| 2016-07-18 14:50:07 | 1ST REVIEW MECHANICAL | | | PERMIT #16040538 | | | 7/18/16 | | | | | | 1) EXHAUST HOODS ARE REQUIRED FOR THE RELOCATED Q'ING | | | OVEN, AND THE NEW WAREWASHER- REFER TO SECTION 507.1 | | | AND 507.2.2. PLEASE NOTE THAT SEPARATE PERMITS ARE | | | REQUIRED FOR KITCHEN EXHAUST HOODS AND FIRE SUPPRESSION | | | SYSTEMS. | | | | | | 2) REFER TO SECTION 809.1, 809.2, & 809.3 FBC-14 | | | EXISTING BUILDING CODE AND PROVIDE MINIMUM VENTILATION | | | CALCULATIONS FOR THE ALTERED KITCHEN IN COMPLIANCE WITH | | | TABLE 403.3 FBC-14 MECHANICAL. PLEASE NOTE AN EXHAUST | | | RATE OF 0.7 CFMS IS REQUIRED- INDICATE HOW THAT | | | REQUIREMENT IS BEING MET. | | | | | | 3) THE KITCHEN PLANS INDICATE A NEW ELECTRIC CLAMSHELL | | | GRILL AND A CHEESE PAN HOLDER ARE BEING LOCATED OUTSIDE | | | OF THE EXHAUST HOOD. CLARIFY IF THIS AN EXISTING OR NEW | | | HOOD, AND NOTE IT IN THE SCHEDULE AND ON THE PLANS. | | | | | | 4) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE NEW | | | ELECTRIC CLAMSHELL GRILL AND CHEESEHOLDER, AND THE | | | RELOCATED Q'ING OVEN. | | | | | | 5) PROVIDE AN AIR DEVICE SCHEDULE. | | | | | | 6) THE COMCHECK SUBMITTAL HAS A COPY OF A DIGITAL | | | SIGNATURE, HOWEVER THIS PLAN WAS NOT SUBMITTED | | | ELECTRONICALLY. IN ACCORDANCE WITH SECTION 61G15- | | | 23.002 FAC. THE ENGINEER MUST PROVIDE AN ORIGINAL | | | SIQNATURE AND SEAL. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | | | | |
|