| Plan Review Notes For Permit 16070502 |
| Permit Number |
16070502 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-18 15:44:31 | 1ST REVIEW MECHANICAL | | | PERMIT #16070502 | | | 7/18/16 | | | | | | 1) THE 8 " AND 6" FLEX DUCTS SUPPLYING 300 CFMS OF AIR | | | TO THE KITCHEN ARE UNDERSIZED PER ASHRAE AND ACCA DUCT | | | SIZING METHODOLOGY. PLEASE INCREASE THE DUCT SIZE TO 9" | | | UP UNTIL THE LAST 150 CFM DROP WHICH CAN BE A 6" | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|