| 2016-07-20 13:45:37 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: 5TH EDITION FBC 2014 & |
| | NFPA 70 2011 (NEC) |
| | |
| | JOB NAME: PALM BEACH ACURA |
| | JOB ADDRESS: 6870 OKEECHOBEE BLVD.. |
| | DESCRIPTION: REMOVE & RELOCATE F/A DEVICES TO MATCH |
| | FLOOR PLAN |
| | MAST. PERMIT: 15110808 |
| | REVISION/SUB-PERMIT: 16070466 |
| | |
| | 1. IN ADDITION TO THE FIRE COMMENTS BELOW ARE |
| | ADDITIONAL ELECTRICAL REQUIREMENTS WHICH YOU MUST |
| | ADDRESS. |
| | 2. NFPA 72 SECTION 17.14.6 REQUIRE THAT THE MANUAL PULL |
| | STATION DEVICE BE LOCATED NO MORE THAN 5? FROM THE EXIT |
| | DOORWAY. |
| | 3. FBC-B907.1.2 HAS SPECIFIC REQUIREMENTS WHICH SHALL |
| | APPEAR ON THE SHOP DRAWINGS SUBMITTED FOR PERMITTING |
| | MANY OF WHICH ARE MISSING FROM YOUR PLANS. |
| | 4. NFPA 72 SECTION 10.5.5.2 HAS SPECIFIC REQUIREMENTS |
| | RELATING TO THE FIRE ALARM BRANCH CIRCUIT. E.G.: |
| | MARKINGS, LOCATION IDENTIFICATION, MECHANICAL |
| | PROTECTION ETC. |
| | 5. THE PLANS INCLUDE AN ITEM LABELED FSPA WHICH DOES |
| | NOT APPEAR ON THE LEGEND. PLEASE IDENTIFY THAT. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |