Plan Review Notes
Plan Review Notes For Permit 16070373
Permit Number 16070373
Review Stop B
Sequence Number 1
Notes
Date Text
2016-07-21 14:48:34BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16070373
 ADD: 4275 45TH ST.
 CONT: NUNNO BUILDERS
 TEL: 954-961-0777
 E-MAIL:
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. JULY 21/ 2016
 ACTION: DENIED
  
 1) PLEASE NOTE SHEET T1.0 UPPER CENTER PORTION OF PLANS
 THE JOBSITE LOCATION GIVEN: MIAMI REGION. 14670 SW 8TH
 ST. MIAMI, MIAMI-DADE COUNTY, FL.
 AND ON THE RIGHT SIDE OF THE PAGE IN THE TITLE BLOCK
 THE ADDRESS OF 4275 45TH ST. WEST PALM BEACH, FL.
 PLEASE CORRECT THE DISCREPANCY IN ADDRESSES.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE
 WORK. DISCREPANCY IN PLANS.
  
 2) SHEET T1.0 THE BUILDING DATA UNDER THE OCCUPANCY
 GROUP LIST THIS AS A: C5.1 PLEASE NOTE THIS IS NOT A
 OCCUPANCY CLASS FOUND IN THE 2014 FBC-B CHAPTER 3.
  
 3) SHEET T1.0 UNDER THE HEADING OF BUILDING DATA LIST
 THIS BUILDING AS CLASSIFICATION TYPE AS IIB. PLEASE
 NOTE ALL PERMIT PULLED IN THE PAST LIST THE BUILDING AS
 A TYPE VB? ADDITIONAL INFORMATION IS REQUIRED.
 107.2.1.3.
  
 4) PLEASE NOTE ALL OF THE ARCHITECTURAL SHEETS SIGNED
 BY NICK JONIHAKIS ARE COPIES OF SIGNATURES YOU CAN SEE
 THE PIXALATION IN THE SIGNATURE.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. FL ADMIN
 CODE 61G16.003 ARCHITECTS. PLANS ARE TO BE SIGNED WITH
 A FULL SIGNATURE FROM THE ARCHITECT OF RECORD PER
 481.221 WITH A MINIMUM OF FIRST AND LAST NAME AS SHOWN
 ON THE ARCHITECTS' LICENSE, FAC 61G1-16.003.
  
 5) THE COMCHECK SUBMITTED HAS A COPY OF AN ELECTRONIC/
 DIGITAL SIGNATURE. 61G15-23.005 PROCEDURES FOR SIGNING
 AND SEALING ELECTRONICALLY TRANSMITTED PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
  
 6) SHEET A1.0 NOTES 1 & 4 INDICATE NEW MODULAR
 COUNTERS, SHEET A1.1 SHOWS CUT SECTION THROUGH THESE
 UNITS. THE PLANS DO NOT SHOW COMPLIANCE WITH THE 2014
 FBC-ACCESS. CODE:
  
 904.4 SALES AND SERVICE COUNTERS. SALES COUNTERS AND
 SERVICE COUNTERS SHALL COMPLY WITH 904.4.1 OR 904.4.2.
 THE ACCESSIBLE PORTION OF THE COUNTER TOP SHALL EXTEND
 THE SAME DEPTH AS THE SALES OR SERVICE COUNTER TOP.
 EXCEPTION: IN ALTERATIONS, WHEN THE PROVISION OF A
 COUNTER COMPLYING WITH 904.4 WOULD RESULT IN A
 REDUCTION OF THE NUMBER OF EXISTING COUNTERS AT WORK
 STATIONS OR A REDUCTION OF THE NUMBER OF EXISTING MAIL
 BOXES, THE COUNTER SHALL BE PERMITTED TO HAVE A PORTION
 WHICH IS 24 INCHES (610 MM) LONG MINIMUM COMPLYING WITH
 904.4.1 PROVIDED THAT THE REQUIRED CLEAR FLOOR OR
 GROUND SPACE IS CENTERED ON THE ACCESSIBLE LENGTH OF
 THE COUNTER.
  
 904.4.1 PARALLEL APPROACH. A PORTION OF THE COUNTER
 SURFACE THAT IS 36 INCHES (915 MM) LONG MINIMUM AND 36
 INCHES (915 MM) HIGH MAXIMUM ABOVE THE FINISH FLOOR
 SHALL BE PROVIDED. A CLEAR FLOOR OR GROUND SPACE
 COMPLYING WITH 305 SHALL BE POSITIONED FOR A PARALLEL
 APPROACH ADJACENT TO THE 36 INCH (915 MM) MINIMUM
 LENGTH OF COUNTER. EXCEPTION: WHERE THE PROVIDED
 COUNTER SURFACE IS LESS THAN 36 INCHES (915 MM) LONG,
 THE ENTIRE COUNTER SURFACE SHALL BE 36 INCHES (915 MM)
 HIGH MAXIMUM ABOVE THE FINISH FLOOR.
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION
 DEVELOPMENT SERVICES DEPARTMENT
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  