPROVAL. |
|