| 2016-12-08 15:00:57 | RESIDENTIAL (R3) ALTERATIONS THIRD BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: FBC-5TH EDITION (2014). |
| | |
| | |
| | NOTE: |
| | ENGINEER OF RECORD MAY BE CHARGED FOUR TIMES THE PLAN |
| | REVIEW FEE IF PLANS ARE DENIED THREE OR MORE TIMES AS |
| | REQUIRED BY FLORIDA STATUTE 553.80(2)(B). |
| | |
| | |
| | 1- SURVEY SUBMITTED SHOWS 2.7' SETBACK FROM THE |
| | PROPERTY LINE ON THE WEST SIDE. ACCORDING TO TABLE |
| | R302.1(1) FBC-RESIDENTIAL, 5TH EDITION (2014) NEED THE |
| | FOLLOWING: |
| | A) OPENINGS ARE NOT ALLOWED. |
| | RESPONSE: LAUNDRY WINDOW ON THE WEST WALL WAS REMOVED |
| | BUT A NEW OPENING WAS CREATED FOR THE NEW A/C. NO |
| | OPENINGS ARE ALLOWED. NEED TO KEEP ONE HOUR FIRE RATING |
| | ON THE WALL. A/C UNIT WILL BRAKE THE FIRE RATING OF THE |
| | ASSEMBLY. REVISE AS REQUIRED. |
| | |
| | B) NEED 1 HOUR FIRE RESISTANCE WALL WITH EXPOSURE ON |
| | BOTH SIDES OF THE WEST SIDE WALL. REVISE PLANS AS |
| | REQUIRED. PROVIDE FIRE RATED WALL DETAIL AND |
| | SPECIFICATIONS. |
| | RESPONSE: REPEAT COMMENT. ENGINEER OF RECORD NEEDS TO |
| | PROVIDE WALL ASSEMBLY DETAIL AND SPECIFICATIONS. |
| | INFORMATION WAS NOT PROVIDED. NOTE: NEED TO SPECIFY |
| | ASSEMBLY TESTED IN ACCORDANCE WITH ASTM E119 OR UL 263 |
| | WITH EXPOSURE FROM BOTH SIDES. |
| | |
| | 2- PROVIDE COMPLETE INFORMATION SHOWING COMPLIANCE WITH |
| | THE REQUIRED HEATING FOR HABITABLE SPACES. SEC. R303.9 |
| | FBC-RESIDENTIAL. |
| | RESPONSE: WALL A/C UNIT WITH HEAT LOCATED ON THE WEST |
| | WALL IS NOT ALLOWED. SEE ITEM #1(A) ABOVE. REVISE AS |
| | REQUIRED. |
| | |
| | 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| | CONTRACTOR OVERHEAD AND PROFIT AND ALL DESIGN |
| | PROFESSIONAL FEES AS REQUIRED BY SEC. 109.3 CITY |
| | AMENDMENTS. |
| | RESPONSE: REPEAT COMMENT. NOT ADDRESSED AT ALL. PROVIDE |
| | COPY OF SIGNED CONTRACT FOR THE CONSTRUCTION AND COPY |
| | OF CONTRACT FOR THE DESIGN PROFESSIONAL. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | FAC 61G20-3.002(33) FOR: |
| | A) BARN DOORS AS SHOWN ON PLANS. |
| | RESPONSE: REPEAT COMMENT. REVIEW IS NOT ONLY FOR |
| | HISTORIC. BUILDING REVIEW IS REQUIRED AS WELL. IF THERE |
| | IS NOT PRODUCT APPROVAL, THEN PROVIDE COMPLETE SITE |
| | SPECIFIC ENGINEERING ANALYSIS FOR BUILDING OFFICIAL |
| | REVIEW AND APPROVAL. |
| | |
| | 5- ENGINEER OF RECORD TO REVIEW/APPROVE ABOVE PRODUCT |
| | APPROVAL AS REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |