Plan Review Notes
Plan Review Notes For Permit 16070383
Permit Number 16070383
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-07-13 15:01:301721 PALM BEACH LAKES BOULEVARD - SUITE E419
 PERMIT #16070383
 MASTER #15110510
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE ADDRESS PROVIDED ON THE PLANS (1741 PALM BEACH
 LAKES BLVD) DOES NOT MATCH THE ADDRESS PROVIDED ON THE
 PERMIT APPLICATION (1721 PALM BEACH LAKES BLVD - SUITE
 E419).
  
 PROVIDE AN EXTERIOR HORN-STROBE DEVICE FOR THE EXTERIOR
 SEATING AREA.
  
 PROVIDE A HORN-STROBE DEVICE INSIDE COOLER #117.
  
 REVISE RISER DIAGRAM WITH DEVICES ADDED FROM PREVIOUS
 COMMENT.
  
 NOTE: OUTLET MALL FIRE ALARM DESIGN REQUIRES THE ENTIRE
 BUILDING (NOT JUST THE SUITE) TO GO INTO GENERAL ALARM
 MODE.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
  
  