2016-07-19 09:59:40PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 1) THE PRODUCT APPROVAL IS MISSING REQUIRED PAGES 10
 AND 33. FBC 107.2.1
  
 2) THE PROJECT IS A LOW SLOPE (FLAT) ROOF LOCATED IN
 EXPOSURE C. THE MAXIMUM DESIGN PRESSURE ON FOR THE
 PROPOSED ASSEMBLY ON PAGE 11 IS -52.5 PSF. THE UPLIFT
 PRESSURES AT THE PERIMETER AND CORNER AREAS WILL
 REQUIRE INCREASED FASTENER DENSITIES. SUBMIT TWO SETS
 OF SIGNED AND SEALED RAS 117 CALCULATIONS AS REQUIRED
 BY LIMITATION NUMBER 7 OF THE PRODUCT APPROVAL.