| Plan Review Notes For Permit 16070370 |
| Permit Number |
16070370 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2016-07-19 15:59:53 | 1ST REVIEW MECHANICAL | | | PERMIT #16070370 | | | 7/19/16 | | | | | | 1) THE EXHAUST SYSTEMS FOR THE NEW GAS DRYERS SHALL BE | | | DONE IN ACCORDANCE WITH THE MANUFACTURER'S | | | SPECIFICATIONS. PLEASE PROVIDE PRODUCT SUBMITTALS | | | APPROVED WITH SIGNATURE BY THE EOR. REFER TO SECTION | | | 504.7 AND PROVIDE COMPLETE DETAILS INCLUDING EXHAUST | | | DUCT SIZES AND GAGE OF STEEL, LENGTH OF DUCT RUNS, | | | LOCATIONS OF CLEANOUTS, SEQUENCE OF OPERATION FOR | | | MULTIPLE INSTALLATIONS (IF APPLICABLE), CLEARANCE TO | | | COMBUSTIBLES, PLEASE NOTE THAT REUSE OF EXISTING | | | EXHAUST DUCTS OR REPLACEMENT WITH THE SAME TYPE MAY NOT | | | BE COMPLIANT WITH MANUFACTURER'S SPECIFICATIONS. | | | | | | 2) INDICATE HOW COMBUSTION AIR IS BEING PROVIDED FOR | | | THE GAS DRYERS AND PROVIDE CALCULATIONS- SECTION 304 | | | FBC-14 FUEL GAS. PLEASE NOTE THAT REUSE OF EXISTING | | | DUCTS, WHERE NOTED ON THE PLAN, MAY NOT BE COMPLIANT | | | WITH MANUFACTURER'S SPECS. | | | | | | 3) SUBMIT TWO COPIES OF THE MIAMI-DADE NOA #13-1017.09 | | | FOR THE AC STAND. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 561-805-6719 | | | [email protected] | | | |
|