| 2017-10-05 08:38:06 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2014 5TH EDITION |
| | FBC CE = FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 |
| | 5TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2014 5TH EDITION, |
| | PART VIII ELECTRICAL |
| | NEC = NFPA 70 2011 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. KITCHEN SMALL APPLIANCE CIRCUITS PROVIDED ARE SHOWN |
| | AS #14 WIRE ON A 20 AMP BREAKER. THERE ARE SEVERAL |
| | OTHER CIRCUITS IN PANEL SCHEDULE IDENTIFIED LIKE THIS. |
| | PROVIDE CORRECTION. NEC 310.15(B)(16), 334.80; FBC RE |
| | TABLE E3702.13, TABLE E3705.5.3 |
| | 2. DISHWASHER AND DISPOSAL ARE SHOWN IN PANEL SCHEDULE |
| | AS #12 WIRE ON A 30 AMP BREAKER. PROVIDE CORRECTION. |
| | NEC 310.15(B)(16), 334.80; FBC RE TABLE E3702.13, TABLE |
| | E3705.5.3 |
| | 3. BREAKER FOR WATER HEATER IS STATED AS 30 AMP IN |
| | PANEL SCHEDULE, WHICH IS TOO LARGE FOR THIS LOAD. |
| | BREAKER SHOULD BE SIZED AT 125% OF THE LOAD. BASED ON |
| | THE 4500 WATT STATED, THIS WOULD BE A MAXIMUM BREAKER |
| | SIZE OF 25 AMPS. PROVIDE CORRECTION. NEC 422.13; FBC |
| | RE3702.10 |
| | 4. THE LOAD CALCULATION PROVIDED FOR PANEL IS |
| | INCORRECT. THE DEMAND FACTORS ARE NOT APPLIED TO EVERY |
| | LOAD IN PANEL. PROVIDE CORRECTED LOAD CALCULATION AS |
| | PER THE FBC RESIDENTIAL CODE, SECTION E3602.2. INCLUDE |
| | ALL LOADS IN THIS CALCULATION. THE CURRENT PANEL |
| | SCHEDULE SHOWS ONLY 1 AHU/AC SYSTEM. NEC 220, FBC RE |
| | 3602.2 |
| | 5. THE RISER DIAGRAM PROVIDED HAS CONFLICTING |
| | INFORMATION. IT SHOWS A FEED TO A DISCONNECT AND THEN |
| | TO PANEL A WITH 2/0 WIRE. IT ALSO SHOWS A FEED DIRECTLY |
| | FROM METER TO PANEL A WITH #1 WIRE. CLARIFY AND/OR |
| | CORRECT. ADDITIONALLY, IF USING A MAIN DISCONNECT AS |
| | DRAWN, THE WIRING FROM THE DISCONNECT TO PANEL A |
| | REQUIRES AN EQUIPMENT GROUNDING CONDUCTOR. REFLECT ALL |
| | CORRECTED INFORMATION ON POWER PLAN AS WELL, IT |
| | CURRENTLY ONLY SHOWS A PANEL, NO DISCONNECT OR METER |
| | CAN. PROVIDE CORRECTION. NEC 250.122; FBC 107.2.1; FBC |
| | RE 3704.6 |
| | 6. PROVIDE CORRECTED NOTES AS FOLLOWS: "ALL RECEPTS. TO |
| | BE TAMPER PROOF AS PER NEC 2010 SEC 406.11". THE 2010 |
| | NEC DOES NOT EXIST AND SECTION 406.11 IN THE CURRENT |
| | CODE, THE 2011 NEC, DOES NOT APPLY TO TR RECEPTACLES. |
| | ALSO; "ELECTRICAL CONTRACTOR TO CONFORM TO 2008 NEC |
| | BUILDING CODES". THIS IS NOT THE CURRENT CODE. PROVIDE |
| | CORRECTIONS. FBC PREFACE, 107.2.1; NEC 406.12; FBC RE |
| | 4002.14 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | |