2016-07-20 11:58:116870 OKEECHOBEE BOULEVARD
 PERMIT #16070466
 MASTER #15110808
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER FBC SECTION 907.1.2 FIRE ALARM SHOP DRAWINGS.
 SHOP DRAWINGS FOR FIRE ALARM SYSTEMS SHALL BE SUBMITTED
 FOR REVIEW AND APPROVAL PRIOR TO SYSTEM INSTALLATION,
 AND SHALL INCLUDE, BUT NOT BE LIMITED TO, ALL OF THE
 FOLLOWING:
  
 1. A FLOOR PLAN THAT INDICATES THE USE OF ALL ROOMS.
  
 3. CANDELA RATINGS FOR VISIBLE ALARM NOTIFICATION
 APPLIANCES.
  
 9. VOLTAGE DROP CALCULATIONS.
  
 11. DETAILS OF CEILING HEIGHT AND CONSTRUCTION.
  
 13. CLASSIFICATION OF THE SUPERVISING STATION.
  
 THE RISER DIAGRAM PROVIDES A DEVICE NUMBER FOR EACH
 DEVICE; HOWEVER, THE FLOOR PLAN DEVICES HAVE NOT BEEN
 PROVIDED WITH IDENTIFICATION NUMBERS, CANDELA RATINGS,
 OR POINT TO POINT WIRING.
  