| Plan Review Notes For Permit 16070380 |
| Permit Number |
16070380 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2016-08-19 13:55:47 | COMPLY WITH THE PLUMBING REVIEW COMMENTS FROM THE | | | 7/31/16 REVIEW. | | | 1) THE SHOWER SHALL BE NOT LESS THAN 30 INCHES WIDE IN | | | THE LEAST DIMENSION AND SHALL BE A MINIMUM OF 900 | | | SQUARE INCHES.SHOWER COMPARTMENTS NOT LESS THAN 25 | | | INCHES IN MINIMUM DIMENSIONS SHALL BE A MINIMUM OF 1300 | | | SQUARE INCHES. 2014 FBC-PLUMBING SEC.417.4.THE PLANS | | | SHOW THE MASTER BATH SHOWER WITH A DIMENSION OF 24 | | | INCHES AT ONE END. | | | 2) INDICATE ON THE PLAN IF ANY OF THE OTHER PLUMBING | | | FIXTURES ARE BEING RELOCATED.WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | | | | PLUMBING PLAN REVIEW | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | 561-805-6692 | | | [email protected] | | | | | | |
|