| 2016-08-24 18:31:08 | ELECTRICAL REVIEW NOTES |
| | REVIEWED FOR COMPLIANCE WITH: |
| | 5TH EDITION FBC 2014 & NFPA 70 2011 (NEC) |
| | |
| | PROJECT NAME: GARAGE REMODEL |
| | JOB ADDRESS: 314 ARDMORE DR. |
| | DESCRIPTION: INTERIOR RENOVATIONS OF REAR BLDG. |
| | MASTER PERMIT: 16070342 |
| | |
| | BELOW PLEASE FIND A LIST OF REQUIRED CORRECTIONS. |
| | ADDITIONAL CORRECTIONS MAY BE REQUIRED AFTER REVIEW OF |
| | SUBMITTED CORRECTIONS. |
| | |
| | PER THE NEC AND THE FBC-R YOU SHALL PROVIDE THE |
| | FOLLOWING FOR A SUCCESSFUL ELECTRICAL PLAN REVIEW: |
| | |
| | 1. A SITE PLAN SHOWING THE LOCATION OF THE FPL UTILITY |
| | POLE SERVING THE PROPERTY; THE ELECTRICAL SERVICE DROP |
| | TO THE METER. YOU SHALL ALSO INDICATE HOW THE ELECTRIC |
| | SERVICE GETS TO THE REAR STRUCTURE. |
| | 2. YOU SHALL SUBMIT AN ELECTRICAL PAGE SHOWING THE |
| | REQUIRED ELECTRICAL RECEPTACLES AND LIGHTING OUTLETS. |
| | SHOW ALL EXISTING OUTLETS AS WELL AS THE PROPOSED AND |
| | ARK THEM ACCORDINGLY. |
| | 3. YOU SHALL INCLUDE ON THE DRAWINGS AT A MINIMUM A |
| | BLOCK NOTE ADDRESSING THE GFI, ARC-FAULT, |
| | TAMPER-RESISTANT OUTLETS AND SMOKE DETECTORS. |
| | 4. NO THAT THE GARAGE IS BEING CONVERTED INTO HABITABLE |
| | SPACE, THE FBC-R REQUIRES THAT HEAT BE PROVIDED. |
| | 5. YOU SHALL INCLUDE AN ELECTRICAL SERVICE RISER |
| | DIAGRAM TO SHOW THAT THE EXISTING SERVICE IS CAPABLE OF |
| | ABSORBING THE ADDED LOADS. |
| | 6. ADDITIONAL COMMENTS MAY ARISE DUE TO DEFICIENT |
| | SUBMITTAL DOCUMENTS. |
| | |
| | WHEN RESUBMITTING, FOR A QUICKER RETURN ON YOUR |
| | RE-SUBMITTAL, PLEASE PROVIDE A RESPONSE LETTER |
| | (NARRATIVE) ADDRESSING EACH ITEM AND THE PAGE NUMBER |
| | WHERE THE CORRECTIONS APPEAR ALONG WITH THE STANDARD |
| | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PAGES INTO THE SUBMITTAL PACKAGE. MARK VOID |
| | AND LEAVE THE PREVIOUSLY REVIEWED SHEETS FOR |
| | COMPARATIVE REVIEW. CLOUDING THE CHANGES WILL BE |
| | GREATLY APPRECIATED. |
| | |
| | IF YOU HAVE FURTHER QUESTIONS, PLEASE DON?T HESITATE TO |
| | CONTACT ME DIRECTLY. |
| | THANK YOU, |
| | MIKE ALBARRAN |
| | ELECTRICAL PLANS EXAMINER |
| | PH: 561-805-6746 |
| | EMAIL: [email protected] |
| | |
| 2016-07-13 17:52:38 | 7/13/16 THE PROPOSED SCOPE OF WORK HAS TO GO BEFORE |
| | ZONING BEFORE ANY TRADE REVIEW. |