| 2016-07-18 10:21:55 | JOB PERMIT NUMBER: 16070494 |
| | JOB ADDRESS: 471 SPENCER DRIVE |
| | WEST PALM BEACH FLORIDA |
| | DATE: JULY 18 2016 |
| | ELECTRICAL PLAN REVIEW COMMENTS |
| | |
| | THE PLANS FOR THE ABOVE MENTIONED PERMIT APPLICATION |
| | HAVE BEEN REVIEWED FOR COMPLIANCE WITH THE EDITION OF |
| | THE NEC, (NATIONAL ELECTRICAL CODE) AND THE FBC, |
| | (FLORIDA BUILDING CODE) AS WELL AS THE CITY OF WEST |
| | PALM BEACH AMENDMENTS IN EFFECT AT THE TIME OF |
| | SUBMITTAL. BELOW IS A LIST OF THE DEFICIENCIES NOTED. |
| | |
| | - IN ADDITION TO THE INFORMATION PROVIDED ADD CONDUIT |
| | SIZES, NEMA RATING, THE GROUNDING DETAIL TO INCLUDE GEC |
| | SIZE, LASTLY PROVIDE A SERVICE CALCULATION TO VERIFY IF |
| | SUFFICIENT TO HANDLE CURRENT LOADS. FBC 107 MINIMUM |
| | PLAN REVIEW, NEC 250.66, NEC 110.28, NEC 220 & 215.5 |
| | - PROVIDE "AIC" RATING OF OVERCURRENT PROTECTION |
| | DEVICES AND "SCR" OF ELECTRICAL EQUIPMENT. FPL FAULT |
| | CURRENT LETTER SHALL BE ATTACHED TO THE SUBMITTAL TO |
| | VERIFY THE INSTALLATION WITHSTANDS LINE TO LINE FAULTS |
| | IF IMPOSED ON ELECTRICAL APPARATUS. NEC 110.9 & 110.10, |
| | NEC 110.24 |
| | - INSTALL ALL REQUIRED PERMANENT PLAQUES SUCH AS |
| | IDENTIFICATION LABEL OF EACH DISCONNECT SHOWING TENANT |
| | ADDRESS AND ANY ADDITIONAL DETAIL. FURTHERMORE INSTALL |
| | ARC FLASH WARNING LABELS AT EACH DISCONNECT AND THE |
| | MARKING SHALL BE SUITABLE TO THE ENVIRONMENT. NEC |
| | 225.37, NEC 110.16 |
| | - A SITE SPECIFIC PLAN IS REQUIRED THAT SHOWS THE |
| | SERVICE LOCATION PERTAINING TO THE OVERHEAD CONDUCTORS |
| | CLEARANCES IF RUNNING THROUGH A COMMERCIAL AREA SUBJECT |
| | OR NOT SUBJECT TO TRUCK TRAFFIC. NEC 230.24(B)(2) OR |
| | (4). |
| | |
| | PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| | MENTIONED DEFICIENCIES. |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE |
| | LETTER (NARRATIVE) ADDRESSING EACH ITEM ALONG WITH THE |
| | STANDARD CITY RE-SUBMITTAL FORM. THE NARRATIVE SHOULD |
| | INCLUDE THE PLAN REVIEWER?S COMMENTS AND YOUR RESPONSE |
| | OR ACTION TO SAME. |
| | ADDITIONALLY, PLEASE INSERT CORRECTED PAGES INTO THE |
| | SUBMITTAL AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARISON. CLOUDING THE CHANGES WILL BE GREATLY |
| | APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | FBC 2014 5TH ED. NEC 2011 |