Plan Review Notes
Plan Review Notes For Permit 16070366
Permit Number 16070366
Review Stop E
Sequence Number 1
Notes
Date Text
2016-07-14 11:04:071ST ELECTRICAL REVIEW NOTES
 REVIEWED FOR COMPLIANCE WITH:
 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC)
  
 1. SHEET E101: PER FBC-EC405.7 A MINIMUM OF 50% OF ALL
 15 & 20 AMP RECEPTACLES SHALL BE AUTOMATICALLY
 CONTROLLED AS INDICATED IN ASHRAE 90.1 SECTION 8.4.2.
 THIS INCLUDES MODULAR PARTITIONS.
 2. SHEET E102: FBC-E C405.2.2. PROVIDE AUTOMATIC
 LIGHTING SHUTOFF.
 3. FBC-E C402.4.8 RECESSED LIGHTING. RECESSED LIGHTING
 INSTALLED IN THE BUILDING THERMAL ENVELOPE SHALL BE IC
 RATED AND BE SEALED TO LIMIT AIR LEAKAGE BETWEEN
 CONDITIONED & NCONDITIONED SPACES.
 4. FBC-E C405.5. INTERIOR LIGHTING POWER REQUIREMENTS.
 A BUILDING COMPLIES WITH THIS SECTION IF ITS TOTAL
 CONNECTED LIGHTING POWER CALCULATED UNDER SECTION
 C405.5.1 IS NO GREATER THAN THE INTERIOR LIGHTING POWER
 CALCULATED UNDER SECTION C405.5.2. PROVIDE A LIGHTING
 POWER DENSITY CHART TO SHOW COMPLIANCE.
 5. FBC-EC405.2.2.3 DAYLIGHT ZONE CONTROL: DAYLIGHT
 ZONES SHALL BE DESIGNED SUCH THAT LIGHTS IN THE
 DAYLIGHT ZONE ARE CONTROLLED INDEPENDENTLY OF GENERAL
 AREA LIGHTING AND ARE CONTROLLED IN ACCORDANCE WITH
 EITHER SECTION C405.2.2.3.1 OR SECTION C405.2.2.3.2.
 6. SHEET E103: NEC 110.16 ARC-FLASH HAZARD WARNING:
 ELECTRICAL EQUIPMENT IN OTHER THAN DWELLING UNITS
 LIKELY TO REQUIRE SERVICED WHILE ENERGIZED SHALL BE
 FIELD MARKED TO WARN AGAINST POTENTIAL ARC-FAULT
 HAZARDS.
 7. NEC 110.24 THE MAXIMUM AVAILABLE FAULT CURRENT
 DURABLY MARKED AND DATED ON ALL NON-DWELLING ELECTRICAL
 APPARATUS.
  
 WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR
 RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER
 WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID
 AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR
 COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE
 GREATLY APPRECIATED.
  
 IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO
 CONTACT ME DIRECTLY.
  
 THANK YOU,
 MIKE ALBARRAN
 ELECTRICAL PLANS EXAMINER
 PH: 561-805-6746
 EMAIL: [email protected]
  