2016-07-18 15:44:311ST REVIEW MECHANICAL
 PERMIT #16070502
 7/18/16
  
 1) THE 8 " AND 6" FLEX DUCTS SUPPLYING 300 CFMS OF AIR
 TO THE KITCHEN ARE UNDERSIZED PER ASHRAE AND ACCA DUCT
 SIZING METHODOLOGY. PLEASE INCREASE THE DUCT SIZE TO 9"
 UP UNTIL THE LAST 150 CFM DROP WHICH CAN BE A 6"
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER