| 2016-08-09 14:35:54 | BUILDING PLAN REVIEW |
| | 2014 FLORIDA BUILDING CODE |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER ? PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | DATE: 8/9/16 |
| | |
| | 1. PROVIDE SITE PLAN. |
| | 2. SCOPE OF WORK EXCEEDS DESCRIPTION ON APPLICATION. |
| | STRUCTURAL CONCRETE, WALLS AND ROOFING SHOWN ON PLANS. |
| | 3. STATED VALUE MAY BE LOW. |
| | 4. ROOFING PERMIT REQUIRED. |
| | 5. PROVIDE RE-INFORCING DTAIL FOR NEW BOND BEAMS. |
| | 6. DETAIL 1, PG A-4 INDICATES NEW ROOF RAFTERS. DEMO |
| | PLANS SHOWS NO WORK IN THIS AREA.. PLEASE CLARIFY. TO |
| | WHAT EXTENT IS ROOFING BEING REMOVED? |
| | 7. PROVIDE LANDINGS AT EXTERIOR DOORS. |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE |
| | DIMENSIONED AND DRAWN UPON SUITABLE MATERIAL. |
| | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK |
| | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, |
| | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL. SUCH DRAWINGS AND SPECIFICATIONS SHALL |
| | CONTAIN INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, |
| | AS TO THE QUALITY OF MATERIALS, WHERE QUALITY IS |
| | ESSENTIAL TO CONFORMITY WITH THE TECHNICAL CODES. SUCH |
| | INFORMATION SHALL BE SPECIFIC, AND THE TECHNICAL CODES |
| | SHALL NOT BE CITED AS A WHOLE OR IN PART, NOR SHALL THE |
| | TERM "LEGAL" OR ITS EQUIVALENT BE USED AS A SUBSTITUTE |
| | FOR SPECIFIC INFORMATION. ALL INFORMATION, DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE |
| | NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN. (SEE ALSO SECTION 107.3.5). |
| | |
| | [A] 109.3 BUILDING PERMIT VALUATIONS. |
| | THE APPLICANT FOR A PERMIT SHALL PROVIDE AN ESTIMATED |
| | PERMIT VALUE AT TIME OF APPLICATION. PERMIT VALUATIONS |
| | SHALL INCLUDE TOTAL VALUE OF WORK, INCLUDING MATERIALS |
| | AND LABOR, FOR WHICH THE PERMIT IS BEING ISSUED, SUCH |
| | AS ELECTRICAL, GAS, MECHANICAL, PLUMBING EQUIPMENT AND |
| | PERMANENT SYSTEMS. IF, IN THE OPINION OF THE BUILDING |
| | OFFICIAL, THE VALUATION IS UNDERESTIMATED ON THE |
| | APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE |
| | APPLICANT CAN SHOW DETAILED ESTIMATES TO MEET THE |
| | APPROVAL OF THE BUILDING OFFICIAL. FINAL BUILDING |
| | PERMIT VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | R311.3 FLOORS AND LANDINGS AT EXTERIOR DOORS. |
| | THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH |
| | EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL NOT BE |
| | LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A |
| | MINIMUM DIMENSION OF 36 INCHES (914 MM) MEASURED IN THE |
| | DIRECTION OF TRAVEL. EXTERIOR LANDINGS SHALL BE |
| | PERMITTED TO HAVE A SLOPE NOT TO EXCEED 1/4 UNIT |
| | VERTICAL IN 12 UNITS HORIZONTAL (2-PERCENT). |
| | |
| | |
| | |