2016-08-24 14:04:41ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 PROJECT NAME: PALM BEACH ACURA
 JOB ADDRESS: 6870 OKEECHOBEE BLVD.
 DESCRIPTION: REMOVE & RELOCATE EXISTING FIRE ALARM
 DEVICES TO MATCH NEW FLOOR PLANS
 MASTER PERMIT: 15110808
 SUB-PERMIT: 16070466
  
 YOUR RESUBMITTAL ADDRESSING THE PREVIOUSLY MENTIONED
 DEFICIENCIES HAS ONCE AGAIN FAILED THE ELECTRICAL
 REVIEW AS INDICATED BELOW. NEW COMMENTS IF ANY PROMPTED
 BY ANOTHER REVIEW, MOST LIKELY DUE TO YOUR FAILURE TO
 SUBMIT A RESPONSE LETTER (NARRATIVE) ADDRESSING THE
 REQUIRED CORRECTIONS WILL BE NUMBERED IN CONTINUATION
 OF ANY PREVIOUS COMMENTS. THESE PLANS HAVE BEEN
 REVIEWED FOR COMPLIANCE WITH THE EDITION OF THE NEC,
 (NATIONAL ELECTRICAL CODE) AND THE FBC, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS IN EFFECT AT THE TIME OF SUBMITTAL AND THE
 2012 EDITION OF NFPA 72.
  
 BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS.
 ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF
 SUBMITTED CORRECTIONS.
 1. PROVIDE A COPY OF ACCEPTED CONTRACT AS PROOF OF
 DECLARED VALUATION.
 2. COMPARING THE DRAWINGS I FIND THAT THE FLOOR PLANS
 AND COMPASS ORIENTATION DIFFER. PLEASE VERIFY WHICH OF
 THE TWO IS THE CORRECT FLOOR PLAN AND COMPASS
 ORIENTATION AND INDICATE SUCH ON THE CORRECTED SET.
 3. AS PREVIOUSLY MENTIONED, FBC-B907.1.2 HAS SPECIFIC
 ITEMS THAT SHALL APPEAR ON THE SUBMITTAL BELOW ARE THE
 MISSING ITEMS.
 A) LOCATION OF PRIMARY POWER SOURCE
 B) SEQUENCE OF OPERATION
 C) CLASSIFICATION OF SUPERVISING STATION
 4. THERE IS NO NEED TO RESUBMIT THE EQUIPMENT SPEC
 SHEETS. THEY ARE KEPT IN THE PACKET AND WILL BE REUSED.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, YOU ARE REQUIRED TO PROVIDE A RESPONSE
 LETTER (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE
 NUMBER WHERE THE CORRECTIONS APPEAR ALONG WITH THE
 STANDARD CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE
 INSERT CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK
 VOID AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  