16070609 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-09-29 13:58:59 | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY | | | FAC 61G20-3.002(33) FOR; | | | A) ROOF TILE AS SPECIFIED ON PLANS. NOA 07-0919.05 | | | SUBMITTED EXPIRED ON 12/16/12. NEED CURRENT NOA. | | | | | | 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 | | | CITY AMENDMENTS. | | | | | | 3- CLARIFY WHY SUBMITTING NOA 13-1217.01 FOR FLAT ROOF | | | DECKS. PLANS DON'T PROVIDE ANY SPECIFICATION FOR THIS | | | TYPE OF ROOFING. AND, CLEARLY IDENTIFY APPROVED | | | ASSEMBLY TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE: | | | IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES | | | FOR ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117 | | | CALCULATIONS WILL BE REQUIRED. SEE GENERAL LIMITATION | | | #7 ON LAST PAGE OF NOA SUBMITTED. | | | | | | |
|