| Notes |
| Date |
Text |
| 2016-07-19 16:43:27 | 1ST REVIEW MECHANICAL | | | PERMIT #16070440 | | | 7/19/16 | | | | | | 1) PROVIDE A NARRATIVE FROM THE ENGINEER OF RECORD | | | ITEMIZING ALL CHANGES MADE TO THE APPROVED PLANS UNDER | | | PERMIT #15060911. IT APPEARS THAT NEW EVAPORATIVE | | | COOLING SYSTEMS HAVE REPLACED THE ORIGINAL SPLIT AIR | | | CONDITIONING SYSTEMS. PLEASE CLARIFY WHY THIS CHANGE | | | WAS MADE AND SUBMIT REVISED SYSTEM AND ENERGY | | | CALCULATIONS. IS THE SPACE NOW BEING USED FOR | | | REFRIGERATED STORAGE? | | | | | | 2) SUBMIT REVISED ELECTRICAL PLANS, AND ALL OTHER | | | BUILDING PLANS AFFECTED BY THE OCCUPANCY AND COOLING | | | SYSTEM CHANGES.CHANGES. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|