| 2016-10-26 10:18:28 | 2ND ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | JOB ADDRESS: 814 CLAREMORE DR. |
| | DESCRIPTION: CONVERT EXISTING GARAGE INTO LIVING SPACES |
| | MASTER PERMIT: 16070342 |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | |
| | NOW THAT THE PROPOSED WORK HAS BEEN APPROVED BY ZONING |
| | WE CAN PRECEDE WITH THE ELECTRICAL REQUIREMENTS FOR A |
| | SUCCESSFUL ELECTRICAL PLAN REVIEW. |
| | 1. YOU WERE ASKED TO MARK ON A SITE PLAN THE LOCATION |
| | OF THE ELECTRICAL SERVICE POLE SERVICE THE PREMISES. |
| | YOU WERE TO ALSO INDICATE THE LOCATION OF THE |
| | ELECTRICAL METER/S AND MAIN DISCONNECT/S. FURTHERMORE |
| | YOU WERE TOLD TO SHOW HOW THE GARAGE IS SERVED |
| | ELECTRICALLY. |
| | 2. THE ELECTRICAL FLOOR PLAN IS MISSING THE REQUIRED |
| | LIGHTING ABOUT THE ELECTRICAL PANEL (NEC 110.26(D)). |
| | THERE IS A MISSING OUTLET BELOW THE ELECTRICAL PANEL |
| | (NEC 210.52(A)(2)). YOU SHALL MARK THE LOCATION OF THE |
| | WATER HEATER AND THE A/C. |
| | 3. YOU WERE PREVIOUSLY INFORMED THAT WITH THIS |
| | CONVERSION YOU WILL HAVE TO PROVIDE HEAT TO THESE |
| | PREMISES. THIS CAN?T BE WITH PORTABLE UNITS. YOU WILL |
| | HAVE TO INDICATE IF THE PROPOSED A/C UNIT IS REVERSE |
| | CYCLE AND PLACE IT STRATEGICALLY TO HEAT THE ENTIRE |
| | AREA OR PROVIDE ADDITIONAL PERMANENT HEATING. THIS |
| | ADDITIONAL LOAD SHALL BE INCLUDED IN THE RISER DIAGRAM |
| | AND LOAD CALCS. |
| | 4. THE ELECTRICAL RISER DIAGRAM AS PRESENTED DOES NOT |
| | ANSWER THE QUESTION. YOU SHALL PROVIDE A RISER DIAGRAM |
| | THAT INCLUDES THE MAIN PANEL W/ITS RESPECTIVE LOAD AS |
| | WELL AS THE SUB PANEL AND ITS LOAD. YOU SHALL INDICATE |
| | IF THE PANELS ARE MAIN BREAKER TYPE OR MAIN LUG ONLY |
| | AND THERE IS A SEPARATE MAIN DISCONNECT. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |