Plan Review Notes
Plan Review Notes For Permit 16070408
Permit Number 16070408
Review Stop E
Sequence Number 1
Notes
Date Text
2016-07-14 11:52:581ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 1. FBC-RE3905.6.2/NEC 314.27(A) LUMINAIRE OUTLETS.
 BOXES USED AT LUMINAIRE OR LAMPHOLDER OUTLETS IN A
 CEILING SHALL BE REQUIRED TO SUPPORT A LUMINAIRE
 WEIGHING A MINIMUM OF 50 LB. ADD THIS TO THE NOTES ON
 CEILING BOXES ON PAGE.
 2. FBC-RE3905.8/NEC 314.27(D) PADDLE FANS. BOXES USED
 FOR THE SOLE SUPPORT OF CEILING FANS SHALL BE MARKED BY
 THE MANUFACTURER AS SUITABLE FOR THE PURPOSE, AND
 INDICATE THE WEIGHT LIMITATIONS BUT SHALL NOT BE USED
 TO SUPPORT PADDLE FANS HEAVIER THAN 70 LBS.
 3. FBC-R4001.15/NEC 404.2(C). WHERE SWITCHES
 CONTROLLING LIGHTING LOADS SUPPLIED BY A GROUNDED
 BRANCH CIRCUIT, THE GROUNDED BRANCH CIRCUIT CONDUCTOR
 FOR THE CONTROLLED LIGHTING CIRCUIT SHALL BE PROVIDED
 AT THE SWITCH.
 4. FBC-RE3901.2.1/NEC 210.52 (A)(1) SPACING.
 RECEPTACLES SHALL BE INSTALLED SUCH THAT NO POINT
 MEASURED HORIZONTALLY ALONG THE FLOOR LINE IN ANY WALL
 SPACE IS MORE THAN 6 FT. FROM A RECEPTACLE OUTLET. THIS
 INCLUDES THE DISTANCE FROM THE EDGE OF THE WALL. THERE
 ARE MISSING OUTLETS BOTH IN THE MASTER BEDROOM AND
 ALONG THE NEW WALL OF THE DINING AREA.
 5. FBC-RE3901.6/NEC 210.52(D) BATHROOMS. IN DWELLING
 UNITS, AT LEAST ONE RECEPTACLE OUTLET SHALL BE
 INSTALLED IN BATHROOMS WITHIN 3 FT. OF THE OUTSIDE EDGE
 OF EACH BASIN. MISSING OUTLET IN THE GUEST BATHROOM.
 6. FBC-R314: IF NOT ALREADY COMPLIANT WITH THE LATEST
 SMOKE DETECTOR REQUIREMENTS, THIS ARTICLE REQUIRES THAT
 YOU COME INTO COMPLIANCE WITH THE LATEST REQUIREMENTS
 AS IF NEW CONSTRUCTION.
 7. NFPA 72 SECTION 18.4.5: ASCERTAIN CONTINUED
 COMPLIANCE WITH THE FIRE ALARM NOTIFICATION
 REQUIREMENTS OF THIS SECTION.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  