Plan Review Notes
Plan Review Notes For Permit 16070380
Permit Number 16070380
Review Stop E
Sequence Number 1
Notes
Date Text
2016-07-14 10:14:18REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
 - PROVIDE AN ELECTRICAL FLOOR PLAN SHOWING LOCATIONS OF
 SMOKE DETECTORS, KITCHEN COUNTERTOP GFCI, BATHROOM
 GFCI, LIGHTING IN ALL AREAS WITHIN THE SCOPE OF WORK.
 FBC 107 MINIMUM PLAN REVIEW.
  
 - FBC R E3901.2.4 COUNTERTOP RECEPTACLES, FBC R E3901.3
 SMALL APPLIANCE RECEPTACLES, FBC R E3902.6 KITCHEN
 RECEPTACLES, FBC R E3902.1 BATHROOM RECEPTACLES.
  
 - SMOKE DETECTORS SHALL BE INSTALLED PER RESIDENTIAL
 CODE SECTIONS 314 & 315. ALL NEW RECEPTACLES SHALL BE
 TAMPER RESISTANT IN ACCORDANCE WITH FBC R E4002.14
  