| 2016-07-22 15:26:05 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| | FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| | |
| | THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| | AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| | PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| | INSPECTION. |
| | |
| | 1) SHEET A2 - PER NFPA 101, CHAPTER 43 BUILDING |
| | REHABILITATION |
| | |
| | |
| | 43.4 RENOVATIONS. |
| | 43.4.1 GENERAL REQUIREMENTS. |
| | 43.4.1.3 ALL NEW WORK SHALL COMPLY WITH THE |
| | REQUIREMENTS OF THIS CODE APPLICABLE TO EXISTING |
| | BUILDINGS. |
| | 43.4.1.4 THE WORK SHALL NOT MAKE THE BUILDING LESS |
| | CONFORMING WITH OTHER SECTIONS OF THIS CODE, OR WITH |
| | ANY PREVIOUS APPROVED ALTERNATIVE ARRANGEMENTS, THAN IT |
| | WAS BEFORE THE RENOVATION WAS UNDERTAKEN, UNLESS |
| | OTHERWISE SPECIFIED IN 43.4.1.5. |
| | |
| | ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR |
| | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND |
| | SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY |
| | CERTIFIED LIFE SAFETY CONTRACTORS. |
| | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE |
| | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| | CONSTRUCTION PERIOD. |
| | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND |
| | BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| | AND COMPLETE PROTECTION IS RETURNED. |
| | |
| | 2) THE FIRE INSPECTOR WILL REVIEW AND VERIFY COMPLAINCE |
| | NOTED ABOVE. PLEASE ENSURE REVIEW AND COMPLAINCE PRIOR |
| | TO INSPECTION. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |