Plan Review Notes
Plan Review Notes For Permit 16070466
Permit Number 16070466
Review Stop E
Sequence Number 1
Notes
Date Text
2016-07-20 13:45:37ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 &
 NFPA 70 2011 (NEC)
  
 JOB NAME: PALM BEACH ACURA
 JOB ADDRESS: 6870 OKEECHOBEE BLVD..
 DESCRIPTION: REMOVE & RELOCATE F/A DEVICES TO MATCH
 FLOOR PLAN
 MAST. PERMIT: 15110808
 REVISION/SUB-PERMIT: 16070466
  
 1. IN ADDITION TO THE FIRE COMMENTS BELOW ARE
 ADDITIONAL ELECTRICAL REQUIREMENTS WHICH YOU MUST
 ADDRESS.
 2. NFPA 72 SECTION 17.14.6 REQUIRE THAT THE MANUAL PULL
 STATION DEVICE BE LOCATED NO MORE THAN 5? FROM THE EXIT
 DOORWAY.
 3. FBC-B907.1.2 HAS SPECIFIC REQUIREMENTS WHICH SHALL
 APPEAR ON THE SHOP DRAWINGS SUBMITTED FOR PERMITTING
 MANY OF WHICH ARE MISSING FROM YOUR PLANS.
 4. NFPA 72 SECTION 10.5.5.2 HAS SPECIFIC REQUIREMENTS
 RELATING TO THE FIRE ALARM BRANCH CIRCUIT. E.G.:
 MARKINGS, LOCATION IDENTIFICATION, MECHANICAL
 PROTECTION ETC.
 5. THE PLANS INCLUDE AN ITEM LABELED FSPA WHICH DOES
 NOT APPEAR ON THE LEGEND. PLEASE IDENTIFY THAT.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  