| 2016-09-29 08:47:56 | 10/31/16 |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO AFTER |
| | CONTRACTOR'S INFORMATION IS UPDATED. PRODUCT APPROVALS |
| | MAY BE SUBMITTED LATER. CONTRACTOR TO ADVICE IF PROVISO |
| | OPTION IS PREFERRED AT THIS TIME. |
| | |
| | |
| | RESIDENTIAL (R3) ADDITION/ALTERATION SECOND BUILDING |
| | REVIEW CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014). |
| | |
| | ORIGINAL COMMENT: |
| | 1- CONTRACTOR LICENSE NUMBER SHOWN ON THE PERMIT |
| | APPLICATION (CPC057027) IS FOR A POOL CONTRACTOR. NEED |
| | TO PROVIDE LICENSE OF GENERAL, BUILDING OR RESIDENTIAL |
| | CONTRACTOR. SEC. 489.113 FLORIDA STATUTES. |
| | |
| | RESPONSE: |
| | NOT ADDRESSED. NEED TO REVISE INFORMATION ON THE PERMIT |
| | APPLICATION TO UPDATE INFORMATION THE CITY SYSTEM. |
| | |
| | 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR; |
| | A) ROOF TILE AS SPECIFIED ON PLANS. NOA 07-0919.05 |
| | SUBMITTED EXPIRED ON 12/16/12. NEED CURRENT NOA. |
| | |
| | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | DETAILS AND PLANS. PROVIDE ONLY THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED |
| | CONNECTOR OR ARCHITECT TO LIST THE CURRENT FLORIDA |
| | PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED |
| | CONNECTOR. |
| | NOTE: NOA 03-0123.05 SUBMITTED EXPIRED ON FEBRUARY 16, |
| | 2008. NEED CURRENT NOA OR FLORIDA PRODUCT APPROVAL. |
| | |
| | 3- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1 |
| | CITY AMENDMENTS. |
| | NOTE: NEED TO APPROVE ALL THE PRODUCT APPROVALS, |
| | INCLUDING THE ONES THAT WERE SUBMITTED EARLIER. |
| | |
| | 4- CLARIFY WHY SUBMITTING NOA 13-1217.01 FOR FLAT ROOF |
| | DECKS. PLANS DON'T PROVIDE ANY SPECIFICATION FOR THIS |
| | TYPE OF ROOFING. AND, CLEARLY IDENTIFY APPROVED |
| | ASSEMBLY TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. NOTE: |
| | IF SELECTED ASSEMBLY DOESN'T MEET THE DESIGN PRESSURES |
| | FOR ALL ROOF ZONES, THEN SIGNED AND SEALED RAS 117 |
| | CALCULATIONS WILL BE REQUIRED. SEE GENERAL LIMITATION |
| | #7 ON LAST PAGE OF NOA SUBMITTED. |
| | |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | ***PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. PLEASE DON"T STAPLE OLD DRAWING. SUBMITT OLD |
| | DRAWINGS FOR REFERENCE. |
| | |